RHVhMVh 3x Cu + H1 3.6/6–18/30 kV SWA Armored Hydrocarbon-Resistant MV Cable

RHVhMVh 3x Cu + H1 is a 3.6/6 kV, 6/10 kV, 8.7/15 kV, 12/20 kV and 18/30 kV (Um up to 36 kV) three-core steel-wire-armored, hydrocarbon-resistant medium-voltage power cable engineered to IEC 60502-2, UIC 895 OR and petrochemical refinery specifications (ED-P-10.01-01). Built with three Class 2 copper conductors (16–240 mm²), triple-extruded 90 °C XLPE insulation, individual H1 copper wire screens over each core.

  • Model designationRHVhMVh 3x Cu + H1 (Three-Core Screened & SWA Armored MV Cable)
  • Reference standardsIEC 60502-2, UIC 895 OR (Oil & Hydrocarbon Resistance), ED-P-10.01-01
  • Rated voltage U0/U3.6/6 (7.2) kV, 6/10 (12) kV, 8.7/15 (17.5) kV, 12/20 (24) kV & 18/30 (36) kV
  • Conductor3 × Class 2 circular compact stranded plain copper (16–240 mm², IEC 60228)
  • Insulation & screenTriple-extruded 90 °C XLPE (R) + individual H1 copper wire screen on each phase
  • Inner & outer sheathsDouble hydrocarbon-, aromatic- & oil-resistant PVC compound (Vh, UIC 895 OR)
  • Mechanical armor (MV)Crown of galvanized round steel wires (SWA) between inner and outer Vh sheaths
  • Thermal & mechanical-25 °C to +90 °C (+250 °C short-circuit); min. bend radius 15 × OD; AG4 impact
Category:

RHVhMVh 3x Cu + H1 3.6/6 kV to 18/30 kV Core Identification & Ratings

  • Type: Oil & Gas Cable
  • Model designation: RHVhMVh 3x Cu + H1 (Three-Core Screened & SWA Armored MV Cable
  • Reference standards: IEC 60502-2, UIC 895 OR (Oil & Hydrocarbon Resistance), ED-P-10.01-01
  • Rated voltage U0/U: 3.6/6 (7.2) kV, 6/10 (12) kV, 8.7/15 (17.5) kV, 12/20 (24) kV & 18/30 (36) kV

Electrical, Thermal & Mechanical Bend Limits

  • Conductor: 3 × Class 2 circular compact stranded plain copper (16–240 mm², IEC 60228
  • Insulation & screen: Triple-extruded 90 °C XLPE (R) + individual H1 copper wire screen on each phase
  • Inner & outer sheaths: Double hydrocarbon-, aromatic- & oil-resistant PVC compound (Vh, UIC 895 OR
  • Mechanical armor (MV): Crown of galvanized round steel wires (SWA) between inner and outer Vh sheaths
  • Thermal & mechanical: -25 °C to +90 °C (+250 °C short-circuit); min. bend radius 15 × OD; AG4 impact

RHVhMVh 3x Cu + H1 3.6/6 kV to 18/30 kV Conductor, Insulation & Sheath Build

RHVhMVh 3x Cu + H1 encloses three individually copper-screened XLPE medium-voltage cores inside double hydrocarbon-resistant Vh sheaths and a galvanized steel wire armor crown.

  • Conductor (Cu): Three Class 2 compact circular stranded plain copper conductors per IEC 60228.
  • Insulation & Semi-Con (R + H): Triple-extruded inner semi-conducting layer, 90 °C XLPE dielectric (R), and cold-strippable outer semi-conducting screen.
  • Metallic Screen (+H1): Individual concentric crown of annealed copper wires and equalizing tape over each of the three cores.
  • Inner Separation Sheath (Vh): Extruded oil- and hydrocarbon-resistant PVC bedding compound (UIC 895 OR).
  • Mechanical Armor (MV) & Outer Sheath (Vh): Crown of galvanized round steel wires (SWA) + outer hydrocarbon- and UV-resistant PVC sheath (Vh).

