EV Charging Power + Cat6A Data SWA LSZH Cable 0.6/1kV, 3 or 5 × 6mm²
Armoured EV charging cable that combines 0.6/1kV power cores with a screened Cat6A data element for charger power and flow monitoring: 3 or 5 × 6mm² copper, galvanised steel wire armour, LSZH inner and UV-resistant LSZH outer sheaths.
- VoltagePower 0.6/1kV; data 0.6/1kV
- Power cores3 or 5 × 6 mm²
- Data elementScreened Cat6A, AWG23
- ArmourGalvanised steel wire (SWA)
- SheathsLSZH inner, UV-resistant LSZH
- Overall diameter21.7 mm / 25.8 mm
- Fixed installation temp.-30°C to +80°C
- Min. bending radius14 × outer diameter
EV Cat6A SWA LSZH Signal & Bus Architecture
- Type: EV charging cable
- Voltage: Power 0.6/1kV; data 0.6/1kV
- Power cores: 3 or 5 × 6 mm²
- Data element: Screened Cat6A, AWG23
Impedance, Attenuation & Operating Limits
- Armour: Galvanised steel wire (SWA
- Sheaths: LSZH inner, UV-resistant LSZH
- Overall diameter: 21.7 mm / 25.8 mm
- Fixed installation temp.: -30°C to +80°C
- Min. bending radius: 14 × outer diameter
EV Cat6A SWA LSZH Pair Twist, Foil & Braid Construction
The cable is a round armoured construction. The power cores and the screened Cat6A data element are laid up together, covered by a black LSZH inner sheath, galvanised steel wire armour and a UV-resistant LSZH outer sheath.
- Power cores: Class 2 stranded copper, 6 mm², with XLPE insulation; three or five cores.
- Cat6A data conductors: Class 1 solid copper, AWG23, with PE insulation, twisted in pairs.
- Data screen: Al/PET tape with a tinned copper drain wire to protect the data signal from the adjacent power cores.
- Data sheath: LSZH orange sheath over the Cat6A element for easy identification at termination.
- Inner sheath: LSZH black inner sheath over the laid-up power cores and data element.
- Armour: Galvanised steel wire armour (SWA) for mechanical protection.
- Outer sheath: UV-resistant LSZH outer sheath for external routes.
Signal Integrity, Crosstalk & Noise Rejection
- Power and data: Three- or five-core 6 mm² power with a screened Cat6A data element.
- Voltage: 0.6/1kV for power and data elements; test voltage 5000V core to core, 2000V core to screen.
- Protection: Galvanised steel wire armour with LSZH inner and UV-resistant LSZH outer sheaths.
- Temperature: -5°C to +50°C during installation; -30°C to +80°C in fixed installation.
Process Plant, Moisture, UV & Chemical Protection
- EV charging units: One cable for charger power and flow-monitoring data between the board and the charging unit.
- External wall routes: SWA and UV-resistant LSZH outer sheath for clipped runs on exposed walls.
- Tray and ladder: For specified tray or ladder routes in car parks, depots and plant rooms.
- Concrete or burial: Where direct burial or concrete installation has the required mechanical protection.
EN 50288 / PAS 5308 / Fieldbus Protocol Standards
- Listed cable references: Manufactured to IEC 60502-1, IEC/EN 60228, IEC/EN 61034-1/2, IEC/EN 60754-1/2, IEC/EN 60332-1-2 and IEC/EN 60332-3-24.
- Data and environment: Reference standards: TIA/EIA 568-B.10, IEC 61158-5, UV resistance to EN 50396 and abrasion resistance to EN 50289-3-7.
- Voltage scope: 0.6/1kV for power and data elements; test voltage 5000V core to core and 2000V core to screen.
- Approvals: Third-party certificates, CPR (EN 50575) declarations and marking requirements are confirmed and quoted per order per project specification.
Instrumentation & Industrial Bus Guides

EV Cat6A SWA LSZH Process Control & Telemetry Topology
This cable combines the power cores and a screened Cat6A twisted data cable for an electric vehicle charging unit in one armoured construction. Three- or five-core 6 mm² copper power cores rated 0.6/1kV sit together with the Cat6A element under galvanised steel wire armour, a black LSZH inner sheath and a UV-resistant LSZH outer sheath.
