LiYY vs LiYCY: Choosing Screened or Unscreened Signal Cable
LiYY is unscreened; LiYCY adds an overall copper-braid screen. Use equipment, routing and termination requirements to choose a candidate and prepare a complete inquiry.

- Nomenclature Code
- Li = Fine Cu · Y = PVC · Y = Sheath / C = Braid
- Core Area & Voltage
- 0.14–1.5 mm² Signal | 250 V – 350 V Control
- LiYY vs. LiYCY Split
- Unscreened vs. Tinned-Copper Braid EMC
- RS-485 Data Limit
- Check 120 Ω Impedance & Cap. (60 pF/m)
Noise Environment
Unscreened LiYY vs. Braided EMC LiYCY
Use LiYY inside isolated low-voltage PLC cabinets; add LiYCY tinned-copper braid when routing near motors, relays, or PWM contactors.
Not Automatic RS-485
Verify Impedance & Pair Cap. Before Bus Use
Standard PVC LiYCY (~120 pF/m) lacks true 120 Ω twisted-pair geometry—specify low-cap PE Li2YCY or dedicated RS-485 on long trunks.
LiYY is unscreened; LiYCY has an overall tinned-copper braid screen. In the TEBAOFLEX constructions compared here, both use PVC core insulation and a PVC outer sheath. Choose between them by checking the connected equipment’s cable requirements, the route and the screen connection—not by assuming that screened cable is always the better option.
A LiYY vs LiYCY comparison should lead to a shortlist and a complete specification. For individual core color identification up to 44 cores and twisted-pair grouping, reference our DIN 47100 color code chart. The model name alone does not establish the required pair arrangement, electrical ratings or suitability for a particular communication interface.
What changes between LiYY and LiYCY?
The main construction difference is the screen around the assembled cores. The TEBAOFLEX LiYY construction compared here has no metallic screen. Its LiYCY counterpart adds a tinned-copper braid around the complete core bundle, beneath the outer sheath. That is an overall screen, not a separate screen around each signal pair.
Both constructions have cores stranded in layers. Do not read “screened multicore” as “twisted pair.” A request for paired conductors, individually screened pairs or a specified characteristic impedance needs its own confirmation against the offered construction.
Both models sit within the PVC control and data cable range. If the distinction between core insulation and the outer sheath is still unclear, use the PVC control cable datasheet guide before comparing the screen field. Where an unscreened circuit instead requires numbered power-and-control cores rather than signal cores, review our YY flexible PVC control cable.
When should you consider LiYY or LiYCY?
Consider LiYY when the equipment specification permits an unscreened connection and the reviewed installation conditions fit the offered cable. Consider LiYCY when an overall braid screen is required and the cable’s other construction details also match. If the requirements are incomplete, clarify them before treating either model as an approved choice.
| Choose this route when… | Candidate to review | Confirm before selection |
|---|---|---|
| The equipment permits unscreened wiring, and the system designer has reviewed the proposed route. | LiYY unscreened signal cable | Core arrangement, circuit requirements, dimensions and installation duty. |
| The equipment or project specification calls for an overall copper-braid screen. | LiYCY screened signal cable | Screen construction, connection hardware and the rest of the selected variant’s datasheet. |
| The interface specifies twisted pairs, individual pair screens or particular transmission parameters. | A construction documented to meet that interface. | The actual pair layout and electrical data. Neither family name alone proves a match. |
| The screen requirement or cable route is unknown. | Keep the choice open. | Obtain the equipment manual and route information; “screened” is not a substitute for missing requirements. |
Sources: DIN VDE 0812, IEC 60228 Class 5 fine-wire stranding, and EN 50288-7 industrial EMC routing principles.
These product links are family-level starting points. Compare the specific construction offered in the quotation; do not assume that matching core count and conductor area make two cables interchangeable.
Which equipment and routing details affect the choice?
The equipment manual can specify more than the presence of a screen. Check the exact controller, input module and field device—not simply a label such as “PLC cable” or “sensor cable.” Record which document requires screening, whether conductors must be paired and how the cable enters each enclosure; for how internal IDC ribbon and flat flex cables transition at DIN-rail modules to external round cables, see our ribbon cable and flat flex cable vs round control cable guide.
For example, Schneider Electric’s TeSys island Wiring Guidelines, document DOCA0270EN-04, requires screened cabling for its analog I/O module. It also recommends twisted-pair inner conductors and describes a circumferential screen connection. Those instructions apply to that equipment, illustrating why a general LiYY/LiYCY comparison cannot replace the connected device’s wiring instructions.
