Individually and Overall Screened Instrumentation Cable
Individually and overall screened instrumentation cable combines separately foil-screened twisted pairs with a second overall foil screen for 75 V signal circuits. Rated voltage: 75 V Nominal signal conductor area: 0.5 mm² Signal conductor construction: 7 × 0.29 mm tinned copper DC conductor resistance: 42 Ω/km Characteristic impedance: 70 Ω at 10 MHz
- Rated voltage75 V
- Nominal signal conductor area0.5 mm²
- Signal conductor construction7 × 0.29 mm tinned copper
- DC conductor resistance42 Ω/km
- Characteristic impedance70 Ω at 10 MHz
- Typical operating capacitance85 nF/km
- Operating temperature-20 to +70 °C
- Pairs × (signal + drain) × mm²Nominal OD (mm)
Individually and Overall Screened Signal & Bus Architecture
- Type: Industrial Cables
- Rated voltage: 75 V
- Nominal signal conductor area: 0.5 mm²
- Signal conductor construction: 7 × 0.29 mm tinned copper
Impedance, Attenuation & Operating Limits
- DC conductor resistance: 42 Ω/km
- Characteristic impedance: 70 Ω at 10 MHz
- Typical operating capacitance: 85 nF/km
- Operating temperature: -20 to +70 °C
- Pairs × (signal + drain) × mm²: Nominal OD (mm
Individually and Overall Screened Pair Twist, Foil & Braid Construction
The representative four-pair section shows eight insulated cores, four individual pair screen boundaries and one overall screen. It contains no copper braid or steel armor. The diagram separates the drain positions for identification.
- Signal conductors: Tinned copper, nominal 0.5 mm²; 7 × 0.29 mm.
- Insulation / identification: PE; nominal insulated diameter 1.6 mm; blue/red selected pair construction.
- Individual pair screen: Aluminum/polyester foil, tinned-copper drain wire and polyester wrapping.
- Overall screen: Aluminum/polyester foil with a separate drain wire.
- Outer sheath: PVC or low-smoke halogen-free flame-retardant compound.
Signal Integrity, Crosstalk & Noise Rejection
- Installation and connection: Use the equipment bonding and EMC design to define screen connections.
- Count signal cores and screen connections separately: The representative four-pair build has eight insulated signal conductors and five screen-drain connections: one for each pair and one for the overall screen.
- Operating temperature: -20 to +70 °C
- Pairs × (signal + drain) × mm²: Nominal OD (mm
Process Plant, Moisture, UV & Chemical Protection
- Selection point: Information to specify
- Pair screen allocation: Screening requirement of each instrument loop
- Drain identification: Four pair drains plus one overall drain in the illustrated four-pair build
- Terminal enclosure: Pair count, finished OD and screen-tail space
EN 50288 / PAS 5308 / Fieldbus Protocol Standards
- Reference / performance: Applicable condition
- IEC 60332-1: Single-cable flame-retardance reference for the specified construction.
- Individual plus overall foil screening: Separate screen boundaries and drain connections as listed in Construction.
- 75 V instrumentation duty: Use the specified operating voltage, temperature and pair data for the selected build.
Instrumentation & Industrial Bus Guides

Individually and Overall Screened Process Control & Telemetry Topology
Individually and overall screened instrumentation cable combines separately foil-screened twisted pairs with a second overall foil screen for 75 V signal circuits. Seven-wire tinned-copper conductors and PE insulation form the selected blue/red pair construction, with PVC or low-smoke halogen-free flame-retardant outer sheath options.
The individual screens establish a separate boundary around each pair, while the overall screen surrounds the complete assembly. That arrangement requires a clear termination schedule for both levels. Pair drain wires and the overall drain are connection elements of the screen system; they are additional to the two insulated signal conductors in each pair.
DCS, PLC, Fieldbus & Sensor Network Routes
- For instrumentation and process-control signal circuits where both pair-level screening and an overall screen are specified.
- Selection point: Information to specify
- Pair screen allocation: Screening requirement of each instrument loop
- Drain identification: Four pair drains plus one overall drain in the illustrated four-pair build
- Terminal enclosure: Pair count, finished OD and screen-tail space
Installation and connection
Use the equipment bonding and EMC design to define screen connections. Two screening levels alone do not establish the installed interference result; routing, terminations and the connected instrument remain part of the complete circuit.
Individually and Overall Screened Impedance, Grounding & Bus FAQ
How does Individually and Overall Screened Instrumentation Cable handle installation and connection in field installations?
Use the equipment bonding and EMC design to define screen connections. Two screening levels alone do not establish the installed interference result; routing, terminations and the connected instrument remain part of the complete circuit.