Primary Electrical & Mechanical Performance

  • Double Vh hydrocarbon-barrier sheaths: Both the inner bedding sheath (under the armor) and the outer jacket are formulated to UIC 895 OR to resist aliphatic and aromatic hydrocarbons.
  • Individual H1 copper screen per core: Each of the three XLPE-insulated phase cores carries its own extruded semi-con screen and concentric copper wire shield (H1) for radial field control.
  • Galvanized steel wire armor (MV / SWA): Round galvanized steel wire armor protects against excavation strikes, soil subsidence, and high tensile pulling loads in long refinery duct runs.
  • 3.6/6 kV through 18/30 kV refinery coverage: Covers 3.3 kV, 6.0/6.6 kV, 10/11 kV, 15 kV, 20 kV, and 30 kV medium-voltage process compressor, pump, and substation feeders.

Industrial Oil, Flame & Environmental Protection

  • UIC 895 OR chemical & fuel immunity: Withstands prolonged immersion in mineral oils, kerosene, benzene/toluene aromatics, and acidic/alkaline soil groundwater.
  • Triple-extruded 90 °C XLPE dielectric: Dry-cured XLPE insulation with strippable outer semi-conducting screen supports +90 °C continuous load and +250 °C short-circuit surges.
  • Flame-retardant IEC 60332-1-2 & 60332-3: Self-extinguishing hydrocarbon-resistant compound prevents flame propagation along open refinery pipe racks and vertical risers.
  • Complete MV & LV petrochemical family: Combine withNEK 606 RFCU 3.6/6–18/30 kV offshore armored MV cableorRHZ1-OL / RHZ1-2OL MV utility cables.

IEC / EN / VDE / UL Reference Standards

  • IEC 60502-2: Medium-voltage extruded XLPE insulated power cables 3.6/6 kV to 18/30 kV
  • UIC 895 OR & ED-P-10.01-01: Oil, aliphatic & aromatic hydrocarbon resistance on inner/outer Vh sheaths
  • IEC 60228 Class 2 circular compact stranded annealed copper conductors
  • IEC 60332-1-2 & IEC 60332-3: Flame retardance for petrochemical tray and trench routing

Industrial Cable Selection & Routing Guides

Petrochemical refinery pipe rack and underground trench wired with RHVhMVh 3x Cu + H1 6/10 kV and 12/20 kV steel-wire-armored hydrocarbon-resistant MV cables
RHVhMVh 3x Cu + H1 3.6/6 kV to 18/30 kV cables combine individual H1 copper screens, double Vh hydrocarbon-resistant sheaths, and galvanized steel wire armor for refinery service. Photo: Wikimedia Commons contributor, CC BY-SA 2.0, via Wikimedia Commons.

RHVhMVh 3x Cu + H1 3.6/6 kV to 18/30 kV Industrial Installation & Routing Guide

In onshore oil refineries, LNG liquefaction terminals, petrochemical tank farms, and chemical processing plants, underground medium-voltage cable trenches are exposed to aromatic hydrocarbons, crude oil condensates, diesel fuels, and heavy mechanical crushing. RHVhMVh 3x Cu + H1 is the dedicated three-core IEC 60502-2 and UIC 895 OR medium-voltage armored power cable engineered specifically for direct burial and concrete trough routing across refinery process units (ED-P-10.01-01).

In the RHVhMVh designation: R denotes 90 °C cross-linked polyethylene (XLPE) core insulation; H / +H1 denotes the extruded semi-conducting screens and individual concentric copper wire shield (H1) over each of the three phase cores; the first Vh denotes an extruded oil- and hydrocarbon-resistant PVC separation sheath; MV denotes a full crown of galvanized steel wire armor (SWA) providing rodent immunity, tensile pulling strength, and AG4 impact resistance; and the outer Vh denotes a heavy-duty black or red hydrocarbon-resistant PVC outer jacket. For 0.6/1 kV low-voltage refinery distribution, pair with ourFG16OR16FR16 SWA armored hydrocarbon-resistant HEPR cableorRVhMVh-K 0.6/1 kV flexible SWA armored cable.

Typical Plant, Machine & Infrastructure Circuits

  • RHVhMVh 3x Cu + H1 (3×16 mm² to 3×240 mm²) supplies medium-voltage induction and synchronous motors driving crude charge pumps, hydrocracker recycle compressors, cooling-water circulation pumps, and unit substations across petroleum refineries and chemical complexes.
  • Because all three screened phases are cabled together inside a single galvanized steel-wire-armored envelope, RHVhMVh 3x Cu + H1 eliminates trefoil cleating labor, cancels external magnetic fields along steel pipe racks, and prevents hydrocarbon migration into substation basements.

