How to Choose an RS-485 Cable: Impedance, Capacitance, Gauge and Distance

RS-485 cable selection: 120 Ω impedance, low capacitance, twisted pairs and shielding, distance vs baud rate, Modbus, PROFIBUS and CAN differences, what to order.

An RS-485 cable is a twisted-pair cable with a characteristic impedance of 120 Ω, the lowest capacitance the budget allows, and, in a plant, an overall foil-and-braid shield. Those three properties, together with the conductor gauge, decide how far and how fast a Modbus RTU or other RS-485 bus can run before the data turns into the electrical equivalent of a phone call from inside a tunnel. This guide explains what each parameter does, how far a bus can run at each data rate, why a PVC control cable is not a substitute for a 120 Ω cable, and what to write on the purchase order. It covers cable selection only; termination and grounding follow the instructions of the device manufacturer.

Cutaway of a one-pair RS-485 cable showing the twisted pair, drain wire, foil shield, tinned copper braid and outer jacket
Figure 0. Inside a one-pair 120 Ω data bus cable: polyethylene-insulated twisted pair, drain wire, foil shield, tinned copper braid and jacket.

TEBAOFLEX ENGINEERING ROUTE

Not sure which construction your bus needs?

Send the bus length, baud rate, node count and environment to the TEBAOFLEX cable engineering service. You get back a construction proposal for a 120 Ω RS-485 data bus cable together with the datasheet for the construction offered.

Ask the engineering team →

What does an RS-485 cable have to do?

An RS-485 cable carries a differential signal between up to 32 unit loads on one twisted pair terminated at both ends with 120 Ω. TIA/EIA-485-A defines the driver and receiver electronics; the TI RS-485 Design Guide (SLLA272D) gives the practical limits as 4,000 ft (about 1,200 m) at 100 kbps and 40 ft at 10 Mbps.

The standard defines the electronics, not the cable. What it asks of the cable follows from the physics of a differential line: the two conductors must be twisted so that interference hits both equally and cancels at the receiver, the line must present the same impedance the terminators are built for, and it must not load each bit edge with so much capacitance that the driver runs out of time. The design guide describes the typical industrial RS-485 cable as a sheathed, unshielded twisted pair with a characteristic impedance of 120 Ω and 22–24 AWG conductors; most plant installations add a shield on top of that, for reasons covered below.

Why must the characteristic impedance be 120 Ω?

Characteristic impedance must match the 120 Ω termination resistors fitted at each end of an RS-485 bus. A mismatch reflects part of every signal edge back along the line, where it adds to or subtracts from the next bit. Industrial RS-485 cables are therefore specified at 120 Ω nominal, typically ±10 %, as the Belden 9841 datasheet (2013) shows.

Impedance is a property of the cable’s geometry and insulation, not of its conductor size. Two conductors spaced by a thin, low-permittivity insulation such as polyethylene give a high impedance; the same conductors packed closely in PVC give a low one. That is why a general-purpose PVC screened twisted-pair control cable, however good it is at carrying 24 V DC signals, measures nowhere near 120 Ω: the Lapp UNITRONIC LiYCY (TP) datasheet 0035131 lists 76 Ω at 1 MHz for the 0.14 mm² size and 55 Ω for the 1.5 mm² size, with 62–93 Ω at 100 kHz (Lapp data, retrieved September 2026). The mismatch matters most on the fast edges of each bit, so a short link at 9,600 baud often tolerates it and the same cable fails at 200 m or at 115.2 kbaud. Figure 1 shows the difference.

RS-485 termination: matched 120 ohm cable versus a mismatched low-impedance cable
Figure 1. Matched termination on a 120 Ω cable absorbs each bit edge; the same 120 Ω terminators on a 60–75 Ω PVC control cable reflect part of the edge back along the line.

How much capacitance is acceptable in an RS-485 cable?

Lower capacitance is better for RS-485 at every length and baud rate. Installer guidance converges on 60 pF/m or less between conductors (ModbusCloud RS485 cable selection guide, 2026). Capacitance and length together set the electrical load the driver must charge on every bit edge, so a high-capacitance cable shortens the usable bus at any given baud rate.

Capacitance is the cable’s habit of hoarding charge, a little like the colleague who holds every reply until Friday: the bus still works, just later than the receiver expected. The datasheet figure to compare is conductor-to-conductor capacitance, usually quoted in pF/m or pF/ft at 1 kHz. Table 1 puts the three cable families a buyer is likely to meet side by side. The gap is not subtle: a dedicated RS-485 cable with polyethylene insulation sits around 42 pF/m, a data-grade Ethernet pair around 50 pF/m, and a PVC control cable at two to three times that.

