RG16H1R12 & RG16H1(O)R12 1.8/3–26/45 kV MV HEPR G16 Power Cable
RG16H1R12 (single-core, also available in visible helical triplex RG16H1R12X) and RG16H1OR12 (three-core cabled with inner filler) are medium- and high-voltage power cables rated from U0/U 1.8/3 kV through 3.6/6 kV, 6/10 kV, 8.7/15 kV, 12/20 kV, 18/30 kV, up to 26/45 kV (Um 52 kV), engineered in accordance with CEI 20-13, CEI 20-66, IEC 60502-2, HD 620, and EN 50575 (CPR Class Eca).
- Model designationsRG16H1R12 (1C), RG16H1R12X (Triplex 3×1C) & RG16H1OR12 (3-Core)
- Standards & CPRCEI 20-13, CEI 20-66, IEC 60502-2, HD 620, CEI 20-16 (PD), EN 50575 Eca
- Voltage classes U0/U1.8/3, 3.6/6, 6/10, 8.7/15, 12/20, 18/30 & 26/45 kV (Um up to 52 kV)
- Conductor (R)Class 2 rigid round compact plain red copper (IEC 60228)
- Insulation & ScreensLead-free G16 HEPR rubber; extruded inner & cold-peelable outer semi-con (≥6/10 kV)
- Metallic Shield (H1)Red copper wires with counter-spiral copper tape over each core
- Outer sheath (R12)Red flame-retardant & UV-resistant PVC compound R12 (ISO 4892-2 1000 h)
- Thermal & mechanical90 °C–105 °C operating (250 °C–300 °C short-circuit); min bend 12–14 × OD
RG16H1R12 & RG16H1 Core Identification & Ratings
- Type: PVC Control & Data Cable
- Model designations: RG16H1R12 (1C), RG16H1R12X (Triplex 3×1C) & RG16H1OR12 (3-Core
- Standards & CPR: CEI 20-13, CEI 20-66, IEC 60502-2, HD 620, CEI 20-16 (PD), EN 50575 Eca
- Voltage classes U0/U: 1.8/3, 3.6/6, 6/10, 8.7/15, 12/20, 18/30 & 26/45 kV (Um up to 52 kV
Electrical, Thermal & Mechanical Bend Limits
- Conductor (R): Class 2 rigid round compact plain red copper (IEC 60228
- Insulation & Screens: Lead-free G16 HEPR rubber; extruded inner & cold-peelable outer semi-con (≥6/10 kV
- Metallic Shield (H1): Red copper wires with counter-spiral copper tape over each core
- Outer sheath (R12): Red flame-retardant & UV-resistant PVC compound R12 (ISO 4892-2 1000 h
- Thermal & mechanical: 90 °C–105 °C operating (250 °C–300 °C short-circuit); min bend 12–14 × OD
RG16H1R12 & RG16H1 Conductor, Insulation & Sheath Build
RG16H1R12 and RG16H1OR12 combine compact Class 2 copper conductors with triple-extruded G16 HEPR dielectric, H1 copper wire screens, and an R12 red PVC sheath.
- Conductor (R): Class 2 rigid round compact stranded plain red copper conductor per IEC 60228.
- Inner Semi-Conducting Layer: Extruded semi-conducting elastomer screen over the conductor (on U0/U ≥ 6/10 kV).
- Insulation (G16): Lead-free high-modulus ethylene-propylene rubber (HEPR compound G16).
- Outer Semi-Con & Shield (H1): Cold-peelable extruded external semi-conducting layer (≥6/10 kV) + red copper wires bound with a counter-spiral copper tape (H1).
- Outer Sheath (R12): Red flame-retardant, UV-resistant PVC compound of R12 quality (with extruded inter-core filler O on three-core RG16H1OR12).
Primary Electrical & Mechanical Performance
- 1.8/3 kV to 26/45 kV full MV range: Covers all seven standard Italian/European MV ratings: 1.8/3, 3.6/6, 6/10, 8.7/15, 12/20, 18/30, and 26/45 kV (Um 52 kV, ex Grado 67).
- Cold-peelable outer semi-con (≥6/10 kV): Extruded cold-strippable external semi-conducting screen speeds up MV plug-in and heat/cold-shrink termination installation.
- Direct burial per CEI 11-17 Art. 4.3.11: Approved for free-air racks, cable channels, underground pipes, and unprotected direct burial in compliance with CEI 11-17.