RHVhMVh 3x Cu + H1 3.6/6 kV to 18/30 kV Specification & Selection FAQ

Why does RHVhMVh 3x Cu + H1 use two Vh hydrocarbon-resistant sheaths?

In oil refineries and chemical tank farms, underground soil and water tables can become contaminated with petroleum distillates and aromatic solvents. Applying a hydrocarbon-resistant Vh compound for both the inner bedding sheath (under the steel wire armor) and the outer sheath ensures that even if the outer jacket is mechanically gouged, hydrocarbons cannot penetrate the XLPE core insulation.

What does +H1 mean in RHVhMVh 3x Cu + H1?

+H1 indicates that each of the three medium-voltage phase cores is individually shielded with a concentric copper wire screen (typically 16 mm² per core) over its extruded semi-conducting insulation screen, confining the electric field radially within each phase.

Which voltage ratings are covered by RHVhMVh 3x Cu + H1?

RHVhMVh 3x Cu + H1 is manufactured across all standard refinery medium-voltage tiers: 3.6/6 (7.2) kV, 6/10 (12) kV, 8.7/15 (17.5) kV, 12/20 (24) kV, and 18/30 (36) kV.

What is the minimum bending radius for RHVhMVh 3x Cu + H1?

The minimum static bending radius is 15 × the overall cable diameter (15 × OD), with a recommended pulling bending radius of 20 × OD during trench or duct installation.

Dimensional and electrical tables for 3-core RHVhMVh 3x Cu + H1 medium-voltage armored refinery cables across 3.6/6 kV, 6/10 kV, 8.7/15 kV, 12/20 kV, and 18/30 kV (3×16 mm² to 3×240 mm²).

TEBAOFLEX® — RHVhMVh 3x Cu + H1 3.6/6–18/30 kV SWA Armored Hydrocarbon-Resistant MV Cable

RHVhMVh 3x Cu + H1 3.6/6 (7.2) kV & 6/10 (12) kV Three-Core SWA Armored Hydrocarbon-Resistant Cable Specifications
Voltage U0/U (kV) Formation (mm²) Conductor Ø (mm) Insulation Ø (mm) External OD (mm) Approx. Weight (kg/km) Max. DC Res. 20 °C (Ω/km) Reactance X (Ω/km) Capacitance C (μF/km) Ampacity Open Air (A) Ampacity Buried (A)
3.6/6 (7.2) kV 3 × 50 Cu 8.5 14.5 48.5 5,265 0.387 0.093 0.308 205 181
3.6/6 (7.2) kV 3 × 70 Cu 10.0 16.0 52.1 6,265 0.268 0.089 0.348 253 220
3.6/6 (7.2) kV 3 × 95 Cu 11.1 17.1 54.9 7,600 0.193 0.086 0.377 307 262
3.6/6 (7.2) kV 3 × 120 Cu 12.8 18.8 59.0 8,455 0.153 0.083 0.421 352 298
3.6/6 (7.2) kV 3 × 150 Cu 15.0 21.0 64.1 10,035 0.124 0.080 0.479 397 332
3.6/6 (7.2) kV 3 × 185 Cu 16.5 22.5 67.9 11,670 0.0991 0.079 0.518 453 374
3.6/6 (7.2) kV 3 × 240 Cu 18.1 24.3 72.8 13,735 0.0754 0.077 0.556 532 431
6/10 (12) kV 3 × 25 Cu 5.9 13.9 47.2 4,480 0.727 0.106 0.218 138 125
6/10 (12) kV 3 × 50 Cu 8.5 16.5 53.0 5,810 0.387 0.098 0.273 207 182
6/10 (12) kV 3 × 95 Cu 11.1 19.1 59.5 8,210 0.193 0.090 0.330 309 263
6/10 (12) kV 3 × 150 Cu 15.0 23.0 68.6 10,760 0.124 0.084 0.415 400 334
6/10 (12) kV 3 × 240 Cu 18.1 26.1 76.8 14,520 0.0754 0.080 0.485 535 433

TEBAOFLEX® — RHVhMVh 3x Cu + H1 3.6/6–18/30 kV SWA Armored Hydrocarbon-Resistant MV Cable

