AWG to mm² Converter and Wire Gauge Chart (with kcmil)

Enter an AWG size, a cross-section in mm², or an area in kcmil or circular mils, and the converter returns the other units and the nearest standard sizes. Every value comes from the geometric definition of the American Wire Gauge for solid round wire.

AWG, mm² and kcmil converter

AWG 40 to 1, then 1/0 (0), 2/0 (00), 3/0 (000) and 4/0 (0000).

The converter needs JavaScript. Without it, the wire gauge chart answers every size from 40 AWG to 2000 kcmil, and the mm² to AWG chart covers 0.5 to 1000 mm².

Type a gauge as 12, #12 or 12 AWG, and the aught sizes as 1/0 to 4/0 or as 0 to 0000. For kcmil, “250”, “250 kcmil” and “250 MCM” all work. A value typed as “2.5 mm” is read as a 2.5 mm² cross-section, and the result says so.

Wire gauge chart: AWG to mm² and kcmil

This AWG chart lists every gauge from 40 AWG to 4/0 and the common kcmil sizes from 250 to 2000 kcmil. Each row gives the solid-wire diameter, the cross-section in mm² and kcmil, and the nearest and next larger IEC metric sizes.

AWG to mm² chart: solid round conductors, 40 AWG to 2000 kcmil

SizeDiameter (mm)Diameter (in)Area (mm²)Area (kcmil)Nearest IEC metric size (mm²)Next larger IEC metric size (mm²)
AWG sizes, 40 AWG to 4/0 AWG
40 AWG0.079870.0031450.0050100.009888——
39 AWG0.089690.0035310.0063180.01247——
38 AWG0.10070.0039650.0079670.01572——
37 AWG0.11310.0044530.010050.01983——
36 AWG0.12700.0050000.012670.02500——
35 AWG0.14260.0056150.015970.03152——
34 AWG0.16010.0063050.020140.03975——
33 AWG0.17980.0070800.025400.05013——
32 AWG0.20190.0079500.032030.06321——
31 AWG0.22680.0089280.040390.07970——
30 AWG0.25460.010030.050930.1005——
29 AWG0.28590.011260.064220.1267——
28 AWG0.32110.012640.080980.1598——
27 AWG0.36060.014200.10210.2015——
26 AWG0.40490.015940.12880.2541——
25 AWG0.45470.017900.16240.3204——
24 AWG0.51060.020100.20470.4040——
23 AWG0.57330.022570.25820.5095——
22 AWG0.64380.025350.32550.6424——
21 AWG0.72290.028460.41050.8101——
20 AWG0.81180.031960.51761.0220.50.75
19 AWG0.91160.035890.65271.2880.750.75
18 AWG1.0240.040300.82301.6240.751
17 AWG1.1500.045261.0382.04811.5
16 AWG1.2910.050821.3092.5831.51.5
15 AWG1.4500.057071.6503.2571.52.5
14 AWG1.6280.064082.0814.1072.52.5
13 AWG1.8280.071962.6245.1782.54
12 AWG2.0530.080813.3096.53044
11 AWG2.3050.090744.1728.23446
10 AWG2.5880.10195.26110.3866
9 AWG2.9060.11446.63413.09610
8 AWG3.2640.12858.36616.511010
7 AWG3.6650.144310.5520.821016
6 AWG4.1150.162013.3026.251616
5 AWG4.6210.181916.7733.101625
4 AWG5.1890.204321.1541.742525
3 AWG5.8270.229426.6752.632535
2 AWG6.5440.257633.6366.373535
1 AWG7.3480.289342.4183.695050
1/0 AWG (0)8.2510.324953.48105.55070
2/0 AWG (00)9.2660.364867.43133.17070
3/0 AWG (000)10.400.409685.03167.89595
4/0 AWG (0000)11.680.4600107.2211.6120120
kcmil sizes above 4/0 (diameter of a solid round wire of the same area)
250 kcmil12.700.5000126.7250.0120150
300 kcmil13.910.5477152.0300.0150185
350 kcmil15.030.5916177.3350.0185185
400 kcmil16.060.6325202.7400.0185240
500 kcmil17.960.7071253.4500.0240300
600 kcmil19.670.7746304.0600.0300400
700 kcmil21.250.8367354.7700.0400400
750 kcmil22.000.8660380.0750.0400400
800 kcmil22.720.8944405.4800.0400500
900 kcmil24.100.9487456.0900.0500500
1000 kcmil25.401.000506.71,000500630
1250 kcmil28.401.118633.41,250630800
1500 kcmil31.111.225760.11,500800800
1750 kcmil33.601.323886.71,7508001,000
2000 kcmil35.921.4141,0132,0001,000—

