FR-N1X1G1-flex (NF C 32-323), YMz1Kf & YMvKf 0.6/1–1.8/3 kV Power Cable
FR-N1X1G1-flex 0.6/1 kV and 1.8/3 kV (French NF C 32-323), YMz1Kf 0.6/1 kV and 1.8/3 kV (Dutch NEN / IEC 60502-1 halogen-free CPR B2ca/Cca), and YMvKf 0.6/1 kV and 1.8/3 kV (Dutch NEN / IEC 60502-1 flame-retardant CPR Cca) are European Class 5 flexible 90 °C XLPE-insulated low-voltage power and control cables. Replacing rigid Class 1/2 U-1000 R2V, FR-N1X1G1-R/U, YMz1K and YMvK cables.
- Model designationsFR-N1X1G1-flex (0.6/1 & 1.8/3 kV), YMz1Kf (0.6/1 & 1.8/3 kV) & YMvKf (0.6/1 & 1.8/3 kV)
- Reference standardsNF C 32-323 (French), NEN 1010 / KEMA / IEC 60502-1 / UNE 21123 (Dutch/EU)
- Rated voltage U0/U0.6/1 kV AC (Um 1.2 kV) & 1.8/3 kV AC (Um 3.6 kV / 2.7/5.4 kV DC)
- Conductor (-flex / -f)Class 5 flexible annealed electrolytic copper (1.5–630 mm², IEC 60228)
- Insulation (X1 / Ym)90 °C cross-linked polyethylene (XLPE), +250 °C short-circuit rating
- Outer sheathLSZH polyolefin (G1 on FR-N1X1G1, z1 on YMz1Kf) or Cca flame-retardant PVC (v on YMvKf)
- CPR EuroclassesB2ca-s1a,d1,a1 / Cca-s1a,d1,a1 (FR-N1X1G1 & YMz1Kf); Cca-s2,d2,a3 (YMvKf)
- Min. bending radius5 × OD; operating temperature -40 °C (fixed) to +90 °C
FR-N1X1G1-flex Core Identification & Ratings
- Type: PVC Control & Data Cable
- Model designations: FR-N1X1G1-flex (0.6/1 & 1.8/3 kV), YMz1Kf (0.6/1 & 1.8/3 kV) & YMvKf (0.6/1 & 1.8/3 kV
- Reference standards: NF C 32-323 (French), NEN 1010 / KEMA / IEC 60502-1 / UNE 21123 (Dutch/EU
- Rated voltage U0/U: 0.6/1 kV AC (Um 1.2 kV) & 1.8/3 kV AC (Um 3.6 kV / 2.7/5.4 kV DC
Electrical, Thermal & Mechanical Bend Limits
- Conductor (-flex / -f): Class 5 flexible annealed electrolytic copper (1.5–630 mm², IEC 60228
- Insulation (X1 / Ym): 90 °C cross-linked polyethylene (XLPE), +250 °C short-circuit rating
- Outer sheath: LSZH polyolefin (G1 on FR-N1X1G1, z1 on YMz1Kf) or Cca flame-retardant PVC (v on YMvKf
- CPR Euroclasses: B2ca-s1a,d1,a1 / Cca-s1a,d1,a1 (FR-N1X1G1 & YMz1Kf); Cca-s2,d2,a3 (YMvKf
- Min. bending radius: 5 × OD; operating temperature -40 °C (fixed) to +90 °C
FR-N1X1G1-flex Conductor, Insulation & Sheath Build
FR-N1X1G1-flex, YMz1Kf and YMvKf combine Class 5 flexible copper strands with 90 °C XLPE core insulation and CPR-classified LSZH or flame-retardant PVC sheaths.
- Conductor (-flex / -f): Class 5 flexible annealed electrolytic copper per IEC 60228 / EN 60228.
- Insulation (X1 / Ym): 90 °C cross-linked polyethylene (XLPE) type DIX-3 / XLPE per IEC 60502-1.
- Core Identification: HD 308 S2 color code (2–5 cores); black cores with sequential white numbers + G/Y on ≥6 cores.
- Outer Sheath (G1 / z1 / v): LSZH polyolefin on FR-N1X1G1-flex & YMz1Kf (B2ca/Cca); special bunched-fire-retardant PVC on YMvKf (Cca-s2,d2,a3).
Primary Electrical & Mechanical Performance
- French NF C 32-323 FR-N1X1G1-flex: Direct Class 5 flexible equivalent to rigid NF C 32-323 FR-N1X1G1, certified Cca-s1a,d1,a1 for French ERP (public buildings) and IGH (high-rise towers).
