3-Phase AC and DC Voltage Drop Calculation Formula: Temperature Correction from 20 °C to 90 °C and Reactance Rules
Step-by-step calculation guide covering balanced 3-phase AC, single-phase AC, and DC feeder voltage drop formulas, 20 °C to 90 °C conductor temperature scaling, IEC 60228 datasheet resistance limits, and reactive impedance.

- 3-Phase AC Formula
- ΔU = √3 × I × (R_T cos φ + X sin φ) × L / n
- 1-Phase AC Formula
- ΔU = 2 × I × (R_T cos φ + X sin φ) × L / n
- DC Loop Formula
- ΔU = 2 × I × R_T × L / n (X = 0)
- Metal Constants
- Cu: ρ₂₀=0.017241, α₂₀=0.00393 · Al: 0.028264, 0.00403
Calculate balanced three-phase AC voltage drop using the factor √3 multiplied by current, one-way length, and hot feeder impedance. For single-phase AC and DC circuits, replace √3 with 2 and remove reactance X at 0 Hz. Every reliable feeder check first scales 20 °C conductor resistance to operating temperature T before finding percentage drop. Engineers can run live sizing scenarios in our voltage drop calculator or compute hot resistance first in our conductor resistance calculator.
1. What Is the Formula for 3-Phase AC, Single-Phase AC, and DC Voltage Drop?
Balanced three-phase voltage drop equals ΔU = √3 × I × (RT cos φ + X sin φ) × L / n in volts. Single-phase AC uses the exact same impedance terms with a leading factor of 2 instead of √3. Steady DC circuits also use 2, set cos φ equal to 1, and drop X sin φ completely. Percentage voltage drop then equals 100 × ΔU / U.
Always measure supply voltage U between phases for three-phase circuits, or across poles for DC and single-phase loops. One-way length L stays in kilometers without manual doubling because √3 and 2 already model circuit path geometry. Table 1 defines each equation alongside its governing technical standard.
| System Type | Core Formula (Volts ΔU) | Leading Factor | Active Impedance Term | Reference Supply U | Governing Technical Basis |
|---|---|---|---|---|---|
| Balanced 3-Phase AC | ΔU = √3 × I × (R_T cos φ + X sin φ) × L / n | √3 (1.7321) | Resistive plus reactive | Line-to-line (400 V, 690 V) | IEC 60364-5-52 Annex G |
| Single-Phase 2-Wire AC | ΔU = 2 × I × (R_T cos φ + X sin φ) × L / n | 2.0000 | Resistive plus reactive | Line-to-neutral (120 V, 230 V) | IEC 60364-5-52 & EEPower NEC guide |
| Direct Current (DC) | ΔU = 2 × I × R_T × L / n | 2.0000 | Pure DC resistance only | Pole-to-pole (+ to −, 24–1500 V) | IEC 60028 & NBS HB 100 / 109 |
Sources: IEC 60364-5-52 Annex G steady-state voltage drop methodology, IEC 60028, NBS Handbook 100, and NBS Handbook 109.
Why Does 3-Phase AC Use √3 While Single-Phase and DC Use 2?
Current in a two-wire DC or single-phase circuit flows outbound on one wire and returns at full current through the second wire. That return path doubles total conductor impedance across twice the route distance, producing the multiplier 2 × L.
Balanced three-phase loads behave differently because currents across L1, L2, and L3 sit 120 electrical degrees apart and sum to zero in the neutral. Each line drops only I × Z × L relative to neutral. Multiplying phase-to-neutral drop by √3 (1.7321) converts that phase drop directly into line-to-line terminal voltage loss.
Phase geometry in an electrical equation never fixes physical core count inside one outer jacket. One three-phase feeder might pull single-core cables in trefoil or use a multi-core construction carrying earth and pilot wires. Consult our three-phase cable core schedules when mapping circuit equations into a procurement core schedule.
Every term in Table 1 uses strict SI engineering definitions:
- I (Amperes, A): Steady continuous load current per phase or DC pole, not protective breaker frame size.
- L (Kilometers, km): One-way route distance along tray or trench from source to load (100 m = 0.100 km).
