RFCU 3.6/6–18/30 kV GSWB & RFOU 18/30 kV (P20/P22/P113) Offshore Cable
RFCU (3.6/6 kV, 6/10 kV, 8.7/15 kV, 12/20 kV, and 18/30 kV with galvanized steel wire braid armor C) and RFOU / RFOU M 18/30(36) kV (NEK 606 Code P20 / P22 / P113 with tinned copper wire braid O) are heavy-duty medium-voltage offshore power cables engineered to NEK TS 606 and IEC 60092-354. Built with IEC 60228 Class 2 tinned stranded compressed copper conductors (STCC, 16 to 630 mm²).
- Model designationsRFCU (3.6/6–18/30 kV GSWB Armor) & RFOU / RFOU M 18/30(36) kV (P20/P22/P113)
- StandardsNEK TS 606, IEC 60092-354, IEC 60092-360, IEC 60332-3-22 (Cat A)
- Voltage classes U0/U3.6/6, 6/10, 8.7/15, 12/20 & 18/30 (Um 36) kV
- Conductor & InsulationClass 2 tinned copper (STCC, Class 5 opt.); 90 °C HEPR (IEC 60092-360)
- Core Metallic ScreenSemi-conducting elastomer layer + tinned copper wire braid / tape screen
- Armor (C vs O)RFCU: Galvanized Steel Wire Braid (C); RFOU 30kV: Tinned Copper Braid (O)
- Outer sheath (U)Red SHF2 halogen-free & NEK 606 oil/drilling-mud resistant thermoset (EVA/EMA)
- Thermal & mechanical-20 °C (-40 °C Arctic CSA 22.2) to +90 °C (+250 °C fault); bend 9×D fixed / 15×D pull
RFCU 3.6/6 Shipboard & Offshore Identification
- Type: Oil & Gas Cable
- Model designations: RFCU (3.6/6–18/30 kV GSWB Armor) & RFOU / RFOU M 18/30(36) kV (P20/P22/P113
- Standards: NEK TS 606, IEC 60092-354, IEC 60092-360, IEC 60332-3-22 (Cat A
- Voltage classes U0/U: 3.6/6, 6/10, 8.7/15, 12/20 & 18/30 (Um 36) kV
Marine Electrical, Temperature & Bend Ratings
- Conductor & Insulation: Class 2 tinned copper (STCC, Class 5 opt.); 90 °C HEPR (IEC 60092-360
- Core Metallic Screen: Semi-conducting elastomer layer + tinned copper wire braid / tape screen
- Armor (C vs O): RFCU: Galvanized Steel Wire Braid (C); RFOU 30kV: Tinned Copper Braid (O
- Outer sheath (U): Red SHF2 halogen-free & NEK 606 oil/drilling-mud resistant thermoset (EVA/EMA
- Thermal & mechanical: -20 °C (-40 °C Arctic CSA 22.2) to +90 °C (+250 °C fault); bend 9×D fixed / 15×D pull
RFCU 3.6/6 Halogen-Free / Armored Architecture
RFCU and RFOU 18/30(36) kV combine tinned Class 2 copper conductors, triple-extruded HEPR dielectric, individual copper core screens, F inner bedding, GSWB or TCWB armor, and a red SHF2 mud-resistant jacket.
- Conductor: Tinned stranded compressed annealed copper (STCC) per IEC 60228 Class 2 (Class 5 on request), 16 to 630 mm².
- Conductor & Insulation Screens: Extruded semi-conducting EP-rubber conductor screen and insulation screen.
- Insulation (R): High-modulus ethylene-propylene rubber (HEPR / EPR) per IEC 60092-360 (8.0 mm wall at 18/30 kV).
- Metallic Core Screen & Inner Covering (F): Tinned copper wire braid/tape screen over each phase + halogen-free flame-retardant extruded inner bedding (F).