The data element carries the signal a charger needs for flow monitoring, for example from a current transformer at the supply point, so the installer pulls one cable instead of a power cable and a separate data cable. The armour and LSZH sheaths suit external walls, tray and ladder routes, and direct burial or concrete where the route has the required mechanical protection.
DCS, PLC, Fieldbus & Sensor Network Routes
- Workplace, fleet-depot and car-park chargers are often fed from a distribution board some distance away, and the charger needs data from the supply side as well as power. Typical examples are load management based on a current transformer at the incoming supply, or a network link to a site controller. Running both in one armoured cable saves a second containment route and a second set of glands, and the 0.6/1kV data insulation allows the data element to share the cable with the power cores.
- Choose the three-core version for single-phase chargers and the five-core version where the charger is fed three-phase. The steel wire armour gives mechanical protection for cables clipped to external walls, laid on tray or ladder, or buried where the route design allows it, and the LSZH sheaths limit smoke and corrosive gas where the cable passes through car parks and buildings. The armour must be terminated in suitable glands and bonded as the installation design requires.
EV Cat6A SWA LSZH Impedance, Grounding & Bus FAQ
What is this cable used for?
It feeds an EV charging unit with power and, in the same cable, carries the data the charger uses for flow monitoring or communication. A common use is linking a current transformer at the supply point to the charger for load management, without running a separate data cable.
Should I choose three or five power cores?
Three power cores suit single-phase chargers; five cores suit chargers supplied three-phase. Both versions use 6 mm² power cores and the same Cat6A data element, and both are listed in the dimension table with their overall diameter and weight for gland sizing.
Do I need the armoured or the unarmoured version?
Use this SWA version for external walls, burial or concrete, and routes where the cable needs mechanical protection. For protected indoor routes theunarmoured Cat6A LSZH versionis lighter and smaller.
How does it compare with the CAT5e armoured cable?
TheSWA power and CAT5e data cableuses a CAT5e data element and PVC sheaths. This cable uses a screened Cat6A element and LSZH sheaths, which suits car parks and buildings where low smoke and zero halogen is specified.
What should I send for a quotation?
Send the number of power cores, quantity and cut lengths, the installation route (wall, tray, burial or concrete), the charger type and any CPR class or marking your project requires.
TEBAOFLEX® — Electrical and environmental data
| Parameter | Value |
|---|---|
| Voltage | Power 0.6/1kV; data 0.6/1kV |
| Test voltage | Core to core 5000V; core to screen 2000V |
| Installation temperature | -5°C to +50°C |
| Fixed installation | -30°C to +80°C |
| Minimum bend radius | 14 × outer diameter |
| Power conductors | Class 2 stranded copper, XLPE |
| Data conductors | Class 1 solid copper, PE insulation, screened Cat6A |
| Data screen | Al/PET tape with tinned copper drain wire |
| Armour / sheath | SWA; LSZH inner and UV-resistant LSZH outer sheath |
TEBAOFLEX® — Cable dimensions
| Power cores | CSA | Data | Overall diameter | Weight | Pulling tension |
|---|---|---|---|---|---|
| 3 | 6mm² | AWG23 Cat6A | 21.7mm | 1002kg/km | 568N/mm² |
| 5 | 6mm² | AWG23 Cat6A | 25.8mm | 1479kg/km | 909N/mm² |
TEBAOFLEX® — Electrical characteristics
| Power DC resistance | Data DC resistance | Mutual capacitance | Inductance | L/R ratio | Current at 30°C |
|---|---|---|---|---|---|
| 3.4Ω/km | 9.38Ω/100m | 1000nF/km | 115mH/km | 1µH/Ω | 60A air / 54A clipped / 44A trunking / 46A |
Selection guide: current and data ratings depend on the installation method and conductor temperature. The current values in the table are given at 30°C; ask our engineers to confirm the rating for your route, grouping and ambient temperature before ordering.
Ordering & Quotation Checklist: Send the core count, length, installation route, charger type and any CPR or marking requirement.
Request Quotation & Datasheet for This Cable
Need factory pricing, cross-section drawing or a full PDF datasheet for EV Charging Power + Cat6A Data SWA LSZH Cable 0.6/1kV, 3 or 5 × 6mm²? Share your core count, conductor size, length and destination country—our Taicang cable engineers reply within 24 hours.
- ISO 9001 Factory Direct
- MOQ 50 m (Custom Builds)
- 24h Engineering Reply