- RT (Ω/km): Single-conductor resistance per kilometer scaled to loaded conductor operating temperature T (°C).
- X (Ω/km): Line-frequency inductive reactance per kilometer at 50 Hz or 60 Hz; zero for steady DC circuits.
- cos φ and sin φ: Load power factor entered as a decimal (0.10–1.00), with sin φ = √(1 − cos² φ).
- n (dimensionless): Count of identical parallel cables connected per phase or per DC pole.
System voltage U also dictates how severely a fixed volt drop impacts connected equipment. Losing 6.6 V equals 5.50% on a 120 V circuit, compared with only 2.87% on a 230 V supply. Higher distribution voltages therefore transport power much farther per percent drop, as shown in EEPower’s NEC voltage drop primer.

2. How Does Conductor Temperature Change Resistance from 20 °C to 90 °C?
Hot conductors resist current flow significantly more than cold conductors, following RT = R₂₀ × [1 + α₂₀ × (T − 20)]. For annealed copper (100% IACS), α₂₀ equals 0.00393 per °C. Copper resistance therefore rises 19.65% at 70 °C and 27.51% at 90 °C. Hard-drawn EC aluminum (61.0% IACS) has α₂₀ = 0.00403 per °C, raising resistance by 20.15% at 70 °C and 28.21% at 90 °C.
Checking a loaded 90 °C XLPE feeder with cold 20 °C resistance values understates real voltage drop by roughly 21%–28%. Two algebraic forms convert 20 °C resistance to hot service temperature, and both deliver equivalent results when matched to 20 °C base constants:
- Linear temperature-coefficient form: Multiply R₂₀ by [1 + α₂₀ × (T − 20)] using α₂₀ = 0.00393 /°C for copper or 0.00403 /°C for aluminum.
- Inferred-zero-resistance form: Multiply R₂₀ by (K + T) / (K + 20), where K equals 234.5 °C for copper and 228.1 °C for aluminum per NBS Handbook 100 and NBS Handbook 109.
Always plug in conductor operating temperature T rather than ambient air temperature. Under rated load, core copper approaches its insulation ceiling. PVC power cables such as DIN VDE 0276 NYY-J and NYY-O top out at 70 °C (1.1965× copper factor). Cross-linked XLPE and halogen-free N2XH and N2XCH power cables allow 90 °C continuous operation (1.2751× copper factor).
North American wire schedules add 60 °C and 75 °C breakpoints for building wire and terminal limits. Wet 60 °C circuits multiply R₂₀ by 1.1572× in copper and 1.1612× in aluminum. Feeders capped at 75 °C terminations multiply copper R₂₀ by 1.2162× and aluminum R₂₀ by 1.2217×.
When working from imperial drawings, convert sizes first in our AWG to mm² converter or inspect multi-core nomenclature in our AWG copper and aluminum guide. Browse every engineering converter together in the TEBAOFLEX cable tools suite.
Why Do IEC 60228 Datasheet Limits Exceed Solid IACS Calculations by 5% to 12%?
Theoretical calculators model an ideal solid round rod with ρ₂₀ = 0.017241 Ω·mm²/m for copper or 0.028264 Ω·mm²/m for EC aluminum. Factory datasheets instead publish guaranteed maximum R₂₀ values standardized in IEC 60228:2023 (compare all Class 1, 2, 5, and 6 limits across 0.5–300 mm² in our IEC 60228 conductor classes guide). Those standard limits account for helical strand lay length (+2% wire path), draw tolerances, and compaction variances.
