IRAM 2178-2 (3.3–33 kV) & ICEA S-93-639 (5–35 kV) Medium-Voltage XLPE Cable
IRAM 2178-2 (1.9/3.3 kV, 3.8/6.6 kV, 7.6/13.2 kV, 13.2/22.8 kV & 19/33 kV Category I & II), IEC 60502-2 (3.6/6 kV to 18/30 kV) and ICEA S-93-639 / NEMA WC 74 (5 kV, 8 kV, 15 kV, 25 kV & 35 kV at 100% and 133% insulation levels) are single-core and three-core medium-voltage copper-screened XLPE power cables. Manufactured with triple-extruded dry-cured 90 °C XLPE insulation, they are supplied in Standard Red PVC.
- Standard designationsIRAM 2178-2 (2015), IEC 60502-2, ICEA S-93-639 / NEMA WC 74, UL 1072
- Voltage classes (IRAM)1.9/3.3 kV, 3.8/6.6 kV, 7.6/13.2 kV, 13.2/22.8 kV & 19/33 kV (Cat. I 100% & Cat. II 133%)
- Voltage classes (ICEA)5 kV, 8 kV, 15 kV, 25 kV & 35 kV (100% and 133% Insulation Levels)
- ConductorClass 2 compact circular stranded copper (16–1000 mm² / 6 AWG–1000 kcmil)
- Dielectric systemTriple-extruded inner semi-con, 90 °C TR-XLPE / XLPE & strippable outer semi-con
- Metallic screenConcentric copper wire + equalizing tape or helically lapped copper tape screen
- Sheath & armor variantsRed ST2 PVC, Black Hydrocarbon-Resistant PVC, LSZH (ST8); Unarmored, STA, SWA or AWA
- Thermal & test rating+90 °C continuous / +130 °C overload / +250 °C short-circuit; PD <5 pC routine tested
IRAM 2178-2 Core Identification & Ratings
- Type: PVC Control & Data Cable
- Standard designations: IRAM 2178-2 (2015), IEC 60502-2, ICEA S-93-639 / NEMA WC 74, UL 1072
- Voltage classes (IRAM): 1.9/3.3 kV, 3.8/6.6 kV, 7.6/13.2 kV, 13.2/22.8 kV & 19/33 kV (Cat. I 100% & Cat. II 133%
- Voltage classes (ICEA): 5 kV, 8 kV, 15 kV, 25 kV & 35 kV (100% and 133% Insulation Levels
Electrical, Thermal & Mechanical Bend Limits
- Conductor: Class 2 compact circular stranded copper (16–1000 mm² / 6 AWG–1000 kcmil
- Dielectric system: Triple-extruded inner semi-con, 90 °C TR-XLPE / XLPE & strippable outer semi-con
- Metallic screen: Concentric copper wire + equalizing tape or helically lapped copper tape screen
- Sheath & armor variants: Red ST2 PVC, Black Hydrocarbon-Resistant PVC, LSZH (ST8); Unarmored, STA, SWA or AWA
- Thermal & test rating: +90 °C continuous / +130 °C overload / +250 °C short-circuit; PD <5 pC routine tested
IRAM 2178-2 Conductor, Insulation & Sheath Build
Manufactured on triple-extrusion dry-curing CCV lines, these MV cables combine compact Class 2 copper conductors, void-free 90 °C XLPE insulation, copper wire or tape phase screens, and tailored utility or refinery outer protections.
- Conductor: Compact circular stranded annealed electrolytic copper (IEC 60228 / IRAM NM 280 Class 2 or ASTM B8 Class B).
- Triple-Extruded Dielectric: Extruded semi-conducting conductor screen + 90 °C dry-cured XLPE insulation + strippable semi-conducting insulation screen.
- Metallic Phase Screen: Concentric crown of annealed copper wires (with equalizing tape) or helically lapped annealed copper tape.
- Inner Sheath & Armor (Optional): Extruded PVC, Hydrocarbon-PVC, or LSZH inner bedding + non-magnetic AWA (1-core), galvanized steel SWA (3-core), or double steel tape STA.
