600V ICEA S-73-532 / UL 1277 PVC-Nylon Shielded Process Instrumentation Cable
600 V ICEA S-73-532 (NEMA WC 57) and UL 1277 Type TC Shielded Process Instrumentation Cables (1 to 36 twisted pairs or triads, 20 AWG to 12 AWG / 0.5 to 2.5 mm²) are engineered for refinery, chemical, and power-generation cable trays where 600 V voltage rating is required alongside 600 V power/control cables. Manufactured with dual-layer 90 °C PVC + Polyamide Nylon (THHN/THWN) or single-layer 105 °C PVC core insulation.
- Standard designationsICEA S-73-532 / NEMA WC 57, UL 1277 (600 V Type TC), UL 62 / UL 83 (THHN/THWN cores)
- Core insulation typesDual-layer 90 °C PVC + Polyamide Nylon jacket (AY series) or 105 °C PVC (AN series)
- Shielding optionsOverall 100% Al/PET Foil (SP) or Individual Pair/Triad + Overall Al/PET Foil Shield (SB)
- Armor configurationsUnarmored Tray; Galvanized Steel Wire Armor (SWA / -H); Steel Interlock Armor (-TK)
- Rated voltage & temp.600 V AC; -25 °C to +90 °C dry / +75 °C wet (PVC-Nylon) or +105 °C continuous (105 °C PVC)
- Conductor & size range7-wire Class B stranded annealed copper, 20 AWG to 12 AWG (0.5–2.5 mm²), 1 to 36 pairs/triads
- Outer & inner sheathsSunlight-, oil- and hydrocarbon-resistant PVC (Black or Intrinsically Safe Blue)
- Flame test complianceUL 1277 / UL 1685 (70,000 BTU/hr) & IEC 60332-3-24 Cat. C vertical tray flame propagation
600V ICEA S-73-532 / UL 1277 Type TC Signal & Bus Architecture
- Type: Oil & Gas Cable
- Standard designations: ICEA S-73-532 / NEMA WC 57, UL 1277 (600 V Type TC), UL 62 / UL 83 (THHN/THWN cores
- Core insulation types: Dual-layer 90 °C PVC + Polyamide Nylon jacket (AY series) or 105 °C PVC (AN series
- Shielding options: Overall 100% Al/PET Foil (SP) or Individual Pair/Triad + Overall Al/PET Foil Shield (SB
Impedance, Attenuation & Operating Limits
- Armor configurations: Unarmored Tray; Galvanized Steel Wire Armor (SWA / -H); Steel Interlock Armor (-TK
- Rated voltage & temp.: 600 V AC; -25 °C to +90 °C dry / +75 °C wet (PVC-Nylon) or +105 °C continuous (105 °C PVC
- Conductor & size range: 7-wire Class B stranded annealed copper, 20 AWG to 12 AWG (0.5–2.5 mm²), 1 to 36 pairs/triads
- Outer & inner sheaths: Sunlight-, oil- and hydrocarbon-resistant PVC (Black or Intrinsically Safe Blue
- Flame test compliance: UL 1277 / UL 1685 (70,000 BTU/hr) & IEC 60332-3-24 Cat. C vertical tray flame propagation
600V ICEA S-73-532 / UL 1277 Type TC Pair Twist, Foil & Braid Construction
Engineered for 600 V industrial tray systems, these instrumentation cables pair PVC-Nylon (or 105 °C PVC) core insulation with 100% foil shielding and optional SWA or Interlock metallic armor.
- Conductor: 7-wire Class B concentric stranded annealed electrolytic copper (20 AWG to 12 AWG / 0.5 mm² to 2.5 mm²).
- Core Insulation: Dual-layer 90 °C flame-retardant PVC + clear Polyamide Nylon skin (THHN/THWN), or 105 °C flame-retardant PVC.
- Electrostatic Shielding: Overall 100% Aluminum/Polyester tape + tinned Cu drain wire (SP), or Individual pair/triad foil + drain + Overall foil shield (SB).
- Inner Jacket & Armor (Optional): Extruded PVC inner bedding + Galvanized Steel Wire Armor (SWA / -H) or Galvanized Steel Interlock Armor (-TK).
