1500 V DC Aluminum Solar PV Feeder Cable: PV Al, LSZH, Heavy-Duty & AWA/SWA

PV Al 1500 V DC, PV LSZH Al 1500 V DC, PV LSZH Al 1500 V Heavy Duty and PV AWA/SWA Al 1500 V DC are large-cross-section (1×16 mm² to 1×400 mm² and 2×16 to 2×240 mm²) aluminum DC collector feeder cables engineered to IEC 60502-1 for utility-scale 1,500 V DC photovoltaic power plants. Connecting solar tracker combiner boxes to central inverters or DC-coupled BESS skids.

  • Model designationsPV Al 1500 V, PV LSZH Al 1500 V, PV Al Heavy Duty & PV AWA/SWA Al 1500 V
  • Reference standardsIEC 60502-1, EN 50618 / UNE 211605 (UV), EN 60754-1/2 (LSZH), IEC 60228
  • Rated DC & AC voltage1,500 V DC (max. 1,800 V DC operating) / 0.6/1 kV AC; 6,500 V DC test
  • ConductorClass 2 compact stranded (or Class 5 flexible) aluminum, 16 mm² to 400 mm²
  • InsulationReinforced-wall 90 °C cross-linked polyethylene (XLPE), +250 °C short-circuit
  • Outer sheath / armorBlack/red UV PVC, halogen-free LSZH, AG3 Heavy Duty, or AWA (1C) / SWA (2C) wire armor
  • Water & impact ratingAD7 immersion / AD8 submersion; AG3 / AG4 high-impact direct burial
  • Operating temperature-40 °C to +90 °C continuous (+120 °C max. overload); 30-year solar design life

PV Al 1500 V DC, PV LSZH Al 1500 V, Heavy Core Identification & Ratings

  • Type: EV Charging & Solar Cable
  • Model designations: PV Al 1500 V, PV LSZH Al 1500 V, PV Al Heavy Duty & PV AWA/SWA Al 1500 V
  • Reference standards: IEC 60502-1, EN 50618 / UNE 211605 (UV), EN 60754-1/2 (LSZH), IEC 60228
  • Rated DC & AC voltage: 1,500 V DC (max. 1,800 V DC operating) / 0.6/1 kV AC; 6,500 V DC test

Electrical, Thermal & Mechanical Bend Limits

  • Conductor: Class 2 compact stranded (or Class 5 flexible) aluminum, 16 mm² to 400 mm²
  • Insulation: Reinforced-wall 90 °C cross-linked polyethylene (XLPE), +250 °C short-circuit
  • Outer sheath / armor: Black/red UV PVC, halogen-free LSZH, AG3 Heavy Duty, or AWA (1C) / SWA (2C) wire armor
  • Water & impact rating: AD7 immersion / AD8 submersion; AG3 / AG4 high-impact direct burial
  • Operating temperature: -40 °C to +90 °C continuous (+120 °C max. overload); 30-year solar design life

PV Al 1500 V DC, PV LSZH Al 1500 V, Heavy Conductor, Insulation & Sheath Build

1500 V DC Aluminum Solar Feeder Cables combine compacted aluminum conductors with reinforced 90 °C XLPE insulation and UV/burial-engineered PVC, LSZH, Heavy-Duty, or AWA/SWA jackets.

  • Conductor (Al): Class 2 circular compact stranded aluminum (or Class 5 flexible aluminum on request), 16–400 mm² per IEC 60228.
  • Insulation (XLPE): Reinforced-wall 90 °C cross-linked polyethylene (XLPE) rated for 1,500 V DC continuous (1,800 V DC max).
  • Inner Bedding / Armor (AWA/SWA): On PV AWA/SWA Al: extruded inner bedding sheath + Aluminum Wire Armor (1-core) or Galvanized Steel Wire Armor (2-core).
  • Outer Sheath: UV-stabilized black/red PVC (PV Al), halogen-free polyolefin (PV LSZH Al), thickened AG3 polyolefin (Heavy Duty), or armored outer sheath.