- Armor (C / O) & Outer Sheath (U): Galvanized steel wire braid (C on RFCU) or tinned copper wire braid (O on RFOU) + red SHF2 mud-resistant thermoset outer sheath (U).
Shipboard Fire Integrity & EMC Performance
- RFCU GSWB high-impact armor: Galvanized steel wire braid ('C') provides superior crush, impact, and vertical hanger tensile strength compared with soft copper braid ('O').
- 18/30(36) kV P20/P22/P113 rating: Full 8.0 mm HEPR insulation wall and 20–60 mm² tinned copper fault screen support 30 kV / 33 kV (Um 36 kV) topside power buses and export transformers.
- NEK 606 SHF2 mud resistance: Cross-linked red SHF2 outer sheath resists oil-based and water-based drilling muds, completion brines, and cleaning fluids in hazardous Ex and safe areas.
- Optional -40 °C Arctic grade: Standard minimum installation temperature of -20 °C, with optional Arctic-grade compound passing CSA 22.2 cold bend/impact at -40 °C / -35 °C.
Salt Fog, Mud, Oil & Low-Smoke Resistance
- Fault-rated metallic core screens: Each 18/30 kV phase core integrates a tinned copper wire braid screen (20–60 mm² cross-section) separate from the overall armor braid.
- 88.2 kA 1-sec short-circuit capacity: 1×630 mm² 18/30 kV RFOU withstands an 88,200 A 1-second short-circuit surge (56,000 A on 1×400 mm²) at 250 °C peak conductor temperature.
- 9 × D fixed bending radius: Achieves a 9 × OD minimum bending radius when fixed installed (15 × OD during pulling, max tensile load 50 N × total copper mm²).
- IEC 60332-3-22 Cat A & zero halogen: Certified to IEC 60332-3-22 Cat A bunched flame retardance, IEC 60754-1/2 halogen-free, and IEC 61034-1/2 low smoke density.
IEC 60092 / NEK 606 / BS Marine Standards
- NEK TS 606: 2016 / 2022 (Halogen-free & mud-resistant offshore medium-voltage cables
- IEC 60092-354, IEC 60092-350 & IEC 60092-360: HEPR insulation & SHF2 thermoset sheathing
- IEC 60332-1-2 & IEC 60332-3-22 Category A: bunched vertical flame retardance
- IEC 60754-1/2 zero halogen acid gas & IEC 61034-1/2 low smoke emission
- CSA C22.2 No. 0.3: -40 °C / -35 °C cold bend & impact on optional Arctic grade
Marine & Offshore Cable Engineering Guides

RFCU 3.6/6 Vessel, Platform & FPSO Routing
In offshore oil & gas production (FPSOs, tension-leg platforms, jack-up drilling rigs) and offshore wind topside substations governed by NEK TS 606 and IEC 60092-354, medium-voltage power cables require either high-tensile mechanical armor (RFCU) or 30 kV / 36 kV high-voltage mud-resistant ratings (RFOU 18/30 kV P20/P22/P113). While our standard3.6/6–12/20 kV RFOU offshore medium-voltage cable pagecovers tinned-copper-braided RFOU up to 12/20 kV (P2/P9 through P19/P21), this dedicated specification covers two critical offshore engineering extensions: (1) RFCU 3.6/6 kV to 18/30 kV featuring a Galvanized Steel Wire Braid (C = GSWB) armor over the halogen-free inner bedding (F) for severe mechanical impact and vertical riser tension, and (2) RFOU / RFOU M 18/30(36) kV (NEK 606 Code P20 / P22 / P113) for 30 kV / 33 kV offshore inter-platform and main generator switchgear buses.