Table 1. Conductor-to-conductor capacitance of three cable families used on RS-485 buses
Cable family Insulation Capacitance, conductor to conductor Characteristic impedance Published source
Dedicated 120 Ω RS-485 cable (Belden 9841 class) Polyethylene 42.0 pF/m (12.8 pF/ft) 120 Ω nominal Belden 9841 metric datasheet, 2013
CAT5e / CAT6 data cable Polyethylene or polyolefin About 50 pF/m 100 Ω ModbusCloud, 2026
PVC screened twisted-pair control cable (LiYCY (TP) type) PVC 95–135 pF/m depending on cross-section 55–76 Ω at ≥ 1 MHz Lapp UNITRONIC LiYCY (TP) datasheet 0035131, retrieved September 2026

Values are the manufacturers’ published nominal figures for the products named and are quoted for comparison only.

What wire gauge does an RS-485 cable need?

24 AWG (0.22 mm²) is the common conductor size for RS-485 cables and covers most low-baud buses up to 1,200 m. 22 AWG (0.34 mm²) is chosen for long runs, high ambient temperatures, or a pair that also carries device power. The TI design guide describes 22–24 AWG twisted pair as typical.

Gauge decides DC resistance, and resistance decides how much of the driver’s voltage swing survives to the far end once the terminators are drawing current. It also sets how much voltage is lost if the pair doubles as a supply for field devices, which is common on meter and sensor buses. The conversion between AWG and mm² is a frequent source of ordering errors, so state both on the order: 24 AWG is 0.205 mm² by the AWG formula and is usually listed as 0.22 or 0.25 mm² in European catalogs, and 22 AWG is 0.326 mm², listed as 0.34 mm². For any other gauge, see our AWG to mm² converter and wire gauge chart.

Table 2. Conductor sizes used in RS-485 and twisted-pair signal cables
Size Nominal area Conductor resistance at 20 °C, published Choose this when
RS-485 cable 24 AWG 0.22–0.25 mm² 78.7 Ω/km nominal (Belden 9841, 7×32 tinned copper); 94.2 Ω/km max for 0.23 mm² (Lapp LiYCY (TP) A datasheet, 2026) Standard bus runs at 9.6–115.2 kbaud up to about 1,200 m; compact cable trays and glands
RS-485 cable 22 AWG 0.34 mm² 59.4 Ω/km max (Lapp, 0.34 mm²) Runs near the length limit, elevated ambient temperature, or a pair that also feeds device power
Signal cable 20 AWG 0.5 mm² 36.7 Ω/km max (Lapp, 0.5 mm²) Power-and-data hybrids where the supply current, not the signal, sets the conductor size

Resistance figures are taken from the named manufacturers’ published datasheets; the conductor resistance of a TEBAOFLEX construction is stated on its own datasheet.

How far can an RS-485 cable run?

RS-485 runs about 1,200 m (4,000 ft) at up to 100 kbps on 22–24 AWG, 120 Ω twisted-pair cable, according to the TI RS-485 Design Guide. Above 100 kbps the usable length falls with the data rate, to about 12 m (40 ft) at 10 Mbps. Modbus RTU at 9,600 or 19,200 baud sits inside the 1,200 m region.

Every bus has a Monday-morning limit, and for RS-485 it is the point where cable attenuation and capacitance have rounded the bit edges so far that the receiver can no longer tell a one from a zero. The TI guide places that point, for 22 AWG 120 Ω cable, at roughly 1,200 m, where the line has cost the signal about 6 dB. Table 3 gives the working figures. The PROFIBUS DP rows use the segment lengths from IEC 61158-2 for Type A cable, which shares the RS-485 physical layer but specifies a 150 Ω cable, so treat them as an indication of how quickly length collapses at megabit rates rather than as RS-485 limits.

Table 3. Data rate versus usable cable length for RS-485 buses
Data rate Usable length Basis
Up to 100 kbps (Modbus RTU 9.6–115.2 kbaud) About 1,200 m (4,000 ft) TI SLLA272D, 22–24 AWG, 120 Ω cable, terminated both ends
187.5 kbit/s 1,000 m PROFIBUS DP segment limit, IEC 61158-2 Type A cable (indicative)
500 kbit/s 400 m PROFIBUS DP segment limit (indicative)
1.5 Mbit/s 200 m PROFIBUS DP segment limit (indicative)
3–12 Mbit/s 100 m PROFIBUS DP segment limit (indicative)
10 Mbps About 12 m (40 ft) TI SLLA272D

PROFIBUS figures as summarised by SCADA Protocols, PROFIBUS cable types A, B and C, retrieved September 2026. All lengths assume correct termination and a cable that meets the specification; stubs, unterminated branches and mismatched cable shorten them.