Primary Electrical & Mechanical Performance

  • True 1,500 V DC (1,800 V DC max) dielectric: Reinforced XLPE insulation wall withstands continuous 1,500 V DC (1,800 V DC max) bipolar or floating solar bus voltages without DC space-charge breakdown.
  • 4 trench-ready outer constructions: Choose standard UV PVC, halogen-free LSZH, Heavy-Duty direct-burial LSZH, or rodent-proof AWA (1-core) / SWA (2-core) wire-armored designs.
  • 16 mm² to 400 mm² DC collector sizing: Sized specifically to keep combiner-box-to-inverter DC voltage drop below 1.0%–1.5% across 200 m to 800 m solar tracker rows.
  • UV, ozone & AD7/AD8 moisture immunity: Passes EN 50618 / UNE 211605 UV weathering for exposed tracker risers and AD7/AD8 underground water immersion.

Industrial Oil, Flame & Environmental Protection

  • Compacted Class 2 aluminum conductor: Circular compact stranded aluminum per IEC 60228 ensures gas-tight crimping in bimetallic solar combiner lugs and inverter busbars.
  • Heavy-Duty impact & abrasion shield: PV LSZH Al Heavy Duty increases radial sheath thickness to resist sharp backfill stones and thermal soil movement.
  • AWA / SWA metallic wire armor option: PV AWA/SWA Al 1500 V provides AG4 mechanical impact severity and 100% rodent defense for direct-buried DC main feeders.
  • Red / Black polarity identification: Supplied with black outer sheath (with optional red co-extruded polarity stripe or red/black core identification) for error-free DC +/− pairing.

IEC / EN / VDE / UL Reference Standards

  • IEC 60502-1: 1,500 V DC / 0.6/1 kV AC extruded XLPE insulated power cables
  • EN 50618 & UNE 211605: UV weather resistance and 1,500 V DC photovoltaic endurance
  • EN 60754-1 / EN 60754-2: Halogen-free LSZH jacket on PV LSZH Al & Heavy Duty series
  • IEC 60228 Class 2 compact stranded: or Class 5 flexible) aluminum conductors

Industrial Cable Selection & Routing Guides

Utility-scale solar array inverters and combiner trenches wired with 1500 V DC PV Al, PV LSZH Al Heavy Duty and PV AWA/SWA Al aluminum feeder cables
1500 V DC Aluminum Solar PV Feeder Cables (PV Al, PV LSZH Al, Heavy Duty & AWA/SWA) connect combiner boxes to central inverters across utility solar farms. Photo: Wikimedia Commons contributor, CC BY-SA 4.0, via Wikimedia Commons.

PV Al 1500 V DC, PV LSZH Al 1500 V, Heavy Industrial Installation & Routing Guide

In utility-scale 1,500 V DC photovoltaic power plants, copper string cables (4 mm² to 10 mm²H1Z2Z2-K 1500 V DC solar wireterminate at string combiner boxes or multi-MPPT harnesses, from where high-current DC collector trunks (50 mm² to 400 mm², carrying 150 A to 650 A DC) run hundreds of meters underground to central inverters or DC-coupled battery containers. Specifying 1500 V DC Aluminum Solar PV Feeder Cables over these long DC collector runs cuts conductor cost by up to 60% and halves drum pulling weight.

To match every trench and soil condition across global solar EPC projects, we manufacture four specialized 1,500 V DC (1,800 V DC max) aluminum feeder constructions under IEC 60502-1: PV Al 1500 V (reinforced XLPE insulation + UV/AD7 PVC jacket, CPR Eca); PV LSZH Al 1500 V (halogen-free polyolefin jacket per EN 60754-1/2); PV LSZH Al 1500 V Heavy Duty (thickened impact-resistant double/reinforced LSZH jacket for direct burial in rocky soil without sand bedding); and PV AWA/SWA Al 1500 V (non-magnetic Aluminum Wire Armor AWA on single-core 1×25–400 mm² or Galvanized Steel Wire Armor SWA on 2-core 2×16–240 mm² for severe rodent, termite, and crushing protection). For MV inverter-to-grid connections, pair with ourRHZ1-OL / RHZ1-2OL 12/20–18/30 kV MV aluminum cables.