Why is 'Count signal cores and screen connections separately' critical when specifying Individually and Overall Screened Instrumentation Cable?
The representative four-pair build has eight insulated signal conductors and five screen-drain connections: one for each pair and one for the overall screen. Its typical cable capacitance over 100 m is about 8.5 nF per applicable circuit at 85 nF/km. Both checks help size the termination and review instrument loading.
What layer-by-layer materials and screening options define Individually and Overall Screened Instrumentation Cable?
Signal conductors: Tinned copper, nominal 0.5 mm²; 7 × 0.29 mm.; Insulation / identification: PE; nominal insulated diameter 1.6 mm; blue/red selected pair construction.; Individual pair screen: Aluminum/polyester foil, tinned-copper drain wire and polyester wrapping.; Overall screen: Aluminum/polyester foil with a separate drain wire.; Outer sheath: PVC or low-smoke halogen-free flame-retardant compound.
What operating voltage, test voltage, and bend-space allowances apply to Individually and Overall Screened Instrumentation Cable?
Rated voltage: 75 V; Nominal signal conductor area: 0.5 mm²; Signal conductor construction: 7 × 0.29 mm tinned copper; DC conductor resistance: 42 Ω/km; Characteristic impedance: 70 Ω at 10 MHz
Nominal selection data for the listed constructions. D means the finished cable outside diameter. Match the complete configuration and test conditions to the ordered cable.
TEBAOFLEX® — Individually and Overall Screened Instrumentation Cable Construction, Operating & Compliance Matrix
| Cable Element / Layer | Selected Construction | Operating Parameter / Condition | Normative Reference & Test Scope |
|---|---|---|---|
| Signal conductors | Tinned copper, nominal 0.5 mm²; 7 × 0.29 mm. | Rated voltage: 75 V | IEC 60332-1 — Single-cable flame-retardance reference for the specified construction. |
| Insulation / identification | PE; nominal insulated diameter 1.6 mm; blue/red selected pair construction. | Nominal signal conductor area: 0.5 mm² | Individual plus overall foil screening — Separate screen boundaries and drain connections as listed in Construction. |
| Individual pair screen | Aluminum/polyester foil, tinned-copper drain wire and polyester wrapping. | Signal conductor construction: 7 × 0.29 mm tinned copper | 75 V instrumentation duty — Use the specified operating voltage, temperature and pair data for the selected build. |
| Overall screen | Aluminum/polyester foil with a separate drain wire. | DC conductor resistance: 42 Ω/km | IEC 60332-1 — Single-cable flame-retardance reference for the specified construction. |
| Outer sheath | PVC or low-smoke halogen-free flame-retardant compound. | Characteristic impedance: 70 Ω at 10 MHz | Individual plus overall foil screening — Separate screen boundaries and drain connections as listed in Construction. |
TEBAOFLEX® — Individually and Overall Screened Instrumentation Cable technical parameters
| Parameter | Value / condition |
|---|---|
| Rated voltage | 75 V |
| Nominal signal conductor area | 0.5 mm² |
| Signal conductor construction | 7 × 0.29 mm tinned copper |
| DC conductor resistance | 42 Ω/km |
| Characteristic impedance | 70 Ω at 10 MHz |
| Typical operating capacitance | 85 nF/km |
| Operating temperature | -20 to +70 °C |
TEBAOFLEX® — Individual and overall screen configurations
| Pairs × (signal + drain) × mm² | Nominal OD (mm) |
|---|---|
| 1 × (2 + 1) × 0.5 | 5.5 |
| 2 × (2 + 1) × 0.5 | 7.5 |
| 4 × (2 + 1) × 0.5 | 9.7 |
| 8 × (2 + 1) × 0.5 | 12.9 |
| 12 × (2 + 1) × 0.5 | 14.5 |
| 16 × (2 + 1) × 0.5 | 16.2 |
| 24 × (2 + 1) × 0.5 | 20.1 |
Count signal cores and screen connections separately
The representative four-pair build has eight insulated signal conductors and five screen-drain connections: one for each pair and one for the overall screen. Its typical cable capacitance over 100 m is about 8.5 nF per applicable circuit at 85 nF/km. Both checks help size the termination and review instrument loading.
Selection guide: A designation such as four pairs still means eight insulated signal cores; it does not include drain wires in that count. Keep foil screens and drain connections continuous according to the instrument bonding plan, with room to maintain pair identification at each termination.
Ordering & Quotation Checklist: Send the complete configuration, circuit requirements, length, quantity, installation duty and required test documents. Include the equipment drawing and the relevant environmental or movement conditions.