Does RS-485 need a shielded cable?

RS-485 does not require a shield electrically: TIA/EIA-485-A works over unshielded twisted pair, and the TI design guide describes UTP as typical. In industrial plants an overall foil with a tinned copper braid and drain wire is the normal choice, because it suppresses capacitive coupling from nearby power and drive cables. For when a tinned conductor or braid is worth specifying, see our copper conductor guide. Connect the shield as the device manufacturer specifies.

Twisting handles magnetically induced noise, because both conductors pick up the same disturbance and the receiver subtracts it. Capacitively coupled noise from a parallel 400 V motor cable is a different animal, and the foil is what stops it. The braid adds mechanical robustness and a low-resistance path for the drain wire; the Belden 9841 construction, to take one published example, uses a 100 % foil with a 90 % tinned copper braid and a 24 AWG drain wire. Where the bus shares a tray with variable-speed drives, the shield is not optional in practice, whatever the standard says.

Two-wire or four-wire RS-485: one pair or two?

Two-wire (half-duplex) RS-485 uses one twisted pair plus a signal common conductor; four-wire (full-duplex) RS-485 uses two twisted pairs plus common. Choose a one-pair shielded cable with a drain wire or third conductor for half-duplex Modbus RTU and BACnet MS/TP, and a two-pair cable for full-duplex links or a spare pair.

The signal common is the conductor most often forgotten on the order. TIA/EIA-485-A receivers tolerate a common-mode range of −7 V to +12 V, and without a common reference between nodes that range is easily exceeded when devices sit on different earth potentials. On a shielded cable the drain wire can serve as the common; on an unshielded cable a third conductor is needed. Figure 2 shows the two arrangements and the cable each one needs.

Two-wire half-duplex RS-485 on one twisted pair versus four-wire full-duplex RS-485 on two twisted pairs
Figure 2. Two-wire (half-duplex) RS-485 needs one pair plus a common; four-wire (full-duplex) needs two pairs plus a common.

Modbus RTU, PROFIBUS DP, CAN bus and DeviceNet: is it the same cable?

Modbus RTU, CAN bus and DeviceNet all specify a 120 Ω cable, but PROFIBUS DP Type A specifies 150 Ω nominal (135–165 Ω at 3–20 MHz) with capacitance of 30 pF/m or less, so a PROFIBUS cable is not interchangeable with a generic RS-485 cable. Check the protocol’s cable specification before ordering, not just the connector.

Table 4 collects the cable requirements of the four buses most often confused with each other. The Modbus and CAN figures are close enough that a good 120 Ω, low-capacitance shielded pair can usually serve both, provided the capacitance limit of ISO 11898-2 is respected and the manufacturer confirms it. PROFIBUS is the exception in the group: its 150 Ω, 30 pF/m Type A cable is a different design, usually with a solid 0.64 mm conductor and a violet jacket, and it should be bought as a PROFIBUS cable.

Table 4. Cable requirements of RS-485-family and related fieldbuses
Bus Specification basis Characteristic impedance Capacitance Conductor Shield Specify this cable when
RS-485 / Modbus RTU / BACnet MS/TP TIA/EIA-485-A; Modbus over Serial Line specification 120 Ω Not fixed by the standard; guides recommend ≤ 60 pF/m 22–24 AWG twisted pair Optional under TIA/EIA-485-A; the Modbus serial-line specification calls for shielded twisted pair; foil + braid in plants PLC, meter, HVAC and building-management serial networks
PROFIBUS DP Type A IEC 61158-2 150 Ω nominal (135–165 Ω at 3–20 MHz) ≤ 30 pF/m 0.34 mm² (22 AWG) solid, 0.64 mm Foil + braid, ≥ 60 % coverage; violet jacket PROFIBUS DP networks; buy certified Type A cable, not a generic RS-485 cable
CAN bus (CANopen, J1939) ISO 11898-2 120 Ω (108–132 Ω permitted) ≤ 75 pF/m; typically about 30 pF/m 0.25–0.34 mm², at least one twist per 25 mm Optional; recommended in industrial environments Machine and vehicle CAN networks; confirm the capacitance limit with the cable manufacturer
DeviceNet ODVA DeviceNet cable specification 120 Ω Per ODVA Thick trunk / thin drop constructions Per ODVA DeviceNet trunk and drop lines; buy ODVA-conformant cable

PROFIBUS values as summarised by SCADA Protocols; CAN values as summarised by Kvaser, CAN physical layers; DeviceNet per the ODVA DeviceNet cable guide. All retrieved September 2026. Consult the standard text before specifying a certified network.