— No IEC metric size: the IEC 60228 sizes start at 0.5 mm², and the metric series in these charts ends at 1000 mm².

  • Values are calculated at full precision and rounded to four significant figures for display. Published tables that start from rounded diameters can differ in the last digit, as the conversion section explains.
  • A gauge describes geometry only, so the same row applies to copper and aluminum.
  • The chart lists no resistance or current values; see what this converter does not cover.

Sources: AWG definition, NBS Handbook 100, Copper Wire Tables (1966), section 2.2; ASTM B258-18(2026); kcmil to mm² constant, cross-checked with Wikipedia, “Circular mil”; chart values calculated with the formulas in How do you convert AWG to mm² and kcmil?

Which AWG is closest to 1.5, 2.5, 4 and 6 mm²?

By area, 1.5 mm² is closest to 15 AWG, 2.5 mm² to 13 AWG, 4 mm² to 11 AWG and 6 mm² to 9 AWG. Some published charts list 16, 14, 12 and 10 AWG instead, which are the nearest even gauges and are all smaller.

The gap matters. 14 AWG (2.081 mm²) has about 17 % less copper than 2.5 mm², and 12 AWG (3.309 mm²) has about 32 % more. Odd gauges such as 15, 13, 11 and 9 AWG are genuine AWG sizes, although cables are often offered in a narrower set of gauges.

The column “Smallest AWG or kcmil not smaller” shows the safe direction when you need at least the same copper area. For an mm to AWG lookup, first check whether the value is a cross-section in mm² or a wire diameter in mm. The first column of the chart is the cross-section.

mm² to AWG chart: metric nominal sizes from 0.5 to 1000 mm²

Metric size (mm²)Area (kcmil)Solid-wire diameter (mm)Calculated gauge (AWG)Nearest AWG or kcmilSmallest AWG or kcmil not smaller
0.50.98680.797920.120 AWG (0.5176 mm²)20 AWG (0.5176 mm²)
0.751.4800.977218.418 AWG (0.8230 mm²)18 AWG (0.8230 mm²)
11.9741.12817.217 AWG (1.038 mm²)17 AWG (1.038 mm²)
1.52.9601.38215.415 AWG (1.650 mm²)15 AWG (1.650 mm²)
2.54.9341.78413.213 AWG (2.624 mm²)13 AWG (2.624 mm²)
47.8942.25711.211 AWG (4.172 mm²)11 AWG (4.172 mm²)
611.842.7649.49 AWG (6.634 mm²)9 AWG (6.634 mm²)
1019.743.5687.27 AWG (10.55 mm²)7 AWG (10.55 mm²)
1631.584.5145.25 AWG (16.77 mm²)5 AWG (16.77 mm²)
2549.345.6423.33 AWG (26.67 mm²)3 AWG (26.67 mm²)
3569.076.6761.82 AWG (33.63 mm²)1 AWG (42.41 mm²)
5098.687.9790.31/0 AWG (53.48 mm²)1/0 AWG (53.48 mm²)
70138.19.441between 2/0 and 3/02/0 AWG (67.43 mm²)3/0 AWG (85.03 mm²)
95187.511.00between 3/0 and 4/03/0 AWG (85.03 mm²)4/0 AWG (107.2 mm²)
120236.812.36above 4/0250 kcmil (126.7 mm²)250 kcmil (126.7 mm²)
150296.013.82above 4/0300 kcmil (152.0 mm²)300 kcmil (152.0 mm²)
185365.115.35above 4/0350 kcmil (177.3 mm²)400 kcmil (202.7 mm²)
240473.617.48above 4/0500 kcmil (253.4 mm²)500 kcmil (253.4 mm²)
300592.119.54above 4/0600 kcmil (304.0 mm²)600 kcmil (304.0 mm²)
400789.422.57above 4/0800 kcmil (405.4 mm²)800 kcmil (405.4 mm²)
500986.825.23above 4/01000 kcmil (506.7 mm²)1000 kcmil (506.7 mm²)
6301,24328.32above 4/01250 kcmil (633.4 mm²)1250 kcmil (633.4 mm²)
8001,57931.92above 4/01500 kcmil (760.1 mm²)1750 kcmil (886.7 mm²)
1,0001,97435.68above 4/02000 kcmil (1,013 mm²)2000 kcmil (1,013 mm²)