Both RFCU and RFOU 18/30(36) kV utilize Class 2 tinned stranded compressed copper conductors (STCC), triple-extruded semi-conducting screens and +90 °C HEPR dielectric (8.0 mm radial wall at 18/30 kV), individual tinned copper core screens (20 mm² to 60 mm² fault-rated screen cross-section), and a red SHF2 thermoset outer sheath tested to NEK TS 606 oil- and calcium-bromide/ester drilling-mud immersion. Compare also with our0.6/1 kV NEK 606 RU and RFOU offshore power cables,1.8/3 kV BFOU fire-resistant offshore VFD cables, andBS 6883 / BS 7917 UKOOA offshore power cables.
Shipboard Systems & Offshore Zone Coverage
- RFOU / RFOU M 18/30(36) kV (NEK 606 Code P113 / P20 / P22) (1×70/30 mm² to 1×630/30 mm² and 3×50/45 to 3×300/60 mm²) powers 30 kV / 33 kV gas-turbine generator sets, offshore wind turbine step-up collector switchgear, and subsea umbilical topside termination panels.
- RFCU 3.6/6 kV to 18/30 kV (NEK 606 P5/P12, P6/P13, P7/P14) (1×25 to 1×630 mm² and 3×25 to 3×300 mm²) is specified along open drill-floor pipe racks, moonpool gantries, and vertical leg shafts where galvanized steel wire braid armor is required against dropped-object and mechanical abrasion hazards.
RFCU 3.6/6 Marine & Offshore Technical FAQ
What is the difference between RFCU and RFOU offshore medium-voltage cables?
Both share the same tinned copper conductor, semi-conducting screens, HEPR insulation ('R'), tinned copper phase screens, halogen-free inner bedding ('F'), and SHF2 mud-resistant outer sheath ('U'). The difference is the 3rd letter armor code: RFOU uses a Tinned Copper Wire Braid ('O'), whereas RFCU uses a Galvanized Steel Wire Braid ('C') for higher mechanical crush and tensile strength.
What do NEK 606 codes P20, P22, and P113 designate on 18/30 kV RFOU?
Under NEK TS 606, P20 and P22 (and P113 for 30 kV RFOU / RFOU M) identify 18/30(36) kV halogen-free and oil/drilling-mud-resistant SHF2 medium-voltage offshore power cables.
Why do single-core 18/30 kV RFOU cables list two cross-sections like 1×150/30 mm²?
In designations such as 1×150/30 mm² or 3×300/60 mm², the first number (150 mm² or 300 mm²) is the phase conductor cross-section, and the second number (30 mm² or 60 mm²) is the electrical cross-section of the tinned copper metallic screen designed to carry earth-fault currents.
What is the ambient temperature derating for RFOU and RFCU on offshore platforms?
Tabulated current ratings per IEC 60092-352 Table B.4 are based on a 45 °C ambient air temperature (rating factor 1.00). At 35 °C the rating factor is 1.10; at 50 °C it is 0.94; and at 55 °C it is 0.88.
Technical specification tables for NEK 606 / IEC 60092-354 RFOU / RFOU M 18/30(36) kV (P20 / P22 / P113) single-core and three-core cables (1×70/30 to 1×630/30 mm² & 3×50/45 to 3×300/60 mm²) and RFCU 3.6/6–6/10 kV GSWB-armored offshore MV cables.