- Outer Sheath: Red ST2 PVC (MT), Black Hydrocarbon-Resistant PVC (MTY), or Halogen-Free Low-Smoke ST8 LSZH (MTZ / MTZW).
Primary Electrical & Mechanical Performance
- IRAM 2178-2 7.6/13.2 kV & 19/33 kV Cat I/II: Exact insulation wall thicknesses for Argentine 13.2 kV (4.0 mm Cat I / 4.5 mm Cat II) and 33 kV (8.0 mm Cat I / 9.3 mm Cat II) distribution networks.
- ICEA S-93-639 5–35 kV (100% & 133%): Full AWG/kcmil coverage (6 AWG to 1000 kcmil) with 90–345 mils XLPE insulation walls and 100% copper tape shield per NEMA WC 74 / UL 1072.
- Hydrocarbon-resistant & LSZH MV sheaths: Refinery MTY series resists aliphatic/aromatic hydrocarbons in contaminated tank-farm trenches; MTZ / MTZW series uses zero-halogen LSZH.
- Non-magnetic AWA (1C) & Steel SWA/STA (3C): Armored single-core MV cables use non-magnetic aluminum wire armor (AWA) to prevent eddy-current losses; 3-core MV cables use SWA or STA steel armor.
Industrial Oil, Flame & Environmental Protection
- Dry-cured triple-extruded XLPE (<5 pC PD): Simultaneous extrusion and nitrogen dry curing eliminate micro-voids and moisture, ensuring partial discharge <5 pC at 1.73 × U0.
- Copper wire or copper tape phase screen: Available with concentric copper wire screen + equalizing tape (16/25/35/50 mm²) or helically lapped 0.1 mm copper tape screen.
- Optional longitudinal water blocking (-OL): Hygroscopic water-swelling tapes under the metallic screen (and optional water-blocked conductors) prevent axial moisture migration.
- IEC 60332-3-24 Cat. C bunched flame compliance: All PVC, Hydrocarbon-PVC, and LSZH outer jackets pass vertical bunched tray flame testing.
IEC / EN / VDE / UL Reference Standards
- IRAM 2178-2: Medium-voltage extruded insulated power cables rated 1.9/3.3 kV up to 19/33 kV
- IEC 60502-2: Power cables with extruded insulation and their accessories for 6 kV up to 30 kV
- ICEA S-93-639 / NEMA WC 74 & UL 1072: 5–46 kV shielded power cables at 100% & 133% insulation levels
- IRAM NM 280 / IEC 60228 & ASTM B8 Class B: Compact circular stranded copper conductors
- IEC 60332-3-24 Cat. C, IEC 60754-1/2 & IEC 61034-2: Flame retardance & LSZH smoke/halogen compliance
Industrial Cable Selection & Routing Guides

IRAM 2178-2 Industrial Installation & Routing Guide
Medium-voltage utility feeders, wind/solar collector networks, and oil refinery distribution grids across Argentina and the Americas specify either IRAM 2178-2 (which uniquely defines the Argentine/MERCOSUR 7.6/13.2 kV and 19/33 kV utility voltage levels in Category I [100%] for grounded neutral systems and Category II [133%] for ungrounded/resonant systems), IEC 60502-2 (3.6/6 kV to 18/30 kV), or North American ICEA S-93-639 / NEMA WC 74 (5 kV, 8 kV, 15 kV, 25 kV & 35 kV at 100% and 133% insulation levels). This comprehensive product page unifies all three standards across Single-Core (Unipolar, 16 mm² to 1000 mm² / 6 AWG to 1000 kcmil) and Three-Core (Tripolar, 16 mm² to 400 mm²) copper conductors.