Can you use CAT5e or CAT6 cable for RS-485?

CAT5e and CAT6 cable can carry RS-485 over short, low-speed links: the pairs are twisted and capacitance is about 50 pF/m, but the characteristic impedance is 100 Ω rather than 120 Ω and the 24 AWG conductors are usually solid. Expect reflections at the terminators and a shorter maximum distance; installer guides treat it as a temporary measure (ModbusCloud, 2026).

The 100 Ω figure is the whole story. Ethernet cable is optimised for a 100 Ω system, and an RS-485 bus terminated with 120 Ω at each end sees a 20 % mismatch on every edge. On a 30 m link between two cabinets at 9,600 baud it will almost certainly work. On a 600 m run through a plant it is the first thing an engineer will be asked to replace, and by then the labour costs more than the cable did.

LiYCY (TP) or a dedicated 120 Ω RS-485 cable?

LiYCY (TP) is a PVC-insulated, braid-screened twisted-pair control cable built to VDE 0812 for low-frequency signals, with a published impedance of 55–76 Ω at 1 MHz and 95–135 pF/m capacitance (Lapp datasheet 0035131, September 2026). Use it for short, low-baud serial links inside a cabinet; use a 120 Ω RS-485 cable for any bus that runs hundreds of meters.

The question comes up because LiYCY screened control cable is already on most panel builders’ shelves, and it carries RS-232 and short RS-485 links perfectly well. Its strengths are elsewhere: many pairs in one sheath, DIN 47100 colour coding, a 350–500 V working voltage and a robust tinned copper braid. None of those help a 500 m Modbus trunk, and the impedance and capacitance figures actively hurt it. Table 5 sets the two constructions side by side and says which to choose when.

Table 5. PVC screened control cable versus a dedicated 120 Ω RS-485 cable
Parameter LiYCY (TP), typical published values Dedicated 120 Ω RS-485 cable, Belden 9841 class Choose this when
Insulation PVC Polyethylene —
Characteristic impedance 55–76 Ω at ≥ 1 MHz; 62–93 Ω at 100 kHz 120 Ω nominal Any terminated bus longer than a cabinet: 120 Ω cable
Capacitance, conductor to conductor 95–135 pF/m 42.0 pF/m Long runs or baud rates above 38.4 k: the low-capacitance cable
Conductor Bare copper fine strands, 0.14–1.5 mm², IEC 60228 class 5 24 AWG 7×32 tinned copper —
Screen Tinned copper braid 100 % foil + 90 % tinned copper braid + drain Trays shared with drives: foil + braid
Working voltage 350 V (0.14 mm²) / 500 V (≥ 0.25 mm²) 300 V RMS (UL CM) —
Temperature range −40 °C to +80 °C fixed; −5 °C to +70 °C flexing −30 °C to +90 °C Ovens and engine rooms: check the fixed and flexing ratings separately
Best use Multi-pair signal and RS-232 wiring inside cabinets and machines; short RS-485 links at low baud RS-485, Modbus RTU and other 120 Ω serial buses over plant distances Short and slow: LiYCY (TP). Long, fast or noisy: 120 Ω cable

LiYCY (TP) values from the Lapp UNITRONIC LiYCY (TP) datasheet 0035131 and product information DB0066202; Belden 9841 values from the Belden metric datasheet (2013). Both retrieved September 2026 and quoted for comparison only.

TEBAOFLEX 120 Ω RS-485 data bus cable: the construction offered

TEBAOFLEX is the trade name of Jiangsu Tebaoflex Special Cable, a special-cable manufacturer in Taicang, Jiangsu, China. As of September 2026 the company builds a 120 Ω RS-485 data bus cable to the design rules in this guide, in one-pair and two-pair constructions with 24 AWG or 22 AWG conductors, confirmed per order. The datasheet for the construction offered, with its impedance, capacitance and conductor resistance and the test method used, is issued with the quotation.