TEBAOFLEX® — RFCU 3.6/6–18/30 kV GSWB & RFOU 18/30 kV (P20/P22/P113) Offshore Cable
| Cores × Conductor / Screen (mm²) | Conductor Ø (mm) | HEPR Insulation Wall (mm) | Inner Covering Ø (mm) | Outer Sheath Wall (mm) | Nom. Overall OD (mm) | Approx. Total Weight (kg/km) | Max. DC Resistance at 20 °C (Ω/km) | Reactance 50/60 Hz (Ω/km) | Current Rating at 45 °C (A) | 1-Sec Short-Circuit (A) |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 × 70 / 30 | 10.3 | 8.0 | 33.5 | 2.2 | 40.0 | 2,950 | 0.270 | 0.145 / 0.174 | 242 | 9,800 |
| 1 × 95 / 30 | 12.1 | 8.0 | 35.0 | 2.3 | 42.0 | 3,380 | 0.195 | 0.138 / 0.165 | 293 | 13,300 |
| 1 × 120 / 20 | 13.5 | 8.0 | 37.0 | 2.3 | 44.0 | 3,620 | 0.154 | 0.133 / 0.160 | 339 | 16,800 |
| 1 × 150 / 30 | 14.7 | 8.0 | 38.0 | 2.4 | 45.5 | 4,040 | 0.126 | 0.129 / 0.154 | 389 | 21,000 |
| 1 × 240 / 40 | 19.1 | 8.0 | 42.0 | 2.5 | 50.0 | 5,370 | 0.0762 | 0.120 / 0.143 | 522 | 33,600 |
| 1 × 300 / 35 | 21.6 | 8.0 | 45.0 | 2.6 | 53.0 | 5,960 | 0.0607 | 0.115 / 0.135 | 601 | 42,000 |
| 1 × 400 / 35 | 24.2 | 8.0 | 48.0 | 2.7 | 57.5 | 7,220 | 0.0475 | 0.111 / 0.134 | 670 | 56,000 |
| 1 × 630 / 30 | 31.0 | 8.0 | 55.0 | 3.0 | 63.0 | 10,370 | 0.0286 | 0.104 / 0.125 | 780 | 88,200 |
| 3 × 50 / 45 | 8.5 | 8.0 | 66.5 | 3.5 | 76.0 | 8,880 | 0.391 | 0.118 / 0.142 | 137 | 7,000 |
| 3 × 300 / 60 | 21.6 | 8.0 | 95.0 | 4.5 | 107.0 | 21,300 | 0.0607 | 0.095 / 0.114 | 420 | 42,000 |
TEBAOFLEX® — RFCU 3.6/6–18/30 kV GSWB & RFOU 18/30 kV (P20/P22/P113) Offshore Cable
| Voltage & Formation (n × mm²) | Ø Under Screen (mm) | Ø Under GSWB Armor (mm) | Nom. Overall OD (mm) | Approx. Weight (kg/km) | Current Rating Air 45 °C (A) | Inductive Reactance (Ω/km) | Capacitance (μF/km) |
|---|---|---|---|---|---|---|---|
| 3.6/6 kV 1 × 50 (RFCU) | 15.3 | 17.9 | 22.3 | 1,005 | 171 | 0.127 | 0.289 |
| 3.6/6 kV 1 × 95 (RFCU) | 18.4 | 21.0 | 25.6 | 1,540 | 270 | 0.113 | 0.369 |
| 3.6/6 kV 1 × 150 (RFCU) | 21.4 | 24.0 | 28.8 | 2,115 | 366 | 0.105 | 0.447 |
| 3.6/6 kV 1 × 240 (RFCU) | 25.5 | 28.1 | 33.1 | 3,135 | 501 | 0.098 | 0.528 |
| 3.6/6 kV 3 × 35 (RFCU) | 14.1 | 34.3 | 40.7 | 2,875 | 130 | 0.112 | 0.258 |
| 3.6/6 kV 3 × 70 (RFCU) | 16.7 | 40.4 | 47.0 | 4,265 | 203 | 0.099 | 0.325 |
| 3.6/6 kV 3 × 120 (RFCU) | 20.1 | 48.1 | 55.1 | 6,340 | 285 | 0.091 | 0.412 |
| 6/10 kV 1 × 50 (RFCU) | 17.1 | 19.7 | 24.1 | 1,095 | 171 | 0.132 | 0.227 |
| 6/10 kV 1 × 120 (RFCU) | 21.9 | 24.5 | 29.3 | 1,940 | 316 | 0.113 | 0.318 |
| 6/10 kV 1 × 240 (RFCU) | 27.1 | 29.7 | 34.9 | 3,260 | 501 | 0.101 | 0.418 |
| 6/10 kV 3 × 50 (RFCU) | 17.1 | 41.3 | 47.9 | 3,860 | 158 | 0.112 | 0.227 |
| 6/10 kV 3 × 95 (RFCU) | 20.2 | 48.7 | 55.9 | 5,860 | 246 | 0.101 | 0.287 |