- 60 N/mm² pulling stress & UV stability: Withstands up to 60 N/mm² conductor pulling tension and passes 1,000-hour xenon-arc UV weathering per ISO 4892-2 / IEC 60811-501.
Industrial Oil, Flame & Environmental Protection
- Lead-free G16 HEPR dielectric: High-modulus G16 elastomer resists water treeing, thermal aging, and cyclic load expansion far better than standard thermo-plastic MV dielectrics.
- H1 copper wire + counter-spiral screen: Provides fault-current return path and radial electric field containment on every voltage grade from 1.8/3 kV through 26/45 kV.
- 90 °C / 105 °C thermal capability: Rated +90 °C continuous (+250 °C short-circuit) on standard MV grades and up to +105 °C (+300 °C short-circuit) on PQA 26/45 kV high-voltage grades.
- EN 50575 CPR Class Eca compliance: Meets EU Construction Products Regulation 305/2011/EU and EN 60332-1-2 flame propagation requirements for civil and industrial works.
IEC / EN / VDE / UL Reference Standards
- CEI 20-13, CEI 20-66, IEC 60502-2 & HD 620: Medium-voltage HEPR insulated power cables
- CEI 20-16, IEC 60885-3 & IEC 60840: Partial discharge & high-voltage PQA qualification
- EN 50575: 2014+A1:2016 & EN 60332-1-2 (CPR Euroclass Eca flame propagation
- CEI 11-17 Art. 4.3.11: Underground direct burial & duct installation rules
- ISO 4892-2 & IEC 60811-501: 1,000-hour UV weather resistance on R12 red sheath
Industrial Cable Selection & Routing Guides
Factory Sample & Cut-Section Verification
TEBAOFLEX Production Sample
Authentic TEBAOFLEX workshop cut-end and stripped sample photographs of RG16H1R12 medium-voltage single-core flexible copper HEPR insulated copper-wire-screened power cable, documenting actual conductor stranding, radial wall concentricity, and outer jacket extrusion prior to reel dispatch.




RG16H1R12 & RG16H1 Industrial Installation & Routing Guide
In Italian and European medium-voltage utility, renewable energy, and heavy industrial distribution networks, RG16H1R12 (single-core) and RG16H1OR12 (three-core with extruded inter-core filler O) are the EN 50575 CPR Euroclass Eca compliant successors to legacy RG7H1R and RG7H1OR cables under CEI 20-13, CEI 20-66, and IEC 60502-2. In the CEI nomenclature: R denotes a Class 2 rigid round compact copper conductor; G16 denotes lead-free high-modulus ethylene-propylene rubber (HEPR) insulation; H1 denotes a concentric red copper wire shield bound with a counter-spiral copper tape; and R12 denotes a flame-retardant, UV-stabilized red PVC outer sheath.
On voltage classes U0/U ≥ 6/10 kV (6/10 kV, 8.7/15 kV, 12/20 kV, 18/30 kV, and 26/45 kV), each core incorporates triple-extruded inner semi-conducting layer, G16 HEPR dielectric, and a cold-peelable extruded external semi-conducting layer, ensuring rapid, nick-free jointing and partial-discharge compliance under CEI 20-16 / IEC 60885-3. Where halogen-free LSZH fire safety is required inside tunnels or public buildings, compare with ourRG7H1M1 6/10–18/30 kV LSZH medium-voltage HEPR cableandRG26H1M16 18/30 kV 105 °C CPR Cca LSZH MV cable, or for low-voltage 0.6/1 kV distribution seeFG16(O)R16 / FG16(O)M16 0.6/1 kV HEPR cables.
Typical Plant, Machine & Infrastructure Circuits
- Single-core RG16H1R12 (1×10 mm² to 1×630 mm²) and visible-helix triplex RG16H1R12X are deployed for primary-to-secondary substation interconnect feeders, utility solar PV and wind farm collector step-up transformer connections, and high-power industrial furnace/compressor bus links.
- Three-core RG16H1OR12 (3×16 mm² to 3×300 mm²) integrates three individually H1 copper-wire-screened phase cores (with colored phase identification tapes/threads) under a single red R12 PVC jacket for compact trench and duct routing.
RG16H1R12 & RG16H1 Specification & Selection FAQ
What is the difference between RG16H1R12 and legacy RG7H1R?
RG16H1R12 (and three-core RG16H1OR12) is the EN 50575 CPR Class Eca compliant replacement for legacy RG7H1R / RG7H1OR under CEI 20-13. It upgrades the insulation to lead-free G16 HEPR and the outer jacket to UV-stabilized R12 red PVC.
