600/1000 V Foil-and-Braid Shielded VFD Motor Cable

Fixed VFD-to-motor connections on pumps, fans, conveyors and industrial machinery, with suitable indoor, outdoor, sunlight-exposed or buried routing for the selected marking. TC-ER / WTTC / flexible motor supply: 1000 V for the selected construction. Canadian CIC / TC: 600 V classification. Dry / wet rating: 90°C / 90°C Operating temperature: −40 to +90°C Nominal outside diameter: 17.5 mm

  • TC-ER / WTTC / flexible motor supply1000 V for the selected construction.
  • Canadian CIC / TC600 V classification.
  • Dry / wet rating90°C / 90°C
  • Operating temperature−40 to +90°C
  • Nominal outside diameter17.5 mm
  • Minimum stationary / installation bend radius210 mm / 210 mm
  • Phase-conductor resistance3.18 Ω/km
  • Nominal capacitance75 pF/m conductor-to-conductor; 140 pF/m conductor-to-other.

600/1000 V Foil-and-Braid Shielded VFD Drive & Motor Cable Identification

  • Type: Industrial Cables
  • TC-ER / WTTC / flexible motor supply: 1000 V for the selected construction.
  • Canadian CIC / TC: 600 V classification.
  • Dry / wet rating: 90°C / 90°C

PWM Inverter Voltage, Thermal & Bend Ratings

  • Operating temperature: −40 to +90°C
  • Nominal outside diameter: 17.5 mm
  • Minimum stationary / installation bend radius: 210 mm / 210 mm
  • Phase-conductor resistance: 3.18 Ω/km
  • Nominal capacitance: 75 pF/m conductor-to-conductor; 140 pF/m conductor-to-other.

600/1000 V Foil-and-Braid Shielded VFD Low-Capacitance & Dual-Screen Build

  • Phase conductors: 3 × 10 AWG, 105 × 30 tinned copper; black XLPE insulation.
  • Insulated ground: 1 × 10 AWG tinned copper; green/yellow PVC insulation.
  • Bare ground/drain: Separate 10 AWG tinned-copper stranded element.
  • Overall screen: 100% aluminum/polyester/aluminum foil plus 85% tinned-copper braid.
  • Outer jacket: Black PVC with ripcord; nominal wall 1.9 mm.

Select the complete construction

The four insulated cores and the bare ground/drain form one screened cable assembly. The screen is not mechanical armor. A screened cable and an armored MC cable need different fittings and installation checks.

Define the ordered acceptance conditions

Include the exact construction, applicable designations, dimensions and required inspections in the purchase specification. For motion, define the carrier or route geometry, temperature, speed, acceleration and cycle definition. For optical or RF links, include wavelengths or frequencies, interfaces, connections and the installed link acceptance criteria.

EMC Transfer Impedance & Bearing Current Control

  • Select the complete construction: The four insulated cores and the bare ground/drain form one screened cable assembly.
  • Define the ordered acceptance conditions: Include the exact construction, applicable designations, dimensions and required inspections in the purchase specification.
  • Route and equipment selection: Provide the drive and motor details, required cable length, tray or duct arrangement, nearby signal circuits and bonding design.
  • Order the grounding topology, not just the cable name: A full-size insulated protective conductor and a separate full-size bare ground/drain do not mean three additional insulated earth cores.

Industrial Oil, Vibration & Plant Routing Durability

  • Installation & Routing: Fixed VFD-to-motor connections on pumps, fans, conveyors and industrial machinery, with suitable indoor, outdoor, sunlight-exposed or buried routing for the selected marking.
  • Termination & Entry Check: Use each value for the stated construction and operating condition. Nominal dimensions refer to the representative configuration; select the full size and installation schedule before ordering.
  • UL 1277, TC-ER: Tray-cable / exposed-run construction for the selected rating.
  • UL 2277: WTTC and flexible motor-supply classifications, with their own voltage ratings.

IEC / VDE / UL Variable-Frequency Drive Standards

  • UL 1277, TC-ER: Tray-cable / exposed-run construction for the selected rating.
  • UL 2277: WTTC and flexible motor-supply classifications, with their own voltage ratings.
  • UL 1685 / IEEE 1202: Vertical-tray flame-test references.
  • RoHS: Restricted-substance directive reference.

VFD, Servo & EMC Earthing Guides

Supported black VFD motor cable on a straight steel tray between a closed drive cabinet and an industrial motor-pump skid
Supported cable routing between closed drive equipment and an industrial motor. Coordinate bends, supports and terminations with the selected cable.

600/1000 V Foil-and-Braid Shielded VFD Inverter-Fed Motor & Drive Integration

Foil-and-braid shielded VFD motor cable at 600/1000 V connects variable-frequency drives to AC motors using three tinned-copper phase conductors, XLPE phase insulation, a full-size insulated ground and a separate bare ground/drain. An overall aluminum/polyester/aluminum foil, tinned-copper braid and black PVC jacket complete the selected construction.

The protective conductor, bare ground/drain and overall screen are distinct parts of the assembly. Choose them together with the equipment bonding and termination design. A cable described by its grounding system should still be ordered by its actual conductor count, sizes and materials rather than by a percentage name alone.

Typical Variable-Speed Drive Installations

  • Fixed VFD-to-motor connections on pumps, fans, conveyors and industrial machinery, with suitable indoor, outdoor, sunlight-exposed or buried routing for the selected marking.

Route and equipment selection

Provide the drive and motor details, required cable length, tray or duct arrangement, nearby signal circuits and bonding design. Route selection must account for electrical noise as well as mechanical support and environmental exposure.