Before ordering a metric replacement for an AWG cable, or the reverse, ask our engineers to confirm the replacement against both datasheets. The section on why 2.5 mm² has no exact AWG match explains the two columns.

Sources: values calculated from the AWG definition in NBS Handbook 100 (1966), section 2.2; metric nominal sizes, IEC 60228:2023.

What does AWG mean?

AWG stands for American Wire Gauge, the North American gauge system for solid round electrical wire. A larger AWG number means a smaller wire.

The gauge is fixed by two diameters: 0.4600 in for 4/0 (0000) and 0.0050 in for 36 AWG. The 38 sizes between them form a geometric progression, so each step changes the diameter by the 39th root of 92, about 1.1229.

Three rules of thumb follow from that ratio. Each gauge step changes the cross-section by about 26 %. Three steps roughly double or halve the area, and six steps roughly double or halve the diameter.

Gauges larger than 1 AWG are 1/0, 2/0, 3/0 and 4/0, also written 0, 00, 000 and 0000 and spoken as “one-aught” to “four-aught”. Above 4/0, conductors are named by their area in kcmil. In catalogs and drawings, “#2” and “No. 2” both mean 2 AWG.

The gauge sizes are specified today in ASTM B258, Standard Specification for Standard Nominal Diameters and Cross-Sectional Areas of AWG Sizes of Solid Round Wires Used as Electrical Conductors.

Sources: end points and ratio, NBS Handbook 100 (1966), section 2.2; rules of thumb calculated from that ratio; current standard, ASTM B258-18(2026).

What is kcmil (MCM), and what is a circular mil?

A kcmil is 1,000 circular mils, and a circular mil is the area of a circle 1 mil (0.001 in) across. MCM is the older name for the same unit, so 250 kcmil and 250 MCM are the same size.

Circular mils take π out of the arithmetic. The area of a round wire in circular mils is its diameter in mils, squared. 12 AWG, for example, is 80.81 mil across, so its area is about 6,530 cmil, or 6.530 kcmil.

In SI units, 1 cmil = π/4 × (0.0254 mm)² = 0.000506707479 mm². So 1 kcmil = 0.5067 mm², and 1 mm² is about 1.974 kcmil.

The gauge numbers stop at 4/0, so larger conductors are named directly by area. The chart covers the common kcmil sizes 250, 300, 350, 400, 500, 600, 700, 750, 800, 900, 1000, 1250, 1500, 1750 and 2000 kcmil, starting at the 250 kcmil row.

Sources: circular mil and kcmil, Wikipedia, “Circular mil” and NBS Handbook 100 (1966); kcmil and MCM, Cerrowire, Electrical FAQs, “What is the difference between kcmil and MCM?”; SI constant calculated from 1 mil = 0.0254 mm.