- Dutch NEN 1010 YMz1Kf (B2ca / Cca LSZH): Meets Dutch NEN 1010 and EN 50575 B2ca-s1a,d1,a1 / Cca-s1a,d1,a1 requirements for hospitals, data centers, tunnels, and offices.
- Dutch YMvKf (CPR Cca-s2,d2,a3): Upgrades standard Eca PVC cables (RV-K) to CPR Cca-s2,d2,a3 bunched fire performance for industrial plants, food processing, and infrastructure.
- Available in both 0.6/1 kV & 1.8/3 kV: All three designations (FR-N1X1G1-flex, YMz1Kf, and YMvKf) are manufactured in both 0.6/1 kV and 1.8/3 kV (1,500 V DC solar/inverter) ratings.
Industrial Oil, Flame & Environmental Protection
- 5 × OD bending radius (Class 5 copper): Eliminates the spring-back and terminal torque stress of Class 2 stranded conductors on molded-case circuit breakers and VFD terminals.
- 90 °C XLPE thermal reserve: +90 °C continuous operating temperature (+250 °C short-circuit) allows smaller conductor cross-sections than 70 °C PVC cables.
- UV-resistant EN 50618 outdoor sheath: Outer sheaths on FR-N1X1G1-flex, YMz1Kf, and YMvKf pass UV weathering for exposed rooftop solar trays, cable bridges, and buried ducts.
- Complete European harmonized portfolio: Cross-reference withFG16(O)R16 / FG16(O)M16 Italian Cca cablesandN2XH / (N)HXH FE180 German VDE cables.
IEC / EN / VDE / UL Reference Standards
- NF C 32-323: French 0.6/1 kV & 1.8/3 kV halogen-free XLPE/LSZH cable FR-N1X1G1-flex
- NEN 1010 / IEC 60502-1 / UNE 21123: Dutch YMz1Kf LSZH & YMvKf flame-retardant PVC cables
- EN 50575 & EN 50399: CPR Euroclass B2ca-s1a,d1,a1, Cca-s1a,d1,a1 & Cca-s2,d2,a3
- IEC 60332-3-24, IEC 61034-2: >80% light transmittance) & EN 60754-1/2 (zero halogen on FR-N1X1G1 / YMz1Kf
Industrial Cable Selection & Routing Guides

FR-N1X1G1-flex Industrial Installation & Routing Guide
Engineering schedules in France (NF C 15-100 / NF C 32-323) and the Netherlands / Belgium (NEN 1010) use national cable designations that specify fire reaction, insulation polymer, and conductor flexibility. FR-N1X1G1-flex is the French NF C 32-323 Class 5 flexible halogen-free power cable: FR-N denotes French national standard, 1 denotes 0.6/1 kV (also produced in 1.8/3 kV), X1 denotes 90 °C cross-linked polyethylene (XLPE) insulation, G1 denotes a halogen-free thermoplastic polyolefin outer sheath (CPR Cca-s1a,d1,a1), and -flex denotes Class 5 flexible copper stranding that bends easily inside tight electrical risers where rigid FR-N1X1G1-R cannot.
In Dutch and Benelux projects, YMz1Kf and YMvKf (0.6/1 kV and 1.8/3 kV) are the Class 5 flexible (f = *flexibel*) counterparts to rigid YMz1K and YMvK: Ym denotes 90 °C XLPE core insulation; z1 in YMz1Kf denotes a low-smoke zero-halogen (LSZH) outer sheath certified to CPR B2ca-s1a,d1,a1 / Cca-s1a,d1,a1 (>80% light transmittance); while v in YMvKf denotes a special fire-retardant PVC outer sheath certified to CPR Cca-s2,d2,a3 (EN 50399 bunched fire test). Compare with Spanish/EuropeanRZ1-K (AS) 0.6/1 & 1.8/3 kV flexible LSZH cableor French aluminumU-1000 AR2V / RV Al feeder cable.
Typical Plant, Machine & Infrastructure Circuits
- FR-N1X1G1-flex (0.6/1 kV & 1.8/3 kV) is specified across France and Francophone markets for hospital switchboards, metro stations, commercial towers, and solar PV string-inverter AC/DC runs where NF C 15-100 requires C1/Cca halogen-free cables with tight 5 × OD routing.
- YMz1Kf and YMvKf (1×1.5 mm² to 1×630 mm² and 2×1.5 to 37G2.5 mm²) serve Dutch and Benelux water treatment plants, maritime ports, greenhouse cogeneration, data centers, and rooftop/utility solar installations requiring flexible KEMA/NEN-type cabling.