Check the 50 mm² copper row in Table 2 closely. Solid IACS math gives 0.345 Ω/km at 20 °C, whereas IEC 60228 Class 1 and Class 2 allow up to 0.387 Ω/km (+12.2% higher). Fine-stranded Class 5 copper in flexible RZ1-K XLPE power cables permits slightly higher maxima on several gauges (such as 0.554 Ω/km at 35 mm² and 0.161 Ω/km at 120 mm²). Scale datasheet R₂₀ by the operating temperature factor first, then enter that hot RT into the voltage calculator override field.
| Area (mm²) | Solid Cu 20 °C | IEC Cl.2 Cu 20 °C | IEC Cu 70 °C (×1.1965) | IEC Cu 90 °C (×1.2751) | IEC Cl.2 Al 20 °C | IEC Al 70 °C (×1.2015) | IEC Al 90 °C (×1.2821) |
|---|---|---|---|---|---|---|---|
| 1.5 | 11.494 | 12.100 | 14.478 | 15.429 | Not standard | Not standard | Not standard |
| 2.5 | 6.896 | 7.410 | 8.866 | 9.448 | Not standard | Not standard | Not standard |
| 4 | 4.310 | 4.610 | 5.516 | 5.878 | Not standard | Not standard | Not standard |
| 6 | 2.874 | 3.080 | 3.685 | 3.927 | Not standard | Not standard | Not standard |
| 10 | 1.724 | 1.830 | 2.190 | 2.333 | Not standard | Not standard | Not standard |
| 16 | 1.078 | 1.150 | 1.376 | 1.466 | 1.910 | 2.295 | 2.449 |
| 25 | 0.690 | 0.727 | 0.870 | 0.927 | 1.200 | 1.442 | 1.539 |
| 35 | 0.493 | 0.524 | 0.627 | 0.668 | 0.868 | 1.043 | 1.113 |
| 50 | 0.345 | 0.387 | 0.463 | 0.493 | 0.641 | 0.770 | 0.822 |
| 70 | 0.246 | 0.268 | 0.321 | 0.342 | 0.443 | 0.532 | 0.568 |
| 95 | 0.181 | 0.193 | 0.231 | 0.246 | 0.320 | 0.384 | 0.410 |
| 120 | 0.144 | 0.153 | 0.183 | 0.195 | 0.253 | 0.304 | 0.324 |
| 150 | 0.115 | 0.124 | 0.148 | 0.158 | 0.206 | 0.248 | 0.264 |
| 185 | 0.093 | 0.0991 | 0.119 | 0.126 | 0.164 | 0.197 | 0.210 |
| 240 | 0.072 | 0.0754 | 0.090 | 0.096 | 0.125 | 0.150 | 0.160 |
Sources: Solid values from NBS Handbook 100 (ρ₂₀ Cu 0.017241) and NBS Handbook 109 (α₂₀ Al 0.00403); plain Class 1/2 maxima from IEC 60228:2023.
Look at the fixed metal ratio across every row from 16 mm² to 240 mm². Solid EC aluminum has 1.639× higher resistivity than copper, and IEC 60228 Class 2 aluminum maxima stand 1.65×–1.66× above equal copper gauges. Study metallurgy and termination rules in our aluminum conductor guide and copper conductor guide before switching feeder metals.
3. When Do Power Factor, Inductive Reactance, and Parallel Runs Govern the Result?
Inductive reactance X strongly affects AC voltage drop once cross-sections reach 35–50 mm² and load power factor falls below unity. Small 2.5 mm² lighting circuits are resistance-dominated, so X changes their drop by under 1%. Large lagging motor feeders above 120 mm², however, hit an inductive floor near X ≈ 0.08 Ω/km even as copper size doubles.
At unity power factor (cos φ = 1.0), sin φ drops to zero and reactance contributes nothing to ΔU. Once an induction motor runs at lagging power factor cos φ = 0.85, sin φ becomes 0.5268 and weights X heavily. Unlike resistance (which falls smoothly as 1/A), inductive reactance depends mainly on conductor center spacing rather than wire diameter. Following IEC 60364-5-52 practice and our live calculator default, engineers apply X = 0.08 Ω/km when geometry is unspecified at 50 mm² and above.
That flat reactance floor creates a major engineering surprise on heavy AC distribution feeders. Moving up from 185 mm² to 240 mm² or 300 mm² cuts RT cos φ, yet inductive loss (0.08 × sin φ) stays stubbornly unchanged. Splitting one oversized core into n = 2 parallel feeders cuts both resistance share and reactance share directly.
