ITC/PLTC, APL CAM/ICAM and PAS Part 2 Type 1 & Type 2 Instrumentation Cable Guide: Collective vs Individual Screening and SWA Armor
Compare BS/PAS 5308 Part 2 Type 1 vs Type 2 SWA, 300V ITC/PLTC vs 600V TC-ER, APL-sheathed CAM/ICAM, and 9500-series multipair instrumentation cables.

- Voltage Tiers
- 300/500 V (PAS 5308 / ITC) · 600 V (TC-ER)
- UK PAS Pt 2 Types
- Type 1 PVC Indoor vs. Type 2 SWA Armored
- Screening & Water Seal
- CAM (Collective) · ICAM (Ind.+Coll.) + APL
- Signal Pair Geometries
- Multipair 9500 Series & Single-Pair Loops
Noise Rejection Levels
Collective CAM vs. Individual Pair ICAM
Use collective foil (CAM) on uniform trays and step to individually screened ICAM pairs where analog crosstalk breaks HART signals.
UK / US / Radial Moisture
PAS 5308 Type 2 SWA vs. APL & UL TC-ER
Add APL radial aluminum moisture foil in wet chemical ducts or select UL 1277 600 V TC-ER next to 480 V motor leads.
Selecting fixed instrumentation cables requires matching four parameters: circuit standard (PAS 5308, ITC/PLTC, TC-ER, or SANS 1411), screening (CAM vs ICAM), outer barrier (APL vs SWA), and pair count. Mixing 4–20 mA transmitters, HART signals, thermocouples, and discrete status loops without individual pair screens or moisture barriers causes capacitive crosstalk and damp duct drift. Aligning the TEBAOFLEX Instrumentation & Signal Cable portfolio with your marshalling architecture prevents measurement errors and gland termination failures.
How Do PAS Part 2, ITC/PLTC, TC-ER and SANS 1411 APL Standards Differ?
Global EPC contractors specify fixed signal cables under four regional standards that define voltage grade, conductor stranding, insulation dielectric, and mechanical armor differently. Mapping British BS/PAS 5308 Part 2, North American UL 2250 ITC / UL 13 PLTC / UL 1277 TC-ER, SANS 1411 APL, and European EN 50575 prevents submittal rejections.
- British Process Standard (BS/PAS 5308 Part 2). This standard serves chemical, petrochemical, and utility plants where PVC insulation and PVC outer layers are preferred over polyethylene (Part 1). Rated 300/500 V, it defines Type 1 (unarmored indoor) and Type 2 (galvanized steel wire armored SWA outdoor or direct-buried). Conductors follow EN 60228 Class 5 flexible copper (0.5 mm² and 0.75 mm²) or Class 2 stranded copper (1.5 mm² and 2.5 mm²).
- North American Tray Standards (UL 2250 ITC, UL 13 PLTC, UL 1277 TC-ER). These circuits follow NEC Articles 725, 727, and 336. 300 V ITC/PLTC Shielded Instrumentation Cable serves dedicated 300 V instrument tray circuits (ITC) and power-limited tray circuits (PLTC). By contrast, 600 V UL 1277 TC-ER Individually Screened Instrumentation Cable uses 600 V PVC/nylon insulation for shared 600 V power trays and exposed drops.
- Laminate-Protected Process Standard (SANS 1411 APL CAM / ICAM). This construction pairs 300/500 V XLPE core insulation (SANS 1411 Part 4) with CAM or ICAM aluminum/polyester screens and a PVC bedding (SANS 1411 Part 2 Type B1). Over the bedding sits a bonded aluminum-polyethylene laminate (APL) moisture barrier and a black PE outer layer (SANS 1411 Part 7).
- Compact Equipment Interconnects (EN 50575 PE/LSZH & HDPE/LSZH). This group includes the 9500 Series overall-foil multipair, single-pair foil-screened, and unscreened two-core tinned-copper series. These compact 300 V and 600 V cables use low-capacitance PE or HDPE insulation with LSZH or PVC-LSF outer layers for indoor panels.
For a broader overview of North American PLTC vs Nordic NOMAK/JAMAK constructions, see our companion TC-ER Tray Control, PLTC and Instrumentation Cable Guide.
How Do All Eight TEBAOFLEX Fixed Instrumentation Cable Series Compare?