How do you convert AWG to mm² and kcmil?

Find the diameter from the gauge number, then the area: d = 0.005 in × 92^((36 − n)/39), and A = π/4 × d². For 1/0, 2/0, 3/0 and 4/0, n is 0, −1, −2 and −3.

The converter and both charts use these formulas:

d(in)   = 0.005 × 92^((36 − n) / 39)
d(mm)   = 25.4 × d(in)
A(cmil) = (1000 × d(in))²        A(kcmil) = A(cmil) / 1000
A(mm²)  = π/4 × d(mm)² = 0.506707479 × A(kcmil)
n       = 36 − 39 × log₉₂(d(in) / 0.005)

For mm² to AWG, the converter first finds the solid-wire diameter, d = √(4A/π). It then finds the gauge number n with the last line.

The tool and charts calculate at full precision and round only for display, to four significant figures. NBS Handbook 100 records that ASTM B258-61 rounded the formula diameters to the nearest 0.1 mil. The handbook’s other tables are calculated from those rounded diameters, and it prints derived values to four significant figures for 10 AWG and larger.

In area, tables built from rounded diameters can differ from the formula by up to about 0.25 % at 20 AWG and larger. At the finest gauges, the difference reaches about 3 %.

The figure below draws eight common AWG sizes to scale, each inside the next larger IEC metric size.

Cross-sections of 18 to 4 AWG solid conductors drawn to scale inside the next larger IEC metric sizes, from 1 mm² to 25 mm².18 AWG is 0.8230 mm², next larger IEC metric size 1 mm²; 16 AWG is 1.309 mm², next larger IEC metric size 1.5 mm²; 14 AWG is 2.081 mm², next larger IEC metric size 2.5 mm²; 12 AWG is 3.309 mm², next larger IEC metric size 4 mm²; 10 AWG is 5.261 mm², next larger IEC metric size 6 mm²; 8 AWG is 8.366 mm², next larger IEC metric size 10 mm²; 6 AWG is 13.30 mm², next larger IEC metric size 16 mm²; 4 AWG is 21.15 mm², next larger IEC metric size 25 mm².18 AWG0.8230 mm²→ 1 mm²16 AWG1.309 mm²→ 1.5 mm²14 AWG2.081 mm²→ 2.5 mm²12 AWG3.309 mm²→ 4 mm²10 AWG5.261 mm²→ 6 mm²8 AWG8.366 mm²→ 10 mm²6 AWG13.30 mm²→ 16 mm²4 AWG21.15 mm²→ 25 mm²AWG size (solid)Next larger IEC metric size
Eight common AWG sizes inside the next larger IEC metric size, drawn to the same scale (solid round conductors).

The four worked examples below show intermediate values rounded to four significant figures. The converter keeps full precision, so recalculating from the rounded values can change the last digit.

Example 1: 12 AWG to mm²

  1. Exponent: (36 − 12)/39 = 24/39 = 0.6154.
  2. Diameter: d = 0.005 × 92^0.6154 = 0.005 × 16.16 = 0.08081 in, or 2.053 mm.
  3. Area in circular mils: 80.81² = 6,530 cmil = 6.530 kcmil.
  4. Area in mm²: 6.530 × 0.5067 = 3.309 mm².
  5. Result: 12 AWG = 3.309 mm² (6.530 kcmil). The nearest IEC metric size, and also the next larger one, is 4 mm².

Example 2: 2/0 AWG to mm² and kcmil

  1. Gauge number: 2/0 means n = −1, so the exponent is (36 + 1)/39 = 37/39 = 0.9487.
  2. Diameter: d = 0.005 × 92^0.9487 = 0.005 × 72.96 = 0.3648 in, or 9.266 mm.
  3. Area in circular mils: 364.8² ≈ 133,100 cmil = 133.1 kcmil.
  4. Area in mm²: π/4 × 9.266² = 67.43 mm².
  5. Result: 2/0 AWG = 67.43 mm² (133.1 kcmil). The nearest IEC metric size is 70 mm².