Then follow the proposed route from one device to the other. Mark nearby drives, motor power cables and switching equipment, including where the signal cable would share a duct or run alongside another circuit. Give that information to the system designer so the routing and separation can be assessed. A screen does not remove the need to follow the equipment’s routing requirements.
Before ordering LiYCY, establish where and how its screen will connect. The selected gland, clamp or connector must accommodate the proposed cable and the specified screen connection. The equipment instructions and project bonding design determine that arrangement; this comparison does not prescribe a universal one-end or both-end grounding method.
Does LiYCY automatically qualify as RS-485 cable?
No. An overall copper braid does not establish twisted-pair construction or characteristic impedance. Screening, conductor pairing and transmission-line properties are separate checks. The same applies to a LiYCY variant labelled “TP”: the pair arrangement still needs to be matched with the interface’s electrical requirements.
Texas Instruments’ The RS-485 Design Guide, SLLA272D, explains the role of twisted pairs and the relationship between cable characteristic impedance and line termination. These are properties to verify in the system design; the presence of a braid cannot supply the missing cable data.
For an RS-485 connection, record the equipment’s cable specification, pair count, required impedance, route length and data rate before comparing quotations. A short route or a low data rate alone is insufficient evidence to approve an unspecified LiYCY construction.
How would you compare cables for an analog input?
Hypothetical purchasing example: a machine builder needs an analog signal cable between a field instrument and a cabinet input module. The initial inquiry says only “flexible signal cable”; the route drawing shows a section alongside motor power wiring.
Neither detail settles the selection. The buyer first asks the equipment engineer for the module’s wiring instructions and asks the system designer to review the shared route. In this example, the engineer confirms a requirement for an overall screen, while the route and screen connection are revised in the installation drawing.
LiYCY can now enter the shortlist, subject to confirmation of the required core arrangement, electrical data, diameter and duty. The cable supplier checks the offered construction against the inquiry; the equipment and system designers confirm the connection and routing. The decision is traceable to a documented requirement, rather than to “there is a motor nearby.”
If the manual instead permits an unscreened connection and the route review supports it, LiYY remains a candidate. If the manual requires individually screened pairs, the overall-screen construction described here does not meet that requirement on its own.
What should you send for a useful cable comparison?
Send the interface requirement together with the route and termination details. This lets the cable supplier compare a defined construction with a defined task, while the equipment designer retains responsibility for the system requirements.
| Information | What to provide | Who confirms it |
|---|---|---|
| Equipment and interface | Device and module models, signal type, wiring-manual reference and any stated screen requirement. | Equipment supplier or system designer. |
| Core and screen arrangement | Core count and area; any required pairs, overall screen or individual pair screens. | Equipment designer defines the requirement; cable supplier confirms the offered build. |
| Electrical data | Required circuit ratings and, where specified, impedance, capacitance, length and data rate. | Equipment/system designer defines the requirement; cable supplier confirms the offered variant’s data. |
| Routing | Route drawing, nearby power or drive circuits, parallel sections and available separation. | System or installation designer. |
| Screen connection | Equipment connection detail and the selected clamp, gland or connector, including its accepted cable dimensions. | Equipment/assembly designer, with cable dimensions confirmed by the supplier. |
| Installation duty | Fixed or moving service, movement description, environmental exposure and project document requirements. | System designer and cable supplier against the proposed variant. |
Sources: DIN VDE 0812, IEC 61000-5-2 earthing and cabling guidelines, and TEBAOFLEX LiYY / LiYCY specification sheets.
Compare the quotations against the same requirements sheet. Check any proposed change in cable diameter, connection hardware or construction before accepting a substitution. Ask for the exact model and revision of the supporting datasheet, rather than approving a family name alone. For how single-ended audio and AV leads compare with balanced differential pairs and DIN 47100 screened multicore cables, see our audio and low-level signal cable guide.
When an application requires halogen-free sheathing, low-capacitance polyethylene insulation, or paired instrumentation screens, compare LiHCH and LiHH halogen-free data and control cable, Li2YCY, Li2YCYv, and Li2YCY-P (PiMF) low-capacitance PE data cable, J-Y(St)Y and J-H(St)H screened bus and fire-alarm installation cable, JE-Y(St)Y, JE-LiYCY, and JE-H(St)H industrial instrumentation cable, EN 50288-7 RE-2Y(St)Y, RE-2X(St)Y, and RE-2X(St)H PiMF instrumentation cable, UL 20276 twisted-pair cable & UL 3266 / UL 3271 XLPE wire, and UL 3287 105 °C 600 V XLPE wire.