Every core is manufactured on a dry-curing triple-extrusion catenary line (CCV) that simultaneously applies the smooth inner semi-conducting conductor screen, 90 °C XLPE / TR-XLPE insulation, and strippable outer semi-conducting insulation screen, followed by a concentric copper wire or helically lapped copper tape metallic screen. To suit any industrial or utility environment, the family is produced in four jacket/armor systems: (1) Standard Red UV-PVC (IEC 60332-3-24 Cat. C), (2) Black Hydrocarbon-Resistant Refinery PVC (for direct burial in petrochemical soils), (3) Halogen-Free Low-Smoke LSZH (for indoor substations and tunnels), and (4) Armored (SWA Galvanized Steel Wire on 3-core, Non-Magnetic AWA Aluminum Wire on 1-core, or STA Double Steel Tape). Compare with our EuropeanRHZ1-OL / RHZ1-2OL MV cablesandRHVhMVh refinery MV cables.
Typical Plant, Machine & Infrastructure Circuits
- IRAM 2178-2 (3.3–33 kV) & IEC 60502-2 (6–30 kV) Single-Core and Three-Core Cables serve urban 13.2 kV and 33 kV underground rings, wind/solar farm 33 kV collector lines, and industrial substation feeders.
- Hydrocarbon-Resistant (MTY) and ICEA S-93-639 (5–35 kV) Armored/Unarmored MV Cables power 4.16 kV, 6.6 kV, and 13.8 kV medium-voltage compressor motors, crude-oil pipeline booster pumps, and petrochemical switchgear in refineries, LNG plants, and gas processing complexes.
IRAM 2178-2 Specification & Selection FAQ
What is the difference between Category I (100%) and Category II (133%) insulation levels in IRAM 2178-2 and ICEA S-93-639?
Category I (100% insulation level) is used in effectively grounded systems where single-line-to-ground faults are cleared by protective relays within 1 minute (e.g., 4.0 mm XLPE at 7.6/13.2 kV or 175 mils at 15 kV). Category II (133% insulation level) provides a thicker XLPE wall (e.g., 4.5 mm at 13.2 kV or 220 mils at 15 kV) for ungrounded, impedance-grounded, or resonant systems where earth faults may persist up to 1 hour.
When should I specify the Hydrocarbon-Resistant (MTY) medium-voltage series?
Specify the MTY series (IRAM 2178-2 / IEC 60502-2 with black hydrocarbon-resistant inner and outer sheaths, unarmored or SWA armored) whenever 6.6 kV, 13.2 kV, or 33 kV feeders are direct-buried in oil refineries, petrochemical complexes, or fuel storage terminals.
Why do single-core armored MV cables use Aluminum Wire Armor (AWA) instead of Steel Wire Armor (SWA)?
Surrounding a single alternating-current conductor with magnetic steel wires creates a closed magnetic path that induces severe eddy-current and hysteresis heating in the armor. Using non-magnetic Aluminum Wire Armor (AWA) on single-core MV cables provides full mechanical protection without magnetic heating.
Are halogen-free LSZH medium-voltage cables available in both IRAM/IEC and ICEA 5–35 kV standards?
Yes. Both the metric MTZ series (IRAM 2178-2 3.3–33 kV & IEC 60502-2 6–30 kV) and the AWG/kcmil MTZW series (ICEA S-93-639 5–35 kV) are manufactured with zero-halogen low-smoke (LSZH) outer sheaths meeting IEC 60332-3-24 Cat. C, IEC 60754-1/2, and IEC 61034-2.
Dimensional, weight, electrical, and ampacity tables for IRAM 2178-2 (3.3–33 kV, including 7.6/13.2 kV & 19/33 kV) and ICEA S-93-639 (5–35 kV 100%/133%) single-core and three-core MV XLPE cables across PVC, Hydrocarbon, LSZH and Armored types.