| 6/10 kV 3 × 150 (RFCU) | 23.2 | 55.4 | 63.0 | 7,945 | 329 | 0.093 | 0.344 |
Selection guide: Specify RFCU (galvanized steel wire braid armor C) or RFOU / RFOU M (tinned copper wire braid armor O), NEK 606 P-code (e.g. P20/P22/P113 for 18/30 kV or P5/P12–P7/P14 for RFCU), and size (16–630 mm²). For 275 kV HVAC offshore wind export links, ±320–600 kV HVDC subsea interconnectors, and downhole/pipeline fiber optic sensing, see275 kV HVAC 3-Core Submarine Export & ±320–600 kV HVDC Power CableandDFOS (DAS/DTS/DSS) FIMT Sensing & Downhole TEF/TEC Optical Cable. For medium-voltage 3.6/6 kV to 18/30 kV IEC 60092-354 SHF2 marine electric propulsion cables and UK MoD DEF STAN 02-526 / German VG 95218 naval warship and 60–100 bar water-blocked submarine cables, seeIEC 60092-354 MV Marine Propulsion & DEF STAN 02-526 / VG 95218 Naval Cable. For deepwater API Spec 17E subsea production control umbilicals, API 17G IWOCS, wet-mate EFL/EOFL flying leads, 6–36 kV subsea booster pump jumpers, 12–52 kV subsea flowline Direct Electrical Heating (DEH) & FG-OD oil leak sensing cables, and RM0037–RM0053 / RS935 Work-Class ROV main lift umbilicals, seeAPI 17E Subsea Production Umbilical, API 17G IWOCS, EFL/EOFL & MV Pump Jumper,12–52 kV Subsea DEH, 5 kV SECT, Alloy 825 MI Heating & FG-OD Leak Cable, andRM0037–RM0053, RS935 & 24SSA28 Work-Class ROV Lift Umbilical & RT0106 Tether. For IEEE Std 1580 Type P / UL 1309 2,000 V 3C+3G offshore drilling VFD power cables (37-102VFD unarmored CPE, 37-102-TSVFD basket-weave armored, and 37-103VFD LSZH), see37-102VFD, 37-102-TSVFD (Armored) & 37-103VFD (LSZH) 2kV Type P Offshore VFD Cable.
Ordering & Quotation Checklist: Request a factory quotation for NEK 606 / IEC 60092-354 RFCU (3.6/6–18/30 kV GSWB armored) or RFOU 18/30(36) kV (P20/P22/P113) mud-resistant offshore HEPR cables.
NEK 606 BFOU VFD 1.8/3 kV Fire-Resistant LSZH Offshore VFD Power Cable
1.8/3 kV (for 0.6/1 kV VFD drives)
BS 6883 & BS 7917 0.6/1 kV EPR / SW4 & SW2 Offshore Power & Control Cable
BS 6883, BS 7917, UKOOA code
00/12/FO2, RMP200 & 6XM524 Pipe Crawler & C-3400 / 26XM520 Cleaning Robot Cable
00/12/FO2, 00/20/FOX2 (Electro-Optical), 524/11 (11-Core Copper), RMP200 / RMP300 / RMP350 / RMP500, 6XM524, 1HRS347
Request Quotation & Datasheet for This Cable
Need factory pricing, cross-section drawing or a full PDF datasheet for RFCU 3.6/6–18/30 kV GSWB & RFOU 18/30 kV (P20/P22/P113) Offshore Cable? Share your core count, conductor size, length and destination country—our Taicang cable engineers reply within 24 hours.
- ISO 9001 Factory Direct
- MOQ 50 m (Custom Builds)
- 24h Engineering Reply