TEBAOFLEX manufactures eight fixed instrumentation and audio/signal cable series covering every screening topology (unscreened, single-pair foil, CAM, and ICAM) and outer barrier (unarmored, APL, TC-ER, and SWA).
Table 1. Engineering Matrix: Eight TEBAOFLEX Instrumentation & Signal Cable Constructions
| Cable Series & Product Link | Voltage & Design Reference | Conductor & Core Insulation | Screening & Drain Architecture | Barrier & Outer Layer | Primary Field Application |
|---|---|---|---|---|---|
| 300 V ITC/PLTC Shielded Instrumentation Cable | 300 V (UL 13 PLTC, UL 2250 ITC, UL 1685, IEC 60332-3-22 Cat A) | Plain annealed Cu (7-strand ref); PVC pairs (black/white) or triads (+red) | Collective Al/PET foil + drain, or individual group + collective Al/PET foils + drains | Black PVC outer layer with orange auxiliary wire on selected builds | Dedicated 300 V DCS/PLC marshalling trays and field junction boxes |
| 600 V UL 1277 TC-ER Individually Screened Cable | 600 V (UL 1277 Type TC-ER, NEC Art. 336, UL 1685) | Plain annealed Cu in black/white numbered pairs; PVC/nylon insulation | Each pair has PET tape + Al/PET foil + tinned Cu drain, plus general solid tinned Cu drain | Heavy-duty black PVC tray outer layer (TC-ER) | Multi-pair analog instrumentation sharing 600 V cable trays with exposed drops |
| APL-Sheathed CAM / ICAM Instrumentation Cable | 300/500 V (SANS 1411 Part 4, Part 2 Type B1, Part 7) | Stranded annealed bunched Cu; XLPE core insulation (white/black pairs, +red triads) | CAM (collective Al/PET + drain) or ICAM (individual + collective Al/PET + drains) | PVC bedding + APL Al-PE laminate + separate bunched drain + black PE outer layer | Underground ducts, chemical process plants, and high-humidity outdoor instrument runs |
| BS/PAS 5308 Part 2 Type 1 PVC Instrumentation | 300/500 V (BS/PAS 5308 Part 2, EN 60228, IEC 60332-3-24) | Annealed Cu (Class 5 at 0.5/0.75 mm²; Class 2 at 1.5/2.5 mm²); PVC | CAM (collective Al/PET tape + tinned Cu drain) or ICAM (group + collective foils + drains) | Unarmored black or blue (intrinsically safe) PVC outer layer | Fixed indoor process trays, analyzer houses, and protected control rooms |
| BS/PAS 5308 Part 2 Type 2 PVC SWA Cable | 300/500 V (BS/PAS 5308 Part 2, EN 60228, IEC 60332-3-24) | Annealed Cu (Class 5 at 0.5/0.75 mm²; Class 2 at 1.5/2.5 mm²); PVC | CAM or ICAM Al/PET foil screens with tinned copper drain wires | PVC bedding + galvanized steel wire armor (SWA) + black or blue PVC outer layer | Direct-buried trenches, outdoor pipe racks, and crush-exposed process zones |
| 9500-Series Overall-Foil Multipair Cable | 300 V (EN 50575 CPR documented builds) | Class 2 stranded tinned Cu; PE or PVC paired cores (2 to 25+ pairs) | Overall aluminum foil screen (100% coverage) + stranded tinned copper drain wire | Grey LSZH or PVC-LSF outer layer | Multi-channel RS-232/RS-422 serial links, panel racks, and building automation |
| Single-Pair Foil-Screened Instrumentation | 300 V / 600 V (EN 50575 CPR documented builds) | Stranded tinned Cu (16-strand 18 AWG ref); black/transparent HDPE or PE | Single-pair aluminum foil screen + stranded tinned copper drain wire | Compact grey LSZH or PVC-LSF outer layer | Individual 4–20 mA field transmitters, audio lines, and point-to-point sensors |
| Unscreened Two-Core Audio / Instrumentation | 300 V / 600 V (EN 50575 CPR documented builds) | Stranded tinned Cu (19-strand 16 AWG ref); black/white HDPE or PVC | Unscreened twisted two-core construction | Grey LSZH (300 V ref), violet LSZH (600 V ref), or PVC-LSF | Dry-contact status relays, local audio speakers, and low-noise 24 V DC links |
Sources: BS 5308 / PAS 5308 Part 1 & Part 2, UL 2250 (ITC), UL 13 (PLTC), UL 1277, SANS 1411 / 1507 (CAM/ICAM), and EN 50288-7.