TEBAOFLEX® — IRAM 2178-2 (3.3–33 kV) & ICEA S-93-639 (5–35 kV) Medium-Voltage XLPE Cable
| Voltage Class U0/U (kV) | Formation × Size (mm²) | XLPE Wall (mm) | Unarmored OD (mm) | Unarmored Weight (kg/km) | Armored AWA/SWA OD (mm) | Armored Weight (kg/km) | Max. DC Res. 20 °C (Ω/km) | Ampacity Air / Buried 90 °C (A) |
|---|---|---|---|---|---|---|---|---|
| 7.6/13.2 (15) kV | 1 × 35 Cu | 4.0 | 21.8 | 690 | 26.6 (AWA) | 980 | 0.524 | 195 / 172 |
| 7.6/13.2 (15) kV | 1 × 70 Cu | 4.0 | 24.8 | 1,070 | 29.8 (AWA) | 1,410 | 0.268 | 292 / 248 |
| 7.6/13.2 (15) kV | 1 × 120 Cu | 4.0 | 28.2 | 1,610 | 33.6 (AWA) | 2,010 | 0.153 | 405 / 335 |
| 7.6/13.2 (15) kV | 1 × 185 Cu | 4.0 | 31.8 | 2,290 | 37.4 (AWA) | 2,750 | 0.0991 | 520 / 420 |
| 7.6/13.2 (15) kV | 1 × 240 Cu | 4.0 | 34.6 | 2,890 | 40.6 (AWA) | 3,420 | 0.0754 | 615 / 490 |
| 7.6/13.2 (15) kV | 1 × 400 Cu | 4.0 | 40.2 | 4,420 | 46.6 (AWA) | 5,080 | 0.0470 | 815 / 630 |
| 7.6/13.2 (15) kV | 3 × 50 Cu | 4.0 | 51.5 | 3,380 | 58.5 (SWA) | 5,120 | 0.387 | 210 / 195 |
| 7.6/13.2 (15) kV | 3 × 95 Cu | 4.0 | 58.8 | 5,140 | 66.4 (SWA) | 7,280 | 0.193 | 310 / 280 |
| 7.6/13.2 (15) kV | 3 × 150 Cu | 4.0 | 65.4 | 7,080 | 73.6 (SWA) | 9,620 | 0.124 | 400 / 355 |
| 19/33 (36) kV | 1 × 50 Cu | 8.0 | 31.2 | 1,220 | 36.8 (AWA) | 1,640 | 0.387 | 238 / 205 |
| 19/33 (36) kV | 1 × 95 Cu | 8.0 | 34.8 | 1,760 | 40.8 (AWA) | 2,240 | 0.193 | 355 / 295 |
| 19/33 (36) kV | 1 × 150 Cu | 8.0 | 37.8 | 2,340 | 44.0 (AWA) | 2,890 | 0.124 | 460 / 375 |
| 19/33 (36) kV | 1 × 240 Cu | 8.0 | 42.2 | 3,350 | 48.8 (AWA) | 3,990 | 0.0754 | 620 / 495 |
| 19/33 (36) kV | 1 × 400 Cu | 8.0 | 47.8 | 4,940 | 54.8 (AWA) | 5,710 | 0.0470 | 820 / 635 |
TEBAOFLEX® — IRAM 2178-2 (3.3–33 kV) & ICEA S-93-639 (5–35 kV) Medium-Voltage XLPE Cable
| Voltage & Insulation Level | Size (AWG / kcmil) | XLPE Wall (mils / mm) | Screen Type | Single-Core OD (mm) | Single-Core Weight (kg/km) | Three-Core STA/SWA OD (mm) | Ampacity in Air / Duct 90 °C (A) |
|---|---|---|---|---|---|---|---|
| 5 kV 100% / 133% | 1 × #2 AWG (33.6 mm²) | 90 / 2.29 (115 / 2.92) | Cu Tape | 17.5 | 540 | 44.2 (3C) | 190 / 155 |
| 5 kV 100% / 133% | 1 × 2/0 AWG (67.4 mm²) | 90 / 2.29 (115 / 2.92) | Cu Tape | 20.8 | 910 | 51.4 (3C) | 300 / 240 |
| 5 kV 100% / 133% | 1 × 4/0 AWG (107.2 mm²) | 90 / 2.29 (115 / 2.92) | Cu Tape | 23.9 | 1,350 | 58.2 (3C) | 405 / 320 |
| 5 kV 100% / 133% | 1 × 500 kcmil (253 mm²) | 90 / 2.29 (115 / 2.92) | Cu Tape | 31.5 | 2,890 | 74.8 (3C) | 690 / 535 |