Compare three options for a 400 V, 400 A, 150 m three-phase feeder at 90 °C (cos φ = 0.85, X = 0.08 Ω/km):
- 1 × 240 mm² Cu (n = 1): Solid R₉₀ = 0.0916 Ω/km yields 2.02% resistive drop plus 1.09% reactive drop, totaling 3.12% (12.47 V) and breaching 3%.
- 2 × 120 mm² Cu (n = 2, identical 240 mm² copper): Parallel paths halve reactive drop to 0.55% while matching 2.02% resistive loss, cutting total drop to 2.57% (10.28 V).
- 1 × 300 mm² Cu (n = 1, 25% extra copper): Resistive drop falls to 1.62%, yet unsplit reactance holds at 1.09%, yielding 2.71% (10.85 V), which still trails 2 × 120 mm².
Note that component percentages above round independently from intermediate figures (2.023% + 1.095% = 3.118%). Using parallel feeders also eases tray pulling tension and terminal bend clearance inside compact switchgear cabinets. For adjustable-speed drives carrying steep switching edges and harmonic currents, combine impedance sizing with shielded geometry in our VFD motor cable selection guide.

4. How Do You Work Out 3-Phase AC and 1500 V DC Feeder Drops Step by Step?
Compute steady voltage drop in four sequential steps: find R₂₀, apply the operating temperature factor, calculate weighted impedance, and multiply by circuit factor, current, and length over n. Working through three industrial circuits demonstrates how temperature, IEC tolerance, and reactance alter cable sizing decisions.
Case A: 400 V 3-Phase Industrial Motor Feeder (50 mm² Cu, 120 m, 115 A, 90 °C, cos φ = 0.85)
Evaluate an XLPE 0.6/1 kV copper pump feeder running 120 m (L = 0.120 km) on cable ladders at 90 °C conductor temperature, using X = 0.08 Ω/km (sin φ = 0.5268).
- Cold solid baseline (error-prone check): Solid R₂₀ = 0.017241 × 1000 / 50 = 0.3448 Ω/km. Ignoring temperature and X gives 7.01 V (1.75%).
- Apply 90 °C copper temperature multiplier: R₉₀ = 0.3448 × 1.2751 = 0.4397 Ω/km. Resistance loss jumps 27.5% to 8.93 V (2.23%).
- Include AC reactance (X = 0.08 Ω/km): Effective impedance equals 0.4397 × 0.85 + 0.08 × 0.5268 = 0.4159 Ω/km, yielding 9.94 V (2.49%).
- Substitute IEC 60228 Class 2 max R₂₀: Scaling datasheet ceiling 0.387 Ω/km by 1.2751 produces R₉₀ = 0.4935 Ω/km, pushing total drop to 11.03 V (2.76%).
Omitting both conductor heating and reactance hides 4.02 V (+57.4% error between Step 1 and Step 4). If a plant specification caps drop at 2.5%, Datasheet Check Step 4 tells procurement to step up to 70 mm² before ordering.
Case B: 1500 V DC Solar and BESS Feeder Comparison (120 mm² Al vs. 70 mm² Cu, 220 m, 180 A, 90 °C)
Steady 1500 V DC solar combiners and BESS PCS feeders have zero inductive reactance (X = 0), leaving pure go-and-return hot resistance across L = 0.220 km. Compare a lightweight 120 mm² 1500 V DC aluminum solar feeder against a compact 70 mm² flexible 1500 V DC BESS battery cable operating at 90 °C.
- Aluminum 120 mm² path: Solid EC aluminum R₉₀ (0.2355 × 1.2821 = 0.3020 Ω/km) yields ΔU = 2 × 180 × 0.3020 × 0.220 = 23.92 V (1.59%). With IEC Class 2 max R₂₀ = 0.253 Ω/km (R₉₀ = 0.3244 Ω/km), drop reaches 25.69 V (1.71%).
- Copper 70 mm² path: Solid IACS copper R₉₀ (0.2463 × 1.2751 = 0.3141 Ω/km) yields 24.87 V (1.66%). With IEC Class 2 max R₂₀ = 0.268 Ω/km (R₉₀ = 0.3417 Ω/km), drop reaches 27.06 V (1.80%).