When Should Engineers Specify CAM (Collective) vs ICAM (Individual & Collective) Screening?
In PAS 5308, SANS 1411, and ITC/PLTC instrumentation cables, CAM (collective foil) and ICAM (individual plus collective foils) determine whether adjacent pairs are isolated from one another.
1. CAM (Collective Screen Only)
- Construction. All twisted pairs or triads are cabled together into one assembly and wrapped in polyester tape. One overall aluminum/polyester (Al/PET) foil tape and a tinned-copper drain wire enclose the entire bundle.
- When to Specify CAM. Specify CAM builds of BS/PAS 5308 Part 2 Type 1 or BS/PAS 5308 Part 2 Type 2 SWA for single-pair spurs or homogeneous trunks. You can also select APL-Sheathed CAM Cable or 9500-Series Multipair Cable for identical 24 V DC switch or steady 4–20 mA loops.
- Engineering Advantage. CAM reduces outer cable diameter by 10%–18% and lowers cable weight. It also halves marshalling termination time because technicians land only one drain wire per cable.
2. ICAM (Individual Pair Screen + Collective Overall Screen)
- Construction. Every individual twisted pair or triad has its own numbered insulation, polyester separator, 100% Al/PET foil screen, and dedicated tinned-copper drain wire. An additional overall Al/PET collective screen and master drain wire then enclose the cabled groups.
- When to Specify ICAM. Upgrade to ICAM builds in 300 V ITC/PLTC Shielded Cable or 600 V TC-ER Individually Screened Cable whenever a trunk carries mixed signals. The same rule applies to APL-Sheathed ICAM Cable and PAS 5308 Type 1/Type 2 ICAM in these cases:
- 4–20 mA analog loops carrying superimposed 1.2 kHz / 2.2 kHz HART FSK digital communication;
- Low-millivolt thermocouple extensions or 3-wire Pt100 RTD bridges sharing a trunk with 24 V DC solenoid switching pulses;
- High-frequency turbine flowmeter or vortex pulse outputs (0–10 kHz) that would capacitively couple into adjacent analog inputs.
- Nordic NOMAK / JAMAK Cross-Reference. In Nordic process standards, CAM corresponds to NOMAK Overall-Screened PE Instrumentation Cable (OS). ICAM corresponds to JAMAK Individually and Overall Screened Instrumentation Cable (IS/OS).
How Do PAS Part 2 Type 1 Unarmored, Type 2 SWA and APL Laminate Barriers Compare?
Selecting the outer barrier depends on whether the primary route hazard is mechanical crushing (SWA), radial moisture vapor permeation (APL), or indoor fire spread (Type 1 PVC / LSZH).
Table 2. Barrier Comparison: BS/PAS 5308 Type 1 vs Type 2 SWA vs SANS 1411 APL Laminate
| Engineering Criterion | BS/PAS 5308 Part 2 Type 1 (E006) | BS/PAS 5308 Part 2 Type 2 SWA (E007) | SANS 1411 APL CAM / ICAM (E004) |
|---|---|---|---|
| Core Insulation Material | PVC (300/500 V) | PVC (300/500 V) | Cross-linked polyethylene (XLPE, 300/500 V) |
| Conductor Stranding Rule | Class 5 (0.5, 0.75 mm²); Class 2 (1.5, 2.5 mm²) | Class 5 (0.5, 0.75 mm²); Class 2 (1.5, 2.5 mm²) | Stranded annealed bunched copper (0.5–1.5 mm²) |
| Metallic Barrier Layer | None (unarmored CAM or ICAM foil only) | Galvanized steel wire armor (SWA) over PVC bedding | Bonded aluminum-polyethylene laminate (APL) over PVC bedding |
| Radial Water Vapor Blocking | Standard polymeric PVC outer layer | Moderate (PVC bedding + PVC outer layer) | Hermetic metallic vapor barrier (APL + PE outer layer) |
| Crush & Tensile Resistance | Low-to-moderate (requires tray or conduit support) | High (direct burial, concrete trenches, exposed racks) | Moderate (suited for underground ducts and covered trays) |
| Intrinsically Safe (Ex i) Option | Black or Blue outer layer for Ex i Zone 1/2 circuits | Black or Blue outer layer for Ex i Zone 1/2 circuits | Black PE outer layer (specify Ex i marking on schedule) |
Sources: PAS 5308-2 Type 1 & Type 2 SWA construction tables and aluminum-polyethylene laminate (APL) radial vapor-barrier rules.