What is RG16H1R12X compared to RG16H1OR12?
RG16H1R12X consists of three finished single-core RG16H1R12 cables twisted together in a visible helix (triplex formation) without an overall outer jacket, whereas RG16H1OR12 cables three screened cores together with an extruded inner filler (O) under one common red R12 PVC outer sheath.
At which voltage ratings does RG16H1R12 include extruded semi-conducting screens?
Per CEI 20-13, extruded inner conductor semi-conducting screens and cold-peelable extruded outer insulation semi-conducting screens are applied on all voltage grades from U0/U 6/10 kV through 26/45 kV.
Can RG16H1R12 and RG16H1OR12 be directly buried in the ground?
Yes. Both RG16H1R12 and RG16H1OR12 are approved for direct underground laying even without additional mechanical duct protection, in accordance with Article 4.3.11 of Italian standard CEI 11-17.
Technical specification tables for CEI 20-13 RG16H1R12 and RG16H1(O)R12 medium-voltage HEPR G16 cables across 1.8/3 kV, 3.6/6 kV, 12/20 kV, 18/30 kV, and 26/45 kV (1×10 mm² to 1×630 mm²).
TEBAOFLEX® — RG16H1R12 & RG16H1(O)R12 1.8/3–26/45 kV MV HEPR G16 Power Cable
| Formation (n × mm²) | Conductor Ø (mm) | Avg. G16 Insulation (mm) | Nom. Overall OD (mm) | Approx. Weight (kg/km) | Max. DC Resistance at 20 °C (Ω/km) | Reactance Trefoil / Flat (Ω/km) | Capacitance (μF/km) | Ampacity in Air Trefoil / Flat (A) | Ampacity Buried Trefoil / Flat (A) |
|---|---|---|---|---|---|---|---|---|---|
| 1 × 16 | 4.8 | 2.0 | 13.6 | 365 | 1.15 | 0.12 / 0.18 | 0.23 | 114 / 145 | 126 / 133 |
| 1 × 25 | 6.0 | 2.0 | 14.8 | 470 | 0.727 | 0.12 / 0.18 | 0.27 | 149 / 190 | 162 / 171 |
| 1 × 35 | 7.0 | 2.0 | 15.9 | 580 | 0.524 | 0.11 / 0.17 | 0.30 | 181 / 230 | 193 / 204 |
| 1 × 50 | 8.1 | 2.0 | 17.0 | 700 | 0.387 | 0.11 / 0.16 | 0.34 | 219 / 276 | 227 / 241 |
| 1 × 70 | 9.7 | 2.0 | 18.6 | 920 | 0.268 | 0.10 / 0.16 | 0.40 | 275 / 345 | 278 / 294 |
| 1 × 95 | 11.4 | 2.0 | 20.3 | 1,190 | 0.193 | 0.098 / 0.16 | 0.45 | 339 / 422 | 332 / 351 |
| 1 × 120 | 12.9 | 2.0 | 21.9 | 1,440 | 0.153 | 0.095 / 0.15 | 0.50 | 393 / 487 | 377 / 399 |
| 1 × 150 | 14.3 | 2.0 | 23.3 | 1,720 | 0.124 | 0.092 / 0.15 | 0.55 | 446 / 550 | 421 / 445 |
| 1 × 185 | 16.0 | 2.0 | 25.0 | 2,065 | 0.0991 | 0.089 / 0.15 | 0.60 | 516 / 635 | 477 / 500 |
| 1 × 240 | 18.3 | 2.0 | 27.1 | 2,640 | 0.0754 | 0.086 / 0.14 | 0.68 | 617 / 745 | 550 / 580 |
| 1 × 300 | 21.0 | 2.0 | 30.1 | 3,310 | 0.0601 | 0.084 / 0.14 | 0.75 | 709 / 855 | 621 / 650 |
| 1 × 400 | 23.2 | 2.0 | 32.5 | 4,125 | 0.0470 | 0.083 / 0.14 | 0.83 | 824 / 990 | 702 / 735 |
| 1 × 500 | 26.1 | 2.2 | 36.7 | 5,250 | 0.0366 | 0.081 / 0.14 | 0.88 | 954 / 1,140 | 790 / 830 |
| 1 × 630 | 30.3 | 2.4 | 41.1 | 6,760 | 0.0283 | 0.079 / 0.14 | 0.92 | 1,102 / 1,300 | 885 / 930 |