The construction follows the physics explained above rather than any particular brand: polyethylene insulation for the 120 Ω impedance and low capacitance, tinned copper strands for corrosion resistance at the terminals, an overall foil for capacitive shielding, a tinned copper braid for mechanical robustness and a low-resistance drain path, and a jacket chosen for the installation. Where a project needs a different jacket compound, pair count or conductor size, the same design rules apply and the engineering team confirms the values for that variant.

Table 6. TEBAOFLEX RS-485 Data Bus Cable 120 Ω: design specification
Parameter Specification Basis
Characteristic impedance 120 Ω ±10 % TIA/EIA-485-A termination; value on the datasheet of each construction
Capacitance, conductor to conductor 60 pF/m or less, target Installer guidance for RS-485 buses; value on the datasheet
Conductor Stranded tinned copper, 24 AWG (0.22 mm²) or 22 AWG (0.34 mm²) IEC 60228 conductor class and resistance stated on the datasheet
Insulation Polyethylene Impedance and capacitance design
Pairs One pair (two-wire buses) or two pairs (four-wire buses or a spare) Bus topology
Shield Overall foil plus tinned copper braid with drain wire Industrial installations alongside power and drive cables
Jacket PVC, LSZH or oil-resistant compound, by installation Route and building requirements
Flame test IEC 60332-1-2 Test report supplied with the datasheet

Design specification as of September 2026. Values measured on the construction ordered are given on its datasheet; certifications and listings are confirmed per construction and market, see the questions below.

How do you specify and order an RS-485 cable?

Specify an RS-485 cable by writing down the bus topology and environment first and the cable parameters second: number of pairs, conductor size, shield, jacket material, temperature range, and the length per drum. The seven steps below produce a purchase-order line that a manufacturer can quote without a follow-up call.

  1. State the bus. Protocol (Modbus RTU, BACnet MS/TP, CAN, DeviceNet, PROFIBUS), two-wire or four-wire, highest baud rate, total trunk length and node count. This decides pair count, impedance and the capacitance ceiling.
  2. Choose the pair count. One pair plus drain for half-duplex; two pairs for full-duplex or a spare. Add pairs only for a defined use; every extra pair adds diameter and cost.
  3. Choose the conductor size. 24 AWG for standard runs; 22 AWG for runs near 1,200 m, hot locations or a pair that also carries device power. Stranded tinned copper terminates more reliably in screw and spring terminals than solid conductors.
  4. Specify the shield. Foil plus tinned copper braid with a drain wire for plant installations; foil only is acceptable in clean, low-noise environments.
  5. Match the jacket to the route. PVC for general indoor use, low-smoke zero-halogen (LSZH) where the building code or the end customer requires it, and an oil-resistant compound for machine tools. Cables routed near ovens or engine rooms need the fixed and flexing temperature ratings checked separately; the high-temperature wire guide explains how those ratings are defined.
  6. Fix the drum length. Splices on an RS-485 trunk are impedance discontinuities, so order drum lengths that cover each segment in one piece and ask the manufacturer for the standard drum lengths of the chosen construction before fixing the segment plan.
  7. Ask for the measured values. Request the impedance, capacitance and conductor resistance of the exact construction, with the test method and frequency, and keep the datasheet with the commissioning records.

What is the minimum order for a custom RS-485 cable?

TEBAOFLEX accepts orders from 50 m for standard and custom constructions alike, as of August 2026; unit price varies with the ordered quantity. Confirm the current minimum with the sales team when the construction is agreed, because a special jacket compound can change the practical run length.

How long does an RS-485 cable order take?

Standard lead time at TEBAOFLEX is 7–45 working days as of August 2026, depending on the product type, stock position and customisation. A written quotation states the lead time for the specific construction; confirm it with the sales team before committing to a commissioning date.

Is TEBAOFLEX RS-485 cable UL listed or VDE approved?

As of August 2026, the UL and cUL certificates held by TEBAOFLEX cover flexible cords under UL 62 and CSA C22.2 No. 49, and its VDE approval covers flexible power cables under EN 50525-2-21; neither scope includes this data cable. Projects that need a listed data cable should ask the engineering team which test report applies before specifying it.

Sample availability and freight terms are confirmed by the sales team at quotation.

RS-485 cable FAQs

What is the maximum length of an RS-485 cable?

About 1,200 m (4,000 ft) at data rates up to 100 kbps on 22–24 AWG, 120 Ω cable with terminators at both ends, according to the TI RS-485 Design Guide. The usable length falls as the data rate rises, to about 12 m at 10 Mbps, and any stub, splice or mismatched cable section reduces it further.