Why XLPE + APL Outperforms Unarmored PVC in Wet Underground Ducts
Standard PVC and PE polymer layers allow slow molecular water vapor diffusion during multi-year immersion in waterlogged trenches. In APL-Sheathed CAM / ICAM Instrumentation Cable, a copolymer-coated aluminum tape (APL) is formed over the PVC bedding and bonded to the black PE outer layer. Simultaneously, XLPE core insulation maintains high insulation resistance and low dielectric loss at 90 °C operating temperatures. The APL layer includes its own separate bunched tinned-copper drain wire distinct from the internal CAM/ICAM signal drains. Engineers can therefore bond the outer moisture barrier to earth at the cabinet entry without injecting ground-loop currents into the signal busbar.

When Should Projects Select 300 V ITC/PLTC vs 600 V Individually Screened TC-ER?
In North American plants governed by NEC and UL, choosing 300 V ITC/PLTC vs 600 V TC-ER determines whether instrument cables can share 480 V trays or drop unsupported.
- Choose 300 V ITC/PLTC Shielded Instrumentation Cable (E002, UL 2250 / UL 13) when:
- All circuits run in dedicated instrument cable trays (NEC Article 725 Class 2/3 PLTC or NEC Article 727 ITC) separated from 480 V AC motor feeders;
- You need compact 300 V PVC core walls in 1 to 36 pairs or triads, with collective (OS) or individual-plus-collective (IS/OS) screening;
- Your specification requires UL 1685 vertical tray flame compliance, IEC 60332-3-22 Category A flame testing, and an orange auxiliary wire on two-pair builds.
- Choose 600 V UL 1277 TC-ER Individually Screened Instrumentation Cable (E003, UL 1277 / NEC Article 336) when:
- Instrument pairs must run inside shared 600 V ladder trays alongside 480 V power or 120 V AC control cables without a tray barrier;
- The cable exits the tray for an Exposed Run (TC-ER) drop of up to 1.8 m (6 ft) between supports without rigid metal conduit;
- Each pair requires numbered black/white PVC/nylon cores, polyester tape, and an individual Al/PET foil screen with drain wire plus a general drain.
How Do 9500-Series Multipair, Single-Pair Screened and Unscreened Two-Core Cables Fit Equipment Wiring?
While heavy BS 5308, APL, and TC-ER trunks serve outdoor pipe racks, indoor analyzer cabinets and BMS panels require compact tinned-copper cables with EN 50575 CPR and LSZH options.
- Overall-Foil-Screened Multipair Instrumentation Cable — 9500 Series (E008). Uses Class 2 stranded tinned-copper conductors with low-capacitance PE paired cores, 100% overall aluminum foil, a tinned-copper drain, and a grey LSZH or PVC-LSF outer layer. It suits multi-channel RS-232, RS-422, inter-rack PLC/DCS harnesses, and load-cell trunks.
- Single-Pair Foil-Screened Instrumentation Cable (E009). Features a 1-pair stranded tinned-copper build (16-strand 18 AWG on 300 V HDPE/LSZH references, plus 600 V options) inside an aluminum foil screen and grey LSZH outer layer. It serves individual 4–20 mA field transmitters, analog 0–10 V actuators, and shielded audio feeds.
- Unscreened Two-Core Audio / Instrumentation Cable (E010). Uses two twisted tinned-copper conductors (19-strand 16 AWG on HDPE/LSZH references) without a foil screen inside a grey LSZH (300 V) or violet LSZH (600 V) outer layer. Twisting the black and white cores cancels magnetic pickup on dry-contact status inputs, 24 V DC relays, and speaker circuits.

How Should Engineers Terminate CAM, ICAM, APL and SWA Ground Paths at Marshalling Cabinets?
Improper termination of drain wires, APL moisture barriers, and SWA steel armor causes 50/60 Hz common-mode hum and ground-loop drift in 4–20 mA and thermocouple circuits. Follow these four separation rules during panel assembly and field gland installation:
- Single-Point Instrument Earth (IE) for CAM and ICAM Signal Screens. Connect the CAM collective drain wire and all ICAM individual pair drain wires to the isolated Instrument Earth (IE) busbar at the marshalling cabinet end only. At the field transmitter or junction box, trim and heat-shrink insulate each signal foil and drain wire to block circulating earth currents.