- Outer Jacket: Sunlight-, oil- and hydrocarbon-resistant PVC outer sheath (Black or Intrinsically Safe Blue).
Signal Integrity, Crosstalk & Noise Rejection
- Full 600 V ICEA S-73-532 / UL 1277 rating: Allows co-routing with 600 V power and control cables in the same cable tray or raceway while providing double the dielectric safety margin of 300 V PLTC.
- PVC + Polyamide Nylon (THHN/THWN) cores: Tough nylon skin over each PVC-insulated conductor resists nicking during terminal stripping and blocks hydrocarbon solvent migration.
- Overall (SP) & Individual+Overall (SB) shields: 100% aluminum-mylar tape + 7-wire tinned copper drain wire on every pair/triad (SB) prevents cross-talk between 4–20 mA, HART, and pulse signals.
- Unarmored, SWA (-H) & Interlock (-TK): Complete mechanical coverage from unarmored UL 1277 tray cables to SWA direct-buried cables and flexible steel Interlock (-TK) armored cables.
Process Plant, Moisture, UV & Chemical Protection
- Built-in 22 AWG orange communication wire: Multi-pair cables include an insulated 22 AWG orange talk-wire beneath the overall shield for headset communication during loop calibration.
- Heavy-duty extruded PVC inner bedding: All SWA (-H) and Interlock (-TK) armored variants incorporate an extruded flame-retardant PVC inner jacket beneath the armor.
- Ripcord for fast jacket stripping: High-strength nylon ripcord under the outer sheath allows rapid jacket removal without scoring the foil shield or inner pairs.
- Matched 600V ICEA S-73-532 control cables: Pair directly with our600V ICEA S-73-532 multi-conductor control cablesfor unified plant raceway design.
EN 50288 / PAS 5308 / Fieldbus Protocol Standards
- ICEA S-73-532 / NEMA WC 57: Standard for Control, Thermocouple Extension, and Instrumentation Cables
- UL 1277: 600 V Electrical Power and Control Tray Cables — Type TC) & NEC Article 336
- UL 83: Thermoplastic-Insulated Wires and Cables — 90 °C THHN / 75 °C THWN PVC-Nylon
- UL 1685 / IEEE 383 / IEEE 1202 & IEC 60332-3-24 Cat. C: Vertical tray flame propagation
- ASTM B8 Class B / IEC 60228: 7-wire concentric stranded annealed copper conductors
Instrumentation & Industrial Bus Guides

600V ICEA S-73-532 / UL 1277 Type TC Process Control & Telemetry Topology
Whenever instrumentation twisted pairs or triads must share cable trays, conduits, or marshalling enclosures directly with 480 V / 600 V power and control circuits without metallic dividers under NEC Article 336 (Type TC), or when EPC specifications call for 600 V ICEA S-73-532 (NEMA WC 57) & UL 1277 insulation margins instead of 300 V PLTC, our 600 V PVC-Nylon and 105 °C PVC Shielded Instrumentation Cable family is the standard solution. In the PVC-Nylon (THHN / THWN) series, each 7-strand copper conductor (20 AWG to 12 AWG) is insulated with 15–20 mils of 90 °C flame-retardant PVC over-extruded with a tough 4–5 mil clear Polyamide Nylon armor skin—delivering high dielectric strength, cut-through resistance, and gasoline/oil immunity per UL 83.
For high-ambient-temperature zones without nylon, we also manufacture the 600 V 105 °C single-wall PVC series. Both series are offered with 100% Overall Aluminum/Polyester Foil Shielding (SP) or Individual Pair/Triad + Overall Foil Shielding (SB) with tinned copper drain wires, and can be specified in three mechanical protection levels: (1) Unarmored 600 V Type TC for open ladder trays and conduits, (2) Galvanized Steel Wire Armored (SWA / -H) for direct burial and high-tension underground duct pulls, and (3) Galvanized Steel Interlock Armored (-TK) for crush-resistant overhead pipe racks. For 300 V PLTC/ITC instrumentation, compare with our300V UL 13 PLTC / UL 2250 ITC cables.