Stepping up one gauge class in aluminum (120 mm² Al vs. 70 mm² Cu) lowers steady DC voltage drop while cutting conductor weight along open trenches. Fixed 0.6/1 kV industrial mains apply this same aluminum economics with U-1000 AR2V and RZ1 Al cables. Meanwhile, tight battery racks rely on flexible copper lug clearance detailed in our 1500 V DC BESS cable guide.
Case C: High-Current 400 V Feeder and IEC 60364-5-52 Annex G Limits
Published voltage drop caps depend on supply ownership rather than wire alloy. Under IEC 60364-5-52 Annex G guidelines, public low-voltage supplies target 3% max for lighting and 5% max for motors and general circuits. Installations with dedicated on-site transformers relax to 6% lighting and 8% other loads. North American NEC 210.19(A) and 215.2(A) informational notes likewise advise keeping branch or feeder runs under 3% individually and 5% combined.
| Circuit Scenario | Size & Metal | Model Basis | R_T (Ω/km) | Drop ΔU (V) | Drop %ΔU | Typical 3% Feeder Check |
|---|---|---|---|---|---|---|
| 400 V 3P AC, 115 A, 120 m, 0.85 PF | 50 mm² Cu (n=1) | Solid 90 °C + X=0.08 | 0.4397 | 9.94 V | 2.49% | Passes 3% (solid) |
| 400 V 3P AC, 115 A, 120 m, 0.85 PF | 50 mm² Cu (n=1) | IEC Cl.2 Max 90 °C + X | 0.4935 | 11.03 V | 2.76% | Passes 3% (tight) |
| 1500 V DC, 180 A, 220 m, PF=1.0 | 120 mm² Al (n=1) | IEC Cl.2 Max 90 °C (X=0) | 0.3244 | 25.69 V | 1.71% | Passes 2% PV DC target |
| 1500 V DC, 180 A, 220 m, PF=1.0 | 70 mm² Cu (n=1) | IEC Cl.2 Max 90 °C (X=0) | 0.3417 | 27.06 V | 1.80% | Passes 2% PV DC target |
| 400 V 3P AC, 400 A, 150 m, 0.85 PF | 240 mm² Cu (n=1) | Solid 90 °C + X=0.08 | 0.0916 | 12.47 V | 3.12% | Exceeds 3% feeder limit |
| 400 V 3P AC, 400 A, 150 m, 0.85 PF | 2 × 120 mm² Cu (n=2) | Solid 90 °C + X=0.08 | 0.1832 | 10.28 V | 2.57% | Passes 3% feeder limit |
Sources: Derived from IEC 60364-5-52 Annex G steady-state equations, NBS Handbook 100 & 109 constants, and IEC 60228:2023 Class 2 resistance limits.

5. When Should Engineers Not Rely on Steady-State Voltage Drop Formulas Alone?
Never treat steady-state voltage drop results as complete circuit approval because these formulas omit motor-starting dips, large-conductor AC skin effect, harmonic currents, and cable thermal ampacity. Passing a 3% steady voltage drop check never verifies current-carrying capacity under tray grouping or short-circuit fault ratings.
Recognize four field regimes where simplified algebraic equations require deeper dynamic modeling:
- Direct-on-line motor starting dips: Locked-rotor currents spike 5×–7× steady amperes while power factor falls near 0.35, amplifying X sin φ transient voltage sag.
- AC skin and proximity effects above 150–240 mm²: At 50 Hz or 60 Hz, eddy currents raise effective resistance Rac = RT × (1 + ys + yp) well above DC datasheet figures.
- Unbalanced loads and triplen harmonics: Non-linear rectifiers force 3rd-order harmonic currents onto shared neutrals, breaking balanced 3-phase √3 vector assumptions.
- Tinned, alloy, or medium-voltage shielded runs: Steel-wire armor losses and medium-voltage phase spacing require construction-specific AC resistance and positive-sequence reactance data.