| 15 kV 100% (133%) | 1 × #2 AWG (33.6 mm²) | 175 / 4.45 (220 / 5.59) | Cu Tape | 22.2 (24.5) | 745 | 54.5 (3C) | 195 / 165 |
| 15 kV 100% (133%) | 1 × 2/0 AWG (67.4 mm²) | 175 / 4.45 (220 / 5.59) | Cu Tape | 25.4 (27.7) | 1,140 | 61.6 (3C) | 305 / 250 |
| 15 kV 100% (133%) | 1 × 4/0 AWG (107.2 mm²) | 175 / 4.45 (220 / 5.59) | Cu Tape | 28.5 (30.8) | 1,610 | 68.5 (3C) | 410 / 335 |
| 15 kV 100% (133%) | 1 × 350 kcmil (177 mm²) | 175 / 4.45 (220 / 5.59) | Cu Tape | 32.8 (35.1) | 2,380 | 78.0 (3C) | 555 / 445 |
| 15 kV 100% (133%) | 1 × 500 kcmil (253 mm²) | 175 / 4.45 (220 / 5.59) | Cu Tape | 36.4 (38.7) | 3,210 | 85.8 (3C) | 695 / 550 |
| 35 kV 100% (133%) | 1 × 1/0 AWG (53.5 mm²) | 345 / 8.76 (420 / 10.67) | Cu Tape | 33.4 (37.2) | 1,490 | — | 265 / 225 |
| 35 kV 100% (133%) | 1 × 4/0 AWG (107.2 mm²) | 345 / 8.76 (420 / 10.67) | Cu Tape | 37.4 (41.2) | 2,120 | — | 415 / 345 |
| 35 kV 100% (133%) | 1 × 500 kcmil (253 mm²) | 345 / 8.76 (420 / 10.67) | Cu Tape | 45.2 (49.0) | 3,850 | — | 700 / 560 |
Selection guide: Specify standard (IRAM 2178-2, IEC 60502-2, or ICEA S-93-639), voltage rating & insulation category (100% Cat. I or 133% Cat. II), core count (1C or 3C), outer sheath (PVC, Hydrocarbon-PVC, or LSZH), and armor (Unarmored, AWA, SWA, or STA). For North American utility 15 kV & 35 kV 105 °C Lead-Free EPR concentric neutral URD cables and 46 kV TR-XLPE / 345–400 kV EHV underground transmission cables, see15 kV & 35 kV EPR Concentric Neutral Medium-Voltage URD Cable (ICEA S-94-649)and46 kV 133% TR-XLPE Subtransmission & 345–400 kV EHV Underground XLPE Cable.
Ordering & Quotation Checklist: Request a factory quotation for IRAM 2178-2 (3.3–33 kV), IEC 60502-2 (6–30 kV) or ICEA S-93-639 (5–35 kV) medium-voltage XLPE cables.
RHZ1-OL, RHZ1-2OL, RHZ1 (S/AS) & RH5Z1 6/10–18/30 kV MV XLPE Power Cable
RHZ1-OL / RHZ1-2OL (AL & CU), RHZ1 (S), RHZ1 (AS), RHZ1 Triplex & RH5Z1-OL/2OL
RHVhMVh 3x Cu + H1 3.6/6–18/30 kV SWA Armored Hydrocarbon-Resistant MV Cable
RHVhMVh 3x Cu + H1 (Three-Core Screened & SWA Armored MV Cable)
12–52 kV Subsea DEH, 5 kV Skin-Effect (SECT), Alloy 825 MI Heating & Leak Cable
12–52 kV Subsea Direct Electrical Heating (DEH), 5 kV Skin-Effect (SECT), 600 V Alloy 825 MI, FG-OD Hydrocarbon Leak Cable
Request Quotation & Datasheet for This Cable
Need factory pricing, cross-section drawing or a full PDF datasheet for IRAM 2178-2 (3.3–33 kV) & ICEA S-93-639 (5–35 kV) Medium-Voltage XLPE Cable? Share your core count, conductor size, length and destination country—our Taicang cable engineers reply within 24 hours.