DCS, PLC, Fieldbus & Sensor Network Routes
- 600 V ICEA S-73-532 / UL 1277 Unarmored PVC-Nylon & 105 °C PVC Shielded Cables (1 to 36 pairs/triads, 20–12 AWG) wire process transmitters, control valves, analyzer houses, and turbine skid instrumentation in refineries, petrochemical plants, cement factories, and power generating stations.
- 600 V SWA-Armored (-H) and Interlock-Armored (-TK) PVC-Nylon Instrumentation Cables protect multi-pair DCS/SCADA home-run trunks routed through direct-buried tank-farm trenches, rocky soils, or exposed structural steel without conduit.
600V ICEA S-73-532 / UL 1277 Type TC Impedance, Grounding & Bus FAQ
When should I specify 600 V ICEA S-73-532 / UL 1277 PVC-Nylon instrumentation cable instead of 300 V UL 13 PLTC?
Specify 600 V ICEA S-73-532 / UL 1277 Type TC instrumentation cable whenever the instrumentation cables are routed inside the same cable tray, conduit, or junction box as 480 V / 600 V power and control conductors without a barrier, or when project specifications mandate THHN/THWN PVC-Nylon insulated cores.
What benefit does the Polyamide Nylon layer over the PVC core insulation provide?
The extruded polyamide nylon jacket over each PVC-insulated conductor acts as an tough mechanical and chemical shield: it prevents conductor nicking during wire stripping, reduces inter-pair friction during cable bending, and blocks liquid hydrocarbons or solvents from attacking the primary PVC dielectric.
How do the SWA (-H) and Interlock (-TK) armored 600 V instrumentation variants differ?
SWA (-H) applies a full layer of round galvanized steel wires over the inner PVC jacket for high tensile strength in underground trenches. Interlock (-TK) applies a helically interlocked galvanized steel strip beneath the outer PVC jacket, providing crush protection and flexible routing on above-ground refinery pipe racks.
Do multi-pair 600 V ICEA S-73-532 cables include a communication wire?
Yes. Multi-pair constructions include a 22 AWG PVC-Nylon insulated orange communication/talk wire under the overall shield to facilitate field technician voice communication during loop checking.
Dimensional, weight, resistance, and capacitance tables for 600 V ICEA S-73-532 / UL 1277 PVC-Nylon and 105 °C PVC shielded pair and triad instrumentation cables across Unarmored, SWA (-H) and Interlock (-TK) constructions.
TEBAOFLEX® — 600V ICEA S-73-532 / UL 1277 PVC-Nylon Shielded Process Instrumentation Cable
| Formation × Gauge (AWG / mm²) | Shield Type | PVC + Nylon Wall (mm) | Unarmored OD (mm) | Unarmored Weight (kg/km) | SWA (-H) OD / Weight (mm / kg/km) | Interlock (-TK) OD / Weight (mm / kg/km) |
|---|---|---|---|---|---|---|
| 1 Pair × 18 AWG (1.0 mm²) | Overall (SP) | 0.38 + 0.10 | 6.8 | 62 | 11.4 / 255 | 12.4 / 205 |
| 2 Pairs × 18 AWG (1.0 mm²) | SP / Ind.+Ov. (SB) | 0.38 + 0.10 | 9.8 / 10.6 | 115 / 138 | 14.6 / 385 | 15.6 / 315 |