- Maintain Pair Twist and Sleeve Individual ICAM Drains. Inside the marshalling cabinet, keep each pair or triad twisted to within 25 mm (1 in.) of the terminal block. Slide insulating PVC or silicone tubing over every bare ICAM drain wire so adjacent pair screens never touch inside the trunking.
- Separate APL Laminate Drain from Clean Instrument Earth. On APL-Sheathed CAM / ICAM Instrumentation Cable, bond the outer APL laminate drain wire to the Protective/Chassis Earth (PE) at the cabinet entry plate. Never connect the outer APL moisture barrier drain to the clean 4–20 mA signal reference bar.
- 360° Compression Gland Bonding for BS 5308 Part 2 Type 2 SWA. Terminate the SWA steel armor of BS/PAS 5308 Part 2 Type 2 PVC SWA Cable inside a brass CW or E1W compression gland bonded to PE. Pass the inner CAM/ICAM bedding and signal screens insulated through the gland body to the IE bar.
Frequently Asked Questions
What is the difference between Type 1 and Type 2 in British instrumentation cables?
In BS/PAS 5308 Part 2 PVC instrumentation cables, Type 1 is an unarmored build for fixed indoor cable trays, raceways, and protected analyzer rooms. Type 2 adds an extruded PVC bedding and galvanized steel wire armor (SWA) beneath the outer PVC layer. That SWA layer provides crush and rodent protection for direct burial, outdoor concrete trenches, and exposed process pipe racks.
When should I choose ICAM instead of CAM screening?
Choose CAM (Collective Aluminum Mylar screen) for single-pair runs or multipair trunks carrying identical signal types such as 24 V DC discrete status inputs. Specify ICAM (Individual and Collective Aluminum Mylar screens) whenever a multipair cable combines 4–20 mA HART loops, millivolt thermocouples, 3-wire RTDs, or pulse counters. Each pair’s individual foil screen blocks pair-to-pair capacitive crosstalk.
Why do PAS Part 2 cables switch from Class 5 to Class 2 conductors at 1.5 mm²?
Under PAS 5308 Part 2 and EN 60228 schedules, smaller 0.5 mm² and 0.75 mm² conductors use Class 5 flexible copper (16 or 24 fine strands). Fine stranding keeps small instrument cores flexible and prevents breakage at high-density terminal blocks. At 1.5 mm² and 2.5 mm², the standard switches to 7-strand Class 2 copper for higher column stiffness and long-distance low-resistance loops.
What does the APL barrier do in SANS 1411 CAM and ICAM cables?
APL stands for Aluminum-Polyethylene Laminate. Applied over the PVC bedding and bonded to the black PE outer layer, the APL foil forms a 100% radial barrier against water vapor and hydrocarbons. A separate tinned-copper drain wire under the APL tape allows independent earthing of the outer moisture barrier.
Can 300 V ITC/PLTC instrumentation cables run in the same tray as 480 V power feeders?
Under NEC Articles 725 and 727, 300 V PLTC and ITC cables cannot share an undivided tray section with 480 V or 600 V power conductors without a solid barrier. When instrument pairs share a 600 V tray without a barrier or make exposed drops, specify TEBAOFLEX 600 V TC-ER Individually Screened Instrumentation Cable.
When should Blue outer layers be specified on process instrumentation cables?
A sky-blue outer layer on PAS 5308 Part 2 Type 1 or Type 2 SWA cables identifies Intrinsically Safe (Ex i) circuits in Zone 0, 1, or 2 hazardous areas. Standard non-IS safe-area or explosionproof (Ex d) instrumentation circuits use a black outer layer so technicians never mix Ex i and non-IS wiring.
Before releasing marshalling-cabinet cable schedules across our instrumentation and signal cable range, verify 4–20 mA and RTD pair loop resistance in our Wire Resistance Calculator, cross-check AWG vs mm² pair sizes in the AWG to mm² Converter, and plan single-run wooden drum lengths with the Cable Drum Length Calculator.
Engineering RFQ & Datasheet Review
Confirm PAS 5308 Part 1/2, ITC/PLTC, or APL CAM/ICAM Pair & Screen Schedule
Provide your governing standard, pair/triad count × mm² (0.5–2.5 mm² or 22–16 AWG), collective (CAM/OS) vs individual-and-overall (ICAM/IS+OS) screen, and SWA/APL barrier.