TEBAOFLEX® — RG16H1R12 & RG16H1(O)R12 1.8/3–26/45 kV MV HEPR G16 Power Cable
| Formation (n × mm²) | Conductor Ø (mm) | Insulation Ø (mm) | Approx. Overall OD (mm) | Approx. Weight (kg/km) | Min. Bend Radius (mm) | DC Resistance at 20 °C (Ω/km) | Capacitance (μF/km) | Ampacity in Air Trefoil / Flat (A) | Ampacity Buried Trefoil / Flat (A) |
|---|---|---|---|---|---|---|---|---|---|
| 1 × 50 | 8.1 | 30.2 | 40.0 | 1,800 | 480 | 0.387 | 0.15 | 225 / 250 | 205 / 212 |
| 1 × 70 | 9.9 | 33.3 | 43.0 | 1,990 | 550 | 0.268 | 0.15 | 280 / 315 | 255 / 260 |
| 1 × 95 | 11.5 | 34.9 | 44.0 | 2,300 | 580 | 0.193 | 0.16 | 340 / 380 | 300 / 310 |
| 1 × 120 | 12.9 | 36.5 | 45.6 | 2,630 | 585 | 0.153 | 0.18 | 395 / 440 | 355 / 365 |
| 1 × 150 | 14.2 | 36.85 | 46.0 | 2,790 | 590 | 0.124 | 0.20 | 445 / 495 | 385 / 395 |
| 1 × 185 | 15.9 | 38.85 | 47.0 | 3,200 | 610 | 0.0991 | 0.21 | 510 / 570 | 440 / 450 |
| 1 × 240 | 18.3 | 40.95 | 49.5 | 3,820 | 650 | 0.0754 | 0.23 | 600 / 665 | 510 / 520 |
| 1 × 300 | 20.7 | 43.4 | 53.0 | 4,640 | 690 | 0.0601 | 0.26 | 695 / 760 | 570 / 580 |
| 1 × 400 | 23.5 | 46.2 | 56.0 | 5,430 | 730 | 0.0470 | 0.28 | 800 / 875 | 650 / 655 |
| 1 × 500 | 26.5 | 49.3 | 59.0 | 6,600 | 770 | 0.0366 | 0.31 | 930 / 1,010 | 735 / 740 |
| 1 × 630 | 31.2 | 53.3 | 64.0 | 8,200 | 850 | 0.0283 | 0.34 | 1,070 / 1,180 | 835 / 845 |
Selection guide: Specify RG16H1R12 (single-core), RG16H1R12X (helical triplex), or RG16H1OR12 (three-core), voltage rating (1.8/3, 3.6/6, 6/10, 8.7/15, 12/20, 18/30, or 26/45 kV), and conductor size (10–630 mm²). For Spanish UNE, French Enedis NF C 33-226 and Nordic HD 620-10K utility MV distribution feeders, seeRHZ1-OL, RHZ1-2OL, RHZ1 (S/AS) & RH5Z1 6/10–18/30 kV,HEPRZ1 AL (-OL) & HEPRZ1 (AS) 12/20–18/30 kV, andFR-N20XA8E-AR & TSLF AL 12/20–18/30 kV.
Ordering & Quotation Checklist: Request a factory quotation for CEI 20-13 RG16H1R12, RG16H1R12X, or RG16H1(O)R12 (1.8/3 kV to 26/45 kV) medium-voltage HEPR power cables.
RG7H1M1 6/10–18/30 kV (90°C & 105°C HEPR) LSZH MV Power Cable
RG7H1M1 (Single-Core) & RG7H1M1X (Helical Triplex 3×1C)
RG26H1M16 18/30 kV 105°C HEPR G26 LSZH Medium-Voltage Cable (CPR Cca)
RG26H1M16 12/20 kV & 18/30 kV LS0H 105 °C (CEI UNEL 35334)
FG16(O)R16 / FG16(O)M16 0.6/1kV HEPR Insulated Industrial Power & Control Cable
FG16R16 / FG16(O)R16 (PVC) & FG16M16 / FG16(O)M16 (LSZH)
Request Quotation & Datasheet for This Cable
Need factory pricing, cross-section drawing or a full PDF datasheet for RG16H1R12 & RG16H1(O)R12 1.8/3–26/45 kV MV HEPR G16 Power Cable? Share your core count, conductor size, length and destination country—our Taicang cable engineers reply within 24 hours.
- ISO 9001 Factory Direct
- MOQ 50 m (Custom Builds)
- 24h Engineering Reply