RHVhMVh 3x Cu + H1 8.7/15 (17.5) kV & 12/20 (24) kV Three-Core SWA Armored Hydrocarbon-Resistant Specifications
Voltage U0/U (kV) Formation (mm²) Conductor Ø (mm) Insulation Ø (mm) External OD (mm) Approx. Weight (kg/km) Max. DC Res. 20 °C (Ω/km) Reactance X (Ω/km) Capacitance C (μF/km) Ampacity Open Air (A) Ampacity Buried (A)
8.7/15 (17.5) kV 3 × 35 Cu 7.0 17.2 54.6 5,590 0.524 0.108 0.198 170 152
8.7/15 (17.5) kV 3 × 70 Cu 10.0 20.2 61.8 7,480 0.268 0.097 0.246 256 222
8.7/15 (17.5) kV 3 × 120 Cu 12.8 23.0 68.6 9,820 0.153 0.090 0.292 356 300
8.7/15 (17.5) kV 3 × 185 Cu 16.5 26.7 77.4 13,210 0.0991 0.085 0.352 458 376
12/20 (24) kV 3 × 35 Cu 7.0 19.2 59.0 6,180 0.524 0.114 0.172 172 153
12/20 (24) kV 3 × 50 Cu 8.5 20.7 62.5 6,940 0.387 0.107 0.192 210 184
12/20 (24) kV 3 × 95 Cu 11.1 23.3 68.9 9,460 0.193 0.098 0.228 312 265
12/20 (24) kV 3 × 150 Cu 15.0 27.2 78.2 12,180 0.124 0.091 0.281 404 336
12/20 (24) kV 3 × 240 Cu 18.1 30.3 86.4 16,150 0.0754 0.086 0.324 538 435

Selection guide: Specify RHVhMVh 3x Cu + H1, rated voltage (3.6/6, 6/10, 8.7/15, 12/20, or 18/30 kV), phase cross-section (3×16 to 3×240 mm²), and H1 copper screen fault-current rating.

Ordering & Quotation Checklist: Request a factory quotation for IEC 60502-2 / UIC 895 OR RHVhMVh 3x Cu + H1 (3.6/6 kV to 18/30 kV) SWA armored hydrocarbon-resistant MV cables.

FG16OR16FR16 0.6/1 kV SWA Armored Hydrocarbon-Resistant HEPR Cable

FG16OR16FR16 0.6/1 kV SWA Armored Hydrocarbon-Resistant HEPR Cable

FG16OR16FR16 0.6/1 kV (CU / HEPR G16 / PVC R16 / SWA+CS / PVC R16 HC)

VIEW PRODUCT »

RVFV-K (U-1000 RVFV), RVhMVh-K, RZ1FZ1-K & RZ1MZ1-K 0.6/1 kV Armored Cable

RVFV-K (U-1000 RVFV), RVhMVh-K, RZ1FZ1-K & RZ1MZ1-K 0.6/1 kV Armored Cable

RVFV-K (U-1000 RVFV), RVhMVh-K, RZ1FZ1-K (AS) & RZ1MZ1-K (AS)

VIEW PRODUCT »

RFCU 3.6/6–18/30 kV GSWB & RFOU 18/30 kV (P20/P22/P113) Offshore Cable

RFCU 3.6/6–18/30 kV GSWB & RFOU 18/30 kV (P20/P22/P113) Offshore Cable

RFCU (3.6/6–18/30 kV GSWB Armor) & RFOU / RFOU M 18/30(36) kV (P20/P22/P113)

VIEW PRODUCT »

Direct Factory Engineering RFQ

Request Quotation & Datasheet for This Cable

Need factory pricing, cross-section drawing or a full PDF datasheet for RHVhMVh 3x Cu + H1 3.6/6–18/30 kV SWA Armored Hydrocarbon-Resistant MV Cable? Share your core count, conductor size, length and destination country—our Taicang cable engineers reply within 24 hours.

  • ISO 9001 Factory Direct
  • MOQ 50 m (Custom Builds)
  • 24h Engineering Reply
WhatsApp / Direct Line+86 156 3992 7303

    Leave Us a Message

    Whether you need a quotation, have a technical question or want a cable recommendation, our engineers reply within 24 hours.

    RHVhMVh 3x Cu + H1 3.6/6–18/30 kV SWA Armored Hydrocarbon-Resistant MV CableGet A Quote