FR-N1X1G1-flex Specification & Selection FAQ
What is the difference between FR-N1X1G1-flex and U-1000 R2V?
First, FR-N1X1G1-flex (built to NF C 32-323) has a low-smoke zero-halogen (G1) outer sheath rated CPR Cca-s1a,d1,a1 for public buildings, whereas U-1000 R2V has a standard PVC (R2V) sheath. Second, FR-N1X1G1-flex uses a Class 5 flexible copper conductor (-flex) instead of a rigid Class 1/2 conductor.
What is the difference between Dutch YMz1Kf and YMvKf?
In Dutch NEN nomenclature, both YMz1Kf and YMvKf have 90 °C XLPE insulation (Ym) and Class 5 flexible copper conductors (Kf). However, YMz1Kf has a halogen-free LSZH outer sheath (z1, CPR B2ca/Cca-s1a,d1,a1), whereas YMvKf has a flame-retardant PVC outer sheath (v, CPR Cca-s2,d2,a3).
Why are 1.8/3 kV versions of FR-N1X1G1-flex, YMz1Kf, and YMvKf used in solar PV and VFD installations?
Modern 1,500 V DC utility/rooftop string inverters and 800 V AC transformerless inverters exceed the 0.6/1 kV (1.5 kV DC) voltage ceiling during cold-morning open-circuit or VFD switching transients. Specifying the 1.8/3 kV (3.6 kV AC / 5.4 kV DC max) version provides double insulation safety.
Can FR-N1X1G1-flex, YMz1Kf, and YMvKf be installed outdoors and underground?
Yes. All three cable families pass UV weathering tests (EN 50618 / UNE 211605), AD5–AD7 water resistance, and are approved for open-air cable trays, conduits, and buried duct installations.
Dimensional, ampacity, and voltage-drop specifications for French NF C 32-323 FR-N1X1G1-flex and Dutch YMz1Kf / YMvKf 0.6/1 kV and 1.8/3 kV cables.
TEBAOFLEX® — FR-N1X1G1-flex (NF C 32-323), YMz1Kf & YMvKf 0.6/1–1.8/3 kV Power Cable
| Model & Voltage | Formation (mm²) | Overall OD (mm) | Approx. Weight (kg/km) | Ampacity Open Air 30 °C (A) | Ampacity Buried 20 °C (A) | Voltage Drop (V/A·km) | CPR Euroclass |
|---|---|---|---|---|---|---|---|
| YMz1Kf / FR-N1X1G1 0.6/1 kV | 1 × 6 | 8.2 | 120 | 68 | 58 | 8.41 | B2ca-s1a,d1,a1 |
| YMz1Kf / FR-N1X1G1 0.6/1 kV | 1 × 16 | 10.1 | 225 | 124 | 100 | 3.08 | B2ca-s1a,d1,a1 |
| YMz1Kf / FR-N1X1G1 0.6/1 kV | 1 × 35 | 12.5 | 405 | 200 | 154 | 1.41 | B2ca-s1a,d1,a1 |
| YMz1Kf / FR-N1X1G1 0.6/1 kV | 1 × 70 | 16.2 | 740 | 310 | 225 | 0.705 | B2ca-s1a,d1,a1 |
| YMz1Kf / FR-N1X1G1 0.6/1 kV | 1 × 120 | 20.1 | 1,210 | 437 | 303 | 0.422 | B2ca-s1a,d1,a1 |
| YMz1Kf / FR-N1X1G1 0.6/1 kV | 1 × 240 | 27.5 | 2,375 | 674 | 445 | 0.228 | B2ca-s1a,d1,a1 |
| FR-N1X1G1 / YMz1Kf 0.6/1 kV | 2 × 2.5 | 9.6 | 140 | 36 | 35 | 20.4 | B2ca / Cca-s1a,d1,a1 |
| FR-N1X1G1 / YMz1Kf 0.6/1 kV | 3G 2.5 | 10.5 | 165 | 36 | 35 | 20.4 | B2ca / Cca-s1a,d1,a1 |
| FR-N1X1G1 / YMz1Kf 0.6/1 kV | 4G 6 | 14.2 | 345 | 54 | 51 | 7.30 | B2ca / Cca-s1a,d1,a1 |