Example 3: 250 kcmil to mm²

  1. Area in mm²: 250 × 0.506707479 = 126.7 mm².
  2. Area in circular mils: 250 kcmil = 250,000 cmil.
  3. Solid wire of that area: √250,000 = 500.0 mil = 0.5000 in, or 12.70 mm.
  4. Result: 250 kcmil = 126.7 mm². The nearest IEC metric size is 120 mm², and the next larger is 150 mm².

Example 4: 2.5 mm² to AWG

  1. Solid wire of that area: d = √(4 × 2.5/π) = 1.784 mm, or 0.07024 in (70.24 mil).
  2. Area in kcmil: 2.5/0.5067 = 4.934 kcmil.
  3. Gauge number: n = 36 − 39 × log₉₂(0.07024/0.005) = 36 − 39 × 0.5844 = 13.21, shown as 13.2.
  4. Result: the nearest gauge is 13 AWG (2.624 mm²), which is also the smallest gauge that is not smaller. 14 AWG (2.081 mm²) is smaller, and 12 AWG (3.309 mm²) is larger.

Sources: formula, NBS Handbook 100 (1966), section 2.2; 0.1-mil rounding under ASTM B258-61 and rounded derived values, the same handbook, note to table 1; area differences and worked examples calculated.

Why does 2.5 mm² have no exact AWG match?

Because AWG and metric conductors are two separate series. AWG steps by a fixed ratio of diameters, while metric sizes follow a rounded list of cross-sections. A metric size therefore lands between two gauges, and a chart can show only the nearest standard size, not an exact match.

That gives two answers for every metric size: the nearest size by area, and the smallest size that is not smaller. “Nearest” compares sizes by ratio, the way gauge numbers step, so 4/0 AWG (107.2 mm²) is listed nearest to 120 mm² rather than 95 mm². In the mm² to AWG chart, the two differ at 35 mm² (2 AWG and 1 AWG), 70 mm² (2/0 and 3/0), 95 mm² (3/0 and 4/0), 185 mm² (350 and 400 kcmil) and 800 mm² (1500 and 1750 kcmil).

Published charts disagree for the same reason. Some list the closest gauge, some the closest even gauge, and some always round to the smaller gauge.

The metric sizes are the nominal cross-sections of IEC 60228, the international standard for conductors of insulated cables. The standard sets a maximum resistance for each size, not an exact copper area. For the wider picture, see how electrical cables are classified.

Before ordering, ask our engineers to confirm which nominal size the cable will be made and marked in, metric or AWG.

Sources: nearest and not-smaller sizes calculated; IEC 60228:2023.

Does a stranded conductor have the same area as a solid wire?

Not exactly. An AWG size describes a solid round wire. A stranded conductor of the same size is built so that its combined strand area comes close to that figure, and its overall diameter is larger because of the gaps between strands.

Three things move the real copper area away from the chart value: the number and size of the strands, the lay (twisted strands are slightly longer than the cable) and compaction. Compaction closes the gaps and makes the conductor smaller across, not smaller in area; see compact aluminum conductors.

Metric flexible conductors to IEC 60228 are specified by a maximum resistance per size, so their geometric copper area can sit slightly above or below the nominal mm² value. For the choice of construction, see solid, stranded and fine-stranded copper.

When you replace a metric cable with an AWG cable, or the reverse, compare the maximum conductor resistance on both datasheets, not the area figure alone.

Sources: IEC 60228:2023.

Do copper and aluminum wires use the same gauge?

Yes. AWG and kcmil describe geometry, so 1/0 AWG is 53.48 mm² whether the wire is copper or aluminum. What differs is