Compare related cable duties

  • 600 V MC Armored VFD Cable with Aluminum Interlock Armor
  • LSZH-Jacket Shielded VFD Motor Cable
  • Continuous-Flex TPE VFD Motor Cable

600/1000 V Foil-and-Braid Shielded VFD VFD Screening & Termination FAQ

How does 600/1000 V Foil-and-Braid Shielded VFD Motor Cable handle select the complete construction in field installations?

The four insulated cores and the bare ground/drain form one screened cable assembly. The screen is not mechanical armor. A screened cable and an armored MC cable need different fittings and installation checks.

Why is 'Define the ordered acceptance conditions' critical when specifying 600/1000 V Foil-and-Braid Shielded VFD Motor Cable?

Include the exact construction, applicable designations, dimensions and required inspections in the purchase specification. For motion, define the carrier or route geometry, temperature, speed, acceleration and cycle definition. For optical or RF links, include wavelengths or frequencies, interfaces, connections and the installed link acceptance criteria.

How should engineers address 'route and equipment selection' for 600/1000 V Foil-and-Braid Shielded VFD Motor Cable?

Provide the drive and motor details, required cable length, tray or duct arrangement, nearby signal circuits and bonding design. Route selection must account for electrical noise as well as mechanical support and environmental exposure.

What layer-by-layer materials and screening options define 600/1000 V Foil-and-Braid Shielded VFD Motor Cable?

Phase conductors: 3 × 10 AWG, 105 × 30 tinned copper; black XLPE insulation.; Insulated ground: 1 × 10 AWG tinned copper; green/yellow PVC insulation.; Bare ground/drain: Separate 10 AWG tinned-copper stranded element.; Overall screen: 100% aluminum/polyester/aluminum foil plus 85% tinned-copper braid.; Outer jacket: Black PVC with ripcord; nominal wall 1.9 mm.

Use each value for the stated construction and operating condition. Nominal dimensions refer to the representative configuration; select the full size and installation schedule before ordering.

TEBAOFLEX® — 600/1000 V Foil-and-Braid Shielded VFD Motor Cable Construction, Operating & Compliance Matrix

600/1000 V Foil-and-Braid Shielded VFD Motor Cable 4-Column Engineering Schedule
Cable Element / Layer Selected Construction Operating Parameter / Condition Normative Reference & Test Scope
Phase conductors 3 × 10 AWG, 105 × 30 tinned copper; black XLPE insulation. TC-ER / WTTC / flexible motor supply: 1000 V for the selected construction. UL 1277, TC-ER — Tray-cable / exposed-run construction for the selected rating.
Insulated ground 1 × 10 AWG tinned copper; green/yellow PVC insulation. Canadian CIC / TC: 600 V classification. UL 2277 — WTTC and flexible motor-supply classifications, with their own voltage ratings.
Bare ground/drain Separate 10 AWG tinned-copper stranded element. Dry / wet rating: 90°C / 90°C UL 1685 / IEEE 1202 — Vertical-tray flame-test references.
Overall screen 100% aluminum/polyester/aluminum foil plus 85% tinned-copper braid. Operating temperature: −40 to +90°C RoHS — Restricted-substance directive reference.
Outer jacket Black PVC with ripcord; nominal wall 1.9 mm. Nominal outside diameter: 17.5 mm UL 1277, TC-ER — Tray-cable / exposed-run construction for the selected rating.

TEBAOFLEX® — 600/1000 V Foil-and-Braid Shielded VFD Motor Cable technical parameters

600/1000 V Foil-and-Braid Shielded VFD Motor Cable technical parameters
Parameter Value / condition
TC-ER / WTTC / flexible motor supply 1000 V for the selected construction.
Canadian CIC / TC 600 V classification.
Dry / wet rating 90°C / 90°C
Operating temperature −40 to +90°C
Nominal outside diameter 17.5 mm
Minimum stationary / installation bend radius 210 mm / 210 mm
Phase-conductor resistance 3.18 Ω/km
Nominal capacitance 75 pF/m conductor-to-conductor; 140 pF/m conductor-to-other.
Nominal weight 525 kg/km

TEBAOFLEX® — 600/1000 V Foil-and-Braid Shielded VFD Motor Cable configuration comparison

600/1000 V Foil-and-Braid Shielded VFD Motor Cable configuration comparison
Configuration Selection scope
PVC foil/braid This fixed-route construction.
Aluminum-interlock MC Additional mechanical protection and MC-specific fittings.
Continuous-flex TPE A separate fine-stranded construction with a defined moving bend.

TEBAOFLEX® — VFD jacket and route selection

VFD jacket and route selection
Jacket / construction Route distinction
PVC foil/braid Fixed-route representative.
LSZH outer jacket Separate low-smoke jacket build; identify PE insulation too.
Continuous-flex TPE Fine-stranded moving construction with its own radius.
WTTC TPE Select the exact wind-turbine installation marking and duty.

Order the grounding topology, not just the cable name

A full-size insulated protective conductor and a separate full-size bare ground/drain do not mean three additional insulated earth cores. Keep the conductor schedule and screen-termination drawing together. Specify phase size, ground size, drain size and screen construction independently so that receiving inspection can identify the intended assembly.

Selection guide: Send the circuit schedule, route drawing, connection details and required quantity with your inquiry. Our engineers can coordinate the selected cable construction, finished dimensions, installation conditions and delivery lengths with your equipment specification. Include required reel lengths, installation markings and inspection documents so the delivery schedule matches the project.

Ordering & Quotation Checklist: Send phase/ground sizes, drive and motor ratings, route length, installation classification, environmental exposure and termination details.

Direct Factory Engineering RFQ

Request Quotation & Datasheet for This Cable

Need factory pricing, cross-section drawing or a full PDF datasheet for 600/1000 V Foil-and-Braid Shielded VFD Motor Cable? Share your core count, conductor size, length and destination country—our Taicang cable engineers reply within 24 hours.