Typical Plant, Machine & Infrastructure Circuits

  • Single-core 1×70 mm² through 1×400 mm² PV Al 1500 V (+ / − pairs) connect DC string combiner boxes (SCBs) to central inverter skids (2.5 MW to 6.8 MW blocks) and DC-coupled1500 V DC battery energy storage systems (BESS)in desert, agricultural, and coastal utility solar parks.
  • PV LSZH Al 1500 V Heavy Duty and PV AWA/SWA Al 1500 V are engineered for mechanized trench plowing in stony desert terrain, rodent- and gopher-infested pastures, and unarmored-prohibited EPC specifications where sand-bedding import is cost-prohibitive.

PV Al 1500 V DC, PV LSZH Al 1500 V, Heavy Specification & Selection FAQ

Why are 1500 V DC Aluminum Solar Feeder Cables used between combiner boxes and central inverters?

While 4–10 mm² tinned copper H1Z2Z2-K cables are ideal for flexible module-to-string-combiner connections, the main DC collector runs from combiner boxes to central inverters require 70–400 mm² cross-sections over distances of 200–800 meters. Using 1500 V DC aluminum feeders reduces cable cost by ~60% and cuts pulling weight in half.

When should PV LSZH Al 1500 V Heavy Duty be chosen over standard PV Al 1500 V?

PV LSZH Al 1500 V Heavy Duty features a reinforced, extra-thick abrasion- and impact-resistant halogen-free polyolefin sheath designed for direct burial in rocky solar farm trenches without importing fine sand bedding.

When is PV AWA/SWA Al 1500 V required?

PV AWA/SWA Al 1500 V adds a full crown of Aluminum Wire Armor (AWA on single-core cables) or Galvanized Steel Wire Armor (SWA on 2-core cables), providing 100% protection against gophers, rats, termites, and heavy vehicle wheel loads across solar farm access roads.

What is the maximum continuous DC voltage of PV Al 1500 V cables?

All four variants are rated for 1,500 V DC nominal and up to 1,800 V DC maximum continuous operating voltage between conductors or between conductor and earth, tested at 6,500 V DC for 5 minutes.

Dimensional, weight, current-rating, and voltage-drop specifications for 1,500 V DC PV Al, PV LSZH Al, Heavy Duty and AWA/SWA Armored aluminum solar feeder cables (16 mm² to 400 mm²).

TEBAOFLEX® — 1500 V DC Aluminum Solar PV Feeder Cable: PV Al, LSZH, Heavy-Duty & AWA/SWA

PV Al 1500 V DC & PV LSZH Al 1500 V DC (Standard & Heavy Duty) Single-Core Specifications (IEC 60502-1)
Cross-Section (mm²) Std OD (mm) Std Weight (kg/km) Heavy-Duty OD (mm) Heavy-Duty Weight (kg/km) Max. DC Res. 20 °C (Ω/km) Ampacity Open Air 30 °C (A) Ampacity Buried 20 °C (A) DC Voltage Drop (V/A·km)
1 × 16 Al 9.5 110 11.1 145 1.91 97 81 4.58
1 × 25 Al 11.0 155 12.6 195 1.20 128 104 2.88
1 × 35 Al 12.1 195 13.7 240 0.868 157 125 2.08
1 × 50 Al 13.6 250 15.2 305 0.641 192 149 1.54
1 × 70 Al 15.4 330 17.0 390 0.443 246 185 1.06
1 × 95 Al 17.3 430 19.1 505 0.320 302 221 0.768
1 × 120 Al 19.0 525 20.8 610 0.253 352 252 0.607
1 × 150 Al 21.0 645 22.8 740 0.206 406 285 0.494
1 × 185 Al 23.2 795 25.0 905 0.164 466 322 0.394
1 × 240 Al 26.0 1,020 28.0 1,150 0.125 552 373 0.300
1 × 300 Al 28.8 1,260 30.8 1,410 0.100 636 421 0.240
1 × 400 Al 32.4 1,620 34.6 1,805 0.0778 742 485 0.187

TEBAOFLEX® — 1500 V DC Aluminum Solar PV Feeder Cable: PV Al, LSZH, Heavy-Duty & AWA/SWA