| 4 Pairs × 18 AWG (1.0 mm²) | SP / Ind.+Ov. (SB) | 0.38 + 0.10 | 11.8 / 13.0 | 185 / 225 | 16.8 / 505 | 17.8 / 420 |
| 8 Pairs × 18 AWG (1.0 mm²) | SP / Ind.+Ov. (SB) | 0.38 + 0.10 | 15.6 / 17.4 | 335 / 405 | 21.0 / 775 | 22.0 / 645 |
| 12 Pairs × 18 AWG (1.0 mm²) | SP / Ind.+Ov. (SB) | 0.38 + 0.10 | 18.8 / 21.0 | 485 / 590 | 24.6 / 1,040 | 25.6 / 865 |
| 24 Pairs × 18 AWG (1.0 mm²) | SP / Ind.+Ov. (SB) | 0.38 + 0.10 | 25.8 / 29.0 | 920 / 1,130 | 32.4 / 1,820 | 33.4 / 1,510 |
| 1 Pair × 16 AWG (1.5 mm²) | Overall (SP) | 0.38 + 0.10 | 7.4 | 78 | 12.0 / 285 | 13.0 / 230 |
| 2 Pairs × 16 AWG (1.5 mm²) | SP / Ind.+Ov. (SB) | 0.38 + 0.10 | 10.8 / 11.6 | 150 / 178 | 15.6 / 445 | 16.6 / 365 |
| 4 Pairs × 16 AWG (1.5 mm²) | SP / Ind.+Ov. (SB) | 0.38 + 0.10 | 13.0 / 14.2 | 245 / 295 | 18.0 / 605 | 19.0 / 505 |
| 8 Pairs × 16 AWG (1.5 mm²) | SP / Ind.+Ov. (SB) | 0.38 + 0.10 | 17.4 / 19.2 | 450 / 540 | 23.0 / 955 | 24.0 / 795 |
| 12 Pairs × 16 AWG (1.5 mm²) | SP / Ind.+Ov. (SB) | 0.38 + 0.10 | 20.8 / 23.0 | 655 / 785 | 26.8 / 1,310 | 27.8 / 1,090 |
| 24 Pairs × 16 AWG (1.5 mm²) | SP / Ind.+Ov. (SB) | 0.38 + 0.10 | 28.8 / 32.0 | 1,260 / 1,510 | 35.6 / 2,310 | 36.6 / 1,920 |
| 1 Pair × 14 AWG (2.5 mm²) | Overall (SP) | 0.38 + 0.10 | 8.2 | 105 | 12.8 / 325 | 13.8 / 265 |
| 4 Pairs × 14 AWG (2.5 mm²) | SP / Ind.+Ov. (SB) | 0.38 + 0.10 | 14.6 / 15.8 | 345 / 405 | 19.8 / 765 | 20.8 / 635 |
| 1 Triad × 16 AWG (1.5 mm²) | Overall (SP) | 0.38 + 0.10 | 7.9 | 95 | 12.5 / 310 | 13.5 / 250 |
| 8 Triads × 16 AWG (1.5 mm²) | SP / Ind.+Ov. (SB) | 0.38 + 0.10 | 19.8 / 21.8 | 610 / 720 | 25.6 / 1,220 | 26.6 / 1,020 |
Selection guide: Specify 600 V ICEA S-73-532 / UL 1277 insulation system (90 °C PVC-Nylon THHN/THWN or 105 °C single-wall PVC), shield configuration (Overall SP or Individual+Overall SB), armor option (Unarmored, SWA -H, or Interlock -TK), and pair/triad count.
Ordering & Quotation Checklist: Request a factory quotation for 600 V ICEA S-73-532 / UL 1277 PVC-Nylon or 105 °C PVC shielded instrumentation cables (Unarmored, SWA or Interlock).
300V UL 13 PLTC / UL 2250 ITC Shielded Instrumentation & Thermocouple Cable
UL 13 (Type PLTC), UL 2250 (Type ITC), ANSI MC 96.1 / IEC 60584 (Armored Thermocouple)
600V ICEA S-73-532 Multi-Conductor Control Cable (PVC, XLPE, LSZH & Armored)
ICEA S-73-532 / NEMA WC 57, UL 1277 (Type TC), IEC 60332-3-24 Cat. C, IEC 60754 / 61034
00/12/FO2, RMP200 & 6XM524 Pipe Crawler & C-3400 / 26XM520 Cleaning Robot Cable
00/12/FO2, 00/20/FOX2 (Electro-Optical), 524/11 (11-Core Copper), RMP200 / RMP300 / RMP350 / RMP500, 6XM524, 1HRS347
Request Quotation & Datasheet for This Cable
Need factory pricing, cross-section drawing or a full PDF datasheet for 600V ICEA S-73-532 / UL 1277 PVC-Nylon Shielded Process Instrumentation Cable? Share your core count, conductor size, length and destination country—our Taicang cable engineers reply within 24 hours.
- ISO 9001 Factory Direct
- MOQ 50 m (Custom Builds)
- 24h Engineering Reply