| FR-N1X1G1 / YMz1Kf 0.6/1 kV | 5G 10 | 18.0 | 615 | 75 | 69 | 4.23 | B2ca / Cca-s1a,d1,a1 |
| FR-N1X1G1 / YMz1Kf 0.6/1 kV | 5G 35 | 28.8 | 1,860 | 162 | 138 | 1.22 | Cca-s1a,d1,a1 |
| FR-N1X1G1 / YMz1Kf 1.8/3 kV | 1 × 16 | 11.5 | 255 | 128 | 104 | 3.08 | B2ca / Cca-s1a,d1,a1 |
| FR-N1X1G1 / YMz1Kf 1.8/3 kV | 1 × 50 | 16.2 | 590 | 250 | 185 | 1.01 | B2ca / Cca-s1a,d1,a1 |
| FR-N1X1G1 / YMz1Kf 1.8/3 kV | 1 × 120 | 21.8 | 1,290 | 445 | 310 | 0.422 | B2ca / Cca-s1a,d1,a1 |
| FR-N1X1G1 / YMz1Kf 1.8/3 kV | 1 × 240 | 28.5 | 2,390 | 685 | 450 | 0.228 | B2ca / Cca-s1a,d1,a1 |
TEBAOFLEX® — FR-N1X1G1-flex (NF C 32-323), YMz1Kf & YMvKf 0.6/1–1.8/3 kV Power Cable
| Model & Voltage | Formation (mm²) | Overall OD (mm) | Approx. Weight (kg/km) | Ampacity Open Air 30 °C (A) | Ampacity Buried 20 °C (A) | CPR Euroclass |
|---|---|---|---|---|---|---|
| YMvKf 0.6/1 kV | 1 × 16 | 10.0 | 220 | 124 | 100 | Cca-s2,d2,a3 |
| YMvKf 0.6/1 kV | 1 × 50 | 14.5 | 535 | 245 | 182 | Cca-s2,d2,a3 |
| YMvKf 0.6/1 kV | 1 × 150 | 22.3 | 1,495 | 500 | 340 | Cca-s2,d2,a3 |
| YMvKf 0.6/1 kV | 3G 2.5 | 10.4 | 160 | 36 | 35 | Cca-s2,d2,a3 |
| YMvKf 0.6/1 kV | 5G 6 | 15.5 | 420 | 54 | 51 | Cca-s2,d2,a3 |
| YMvKf 0.6/1 kV | 5G 16 | 21.8 | 945 | 100 | 88 | Cca-s2,d2,a3 |
| YMvKf 1.8/3 kV | 1 × 25 | 12.8 | 345 | 165 | 132 | Eca / Cca |
| YMvKf 1.8/3 kV | 1 × 95 | 19.5 | 990 | 385 | 270 | Eca / Cca |
| YMvKf 1.8/3 kV | 1 × 185 | 25.3 | 1,815 | 575 | 380 | Eca / Cca |
Selection guide: Specify FR-N1X1G1-flex (French NF C 32-323 LSZH), YMz1Kf (Dutch B2ca/Cca LSZH) or YMvKf (Dutch Cca PVC), voltage rating (0.6/1 kV or 1.8/3 kV), and core formation (1×1.5 to 1×630 mm² or 2×1.5 to 37G2.5 mm²).
Ordering & Quotation Checklist: Request a factory quotation for NF C 32-323 FR-N1X1G1-flex, Dutch YMz1Kf (B2ca/Cca LSZH) or YMvKf (Cca) 0.6/1 kV and 1.8/3 kV flexible XLPE cables.
RZ1-K (AS) 0.6/1 & 1.8/3 kV, SZ-K, Z1Z1-K & TXXI Flexible LSZH Power Cable
RZ1-K (AS) 0.6/1 kV, RZ1-K (AS) 1.8/3 kV, SZ-K (AS), Z1Z1-K (AS) & TXXI
U-1000 AR2V (RV Al), RZ1 Al (AS) & XZ1 (S) Al 0.6/1 kV Aluminum Power Cable
U-1000 AR2V / RV Al, RZ1 Al (AS) & XZ1 (S) Al
FG16(O)R16 / FG16(O)M16 0.6/1kV HEPR Insulated Industrial Power & Control Cable
FG16R16 / FG16(O)R16 (PVC) & FG16M16 / FG16(O)M16 (LSZH)
Request Quotation & Datasheet for This Cable
Need factory pricing, cross-section drawing or a full PDF datasheet for FR-N1X1G1-flex (NF C 32-323), YMz1Kf & YMvKf 0.6/1–1.8/3 kV Power Cable? Share your core count, conductor size, length and destination country—our Taicang cable engineers reply within 24 hours.
- ISO 9001 Factory Direct
- MOQ 50 m (Custom Builds)
- 24h Engineering Reply