Calculation and procurement boundary: Never size conductors using cold 20 °C values or skip inductive reactance on 50 mm² and larger AC feeders. Do not mistake passing steady voltage drop for safe thermal ampacity. Verify operating conductor temperature and AC skin effects with an electrical engineer, and before ordering, ask our engineers to confirm maximum conductor resistance and construction details.
6. What Parameters Should Buyers Send Before Ordering Feeder or DC Cables?
Submit six complete circuit parameters instead of a bare cross-section guess so cable engineers can confirm IEC 60228 resistance, thermal rating, and parallel bundle tolerances together. Complete line specifications prevent mid-project gauge changes on industrial power, solar PV, and battery energy storage projects.
Prepare the checklist below alongside our industrial power and control cable hub before releasing a tender:
- Circuit topology and nominal U: State balanced 3-phase AC line-to-line (400 V, 690 V), 1-phase AC, or DC (+/− 24 V to 1500 V DC).
- Continuous current I and power factor cos φ: Specify full-load amperes and whether motor inrush sag limits steady sizing.
- One-way route length L and parallel runs n: Confirm tray or trench distance plus project %ΔU ceiling (for instance 1.5% PV DC or 3% AC feeder).
- Conductor metal and stranding class: Specify annealed copper (Class 1/2 fixed or Class 5 flexible) or EC/AA-8000 aluminum.
- Insulation thermal class (70 °C vs. 90 °C): State PVC (70 °C) or XLPE/EPR/XLPO (90 °C) alongside ambient ground or air conditions.
- Governing cable standard and compliance scope: Request specific IEC, DIN VDE, EN, or UL styles and review approved documentation on our certificates and compliance page and TEBAOFLEX company overview. Before ordering, ask our engineers to confirm the datasheet R₂₀ limit, reactance, and jacket rating for your exact circuit.
ENGINEERING VOLTAGE DROP & CABLE REVIEW
Verify Your Feeder Cross-Section Against Datasheet Resistance
Share system voltage, continuous amperes, one-way length, power factor, insulation temperature rating (70 °C or 90 °C), and your target voltage-drop limit. TEBAOFLEX engineers will match exact IEC 60228 Class 2 or Class 5 power, solar PV, and 1500 V DC ESS cable constructions and confirm guaranteed R₂₀ values on your quotation.
7. Frequently Asked Questions
Why does the 3-phase voltage drop formula multiply by √3 while DC multiplies by 2?
In a two-wire DC or single-phase circuit, current passes through both outgoing and return conductors, doubling single-conductor resistance over 2 × L. In a balanced three-phase load, neutral current cancels and each line drops I × Z × L to neutral, so line-to-line drop scales by √3 (1.7321).
Should I plug 20 °C or 90 °C into the voltage drop calculation?
Always enter the loaded conductor operating temperature (such as 70 °C for PVC or 90 °C for XLPE/XLPO), never 20 °C ambient ratings. Copper resistance rises by 19.65% at 70 °C and 27.51% at 90 °C above 20 °C, so cold calculations understate voltage drop.
How do I convert an IEC 60228 20 °C datasheet resistance to 75 °C or 90 °C?
Multiply the datasheet 20 °C maximum R₂₀ by [1 + α₂₀ × (T − 20)] using α₂₀ = 0.00393 /°C for copper or 0.00403 /°C for aluminum. For 90 °C XLPE operation, multiply copper R₂₀ by 1.2751 and aluminum R₂₀ by 1.2821 before calculating feeder drop.
When can I ignore inductive reactance X in AC voltage drop calculations?
Reactance has zero effect on DC circuits (0 Hz) and at unity AC power factor (cos φ = 1.0, sin φ = 0). On small copper conductors below 35 mm², resistance dominates the total impedance. At 35 mm² and larger with motor power factors around 0.80–0.85, include X ≈ 0.08 Ω/km.
Why do two 120 mm² cables in parallel drop less voltage than one 240 mm² or 300 mm² cable?
Doubling cross-section in one large conductor cuts resistance R in half while leaving inductive reactance X near 0.08 Ω/km. Splitting into n = 2 parallel 120 mm² runs halves current per conductor and cuts reactive drop X sin φ in half simultaneously. That dual reduction lowers overall AC drop.