Does an RS-485 cable have to be shielded?

No. TIA/EIA-485-A works over unshielded twisted pair. A foil-and-braid shield is specified in industrial installations because it blocks capacitive coupling from nearby power and drive cables, which twisting alone does not remove. Connect the shield as the device manufacturer instructs.

What gauge wire is used for RS-485?

24 AWG (0.22 mm²) stranded tinned copper is the common conductor size for RS-485 cable, and the TI design guide describes 22–24 AWG as typical. 22 AWG (0.34 mm²) is used for runs near the 1,200 m limit, higher ambient temperatures, or a pair that also supplies power to field devices.

Can CAT6 cable be used for RS-485?

For short links at low baud rates, yes. CAT6 is a 100 Ω cable, so an RS-485 bus terminated with 120 Ω sees a 20 % impedance mismatch at each end; over long runs or at higher rates the reflections cause errors, and a 120 Ω cable should be used.

Is CAN bus cable the same as RS-485 cable?

Both specify 120 Ω characteristic impedance and twisted pairs, and a low-capacitance shielded 120 Ω cable can often serve either. ISO 11898-2 sets a capacitance limit of 75 pF/m for CAN cable, so confirm the capacitance figure with the manufacturer before using an RS-485 cable on a CAN network. PROFIBUS cable, at 150 Ω, is not interchangeable with either.

Your PLC was bought to run a production line, not to reboot a serial link at three in the morning. Send the bus length, baud rate, node count and environment through the TEBAOFLEX contact route or the cable engineering service, and you will receive a construction proposal with the measured impedance and capacitance of the cable offered, so the numbers on the datasheet are the numbers in the trench.

More Guides from the TEBAOFLEX Engineering Team

Selection, construction and application guides published on tebaoflex-cable.com.

What Is SO Cord? Meaning, Uses and How to Read Its Markings

What Is SO Cord? Meaning, Uses and How to Read Its Markings

Learn what SO cord means, where it is used, and how to read type, AWG, conductor count and voltage markings, with a sample photo and a labeled example.

Read more
SOOW vs SJOOW vs SEOOW: What the Cord Letters Mean and Which to Specify

SOOW vs SJOOW vs SEOOW: What the Cord Letters Mean and Which to Specify

SOOW, SJOOW and SEOOW decoded letter by letter, with voltage, compound and temperature compared and NEC 400.5 ampacity for every size from 18 to 2 AWG.

Read more
Oil Resistant Cable: PR I vs PR II

Oil Resistant Cable: PR I vs PR II

PR I is a 96-hour oil immersion, PR II is 1,440 hours with a higher pass mark. What the two UL ratings prove, and how to specify oil duty.

Read more
High Temp Wire Insulation: What a 200°C Rating Really Means

High Temp Wire Insulation: What a 200°C Rating Really Means

Silicone, PTFE, PFA, FEP and mica-glass compared by what limits each in service, and why the conductor plating often sets the real temperature ceiling.

Read more
Abrasion-Resistant Mining Cable for Mobile Equipment

Abrasion-Resistant Mining Cable for Mobile Equipment

Why mining cable jackets wear out on mobile equipment, how CPE, TPU/PUR and PVC compare, and how to match the jacket to trailing or reeling duty.

Read more
RFOU vs BFOU Cable: NEK 606 Designations Explained

RFOU vs BFOU Cable: NEK 606 Designations Explained

RFOU and BFOU cable designations decoded layer by layer: what R, F, O and U name, how (i) and (c) screening differs, and which IEC 60092 part applies.

Read more
Armoured and Static Mining Cable: Fixed Distribution Routes

Armoured and Static Mining Cable: Fixed Distribution Routes

Armoured mining cable suits static routes, not trailing duty, and its armour is pliable not rigid SWA. Compare fixed routes, pilot cores and standards.

Read more
PAS 5308 and BS 5308 Instrumentation Cable: Specification Guide

PAS 5308 and BS 5308 Instrumentation Cable: Specification Guide

PAS 5308-1 and -2 were withdrawn on 3 April 2024, BS 5308 in 2005. Compare Part, Type and screening, and see what to specify now.

Read more
What Does Type SHD Mean in Mining Cables?

What Does Type SHD Mean in Mining Cables?

Type SHD means Shielded Heavy Duty. See what each letter stands for, what GC, CGC and PCG add, and the MSHA rules that force every layer to exist.

Read more

Need Expert Cable Advice?

Contact our engineering team for technical consultation and a customised quotation.

Get A Quote