PV AWA / SWA Al 1500 V DC Wire-Armored Aluminum Solar Feeder Cable Specifications (1-Core AWA & 2-Core SWA)
Formation (Cores × mm²) Wire Armor Type Overall OD (mm) Approx. Weight (kg/km) Ampacity Open Air 30 °C (A) Ampacity Buried 20 °C (A) DC Voltage Drop (V/A·km)
1 × 25 Al Aluminum Wire Armor (AWA) 16.2 340 128 104 2.88
1 × 50 Al Aluminum Wire Armor (AWA) 18.8 485 192 149 1.54
1 × 95 Al Aluminum Wire Armor (AWA) 23.0 760 302 221 0.768
1 × 150 Al Aluminum Wire Armor (AWA) 27.4 1,110 406 285 0.494
1 × 240 Al Aluminum Wire Armor (AWA) 32.8 1,640 552 373 0.300
1 × 300 Al Aluminum Wire Armor (AWA) 36.0 2,010 636 421 0.240
1 × 400 Al Aluminum Wire Armor (AWA) 40.2 2,560 742 485 0.187
2 × 25 Al Galv. Steel Wire Armor (SWA) 24.8 1,020 108 92 2.88
2 × 50 Al Galv. Steel Wire Armor (SWA) 29.6 1,490 162 132 1.54
2 × 95 Al Galv. Steel Wire Armor (SWA) 37.2 2,460 252 195 0.768
2 × 150 Al Galv. Steel Wire Armor (SWA) 44.5 3,580 338 252 0.494
2 × 240 Al Galv. Steel Wire Armor (SWA) 54.2 5,290 458 330 0.300

Selection guide: Specify PV Al 1500 V (PVC), PV LSZH Al 1500 V, PV LSZH Al 1500 V Heavy Duty (direct burial), or PV AWA/SWA Al 1500 V (wire armored), and aluminum cross-section (1×16 to 1×400 mm² or 2×16 to 2×240 mm²). For TÜV 2 PfG 1169 PV1-F, dual-certified PV1-F / UL 4703 PV-Wire (copper and AA-8000 aluminum), and twin parallel or steel-braided rodent-proof solar string cables, seePV1-F, Dual-Rated PV1-F / UL 4703 & Twin Rodent-Resistant Solar PV Cable.

Ordering & Quotation Checklist: Request a factory quotation for 1500 V DC Aluminum Solar PV Feeder Cables — PV Al, PV LSZH Al, Heavy Duty Buried, or PV AWA/SWA Armored (16–400 mm²).

RHZ1-OL, RHZ1-2OL, RHZ1 (S/AS) & RH5Z1 6/10–18/30 kV MV XLPE Power Cable

RHZ1-OL, RHZ1-2OL, RHZ1 (S/AS) & RH5Z1 6/10–18/30 kV MV XLPE Power Cable

RHZ1-OL / RHZ1-2OL (AL & CU), RHZ1 (S), RHZ1 (AS), RHZ1 Triplex & RH5Z1-OL/2OL

VIEW PRODUCT »

FHL2G Unscreened 1000V AC / 1500V DC Silicone EV High-Voltage Cable (ISO 6722)

FHL2G Unscreened 1000V AC / 1500V DC Silicone EV High-Voltage Cable (ISO 6722)

FHL2G (Unscreened Fine-Stranded High-Voltage Silicone Road Vehicle Cable)

VIEW PRODUCT »

Direct Factory Engineering RFQ

Request Quotation & Datasheet for This Cable

Need factory pricing, cross-section drawing or a full PDF datasheet for 1500 V DC Aluminum Solar PV Feeder Cable: PV Al, LSZH, Heavy-Duty & AWA/SWA? Share your core count, conductor size, length and destination country—our Taicang cable engineers reply within 24 hours.

  • ISO 9001 Factory Direct
  • MOQ 50 m (Custom Builds)
  • 24h Engineering Reply
WhatsApp / Direct Line+86 156 3992 7303

    Leave Us a Message

    Whether you need a quotation, have a technical question or want a cable recommendation, our engineers reply within 24 hours.

    1500 V DC Aluminum Solar PV Feeder Cable: PV Al, LSZH, Heavy-Duty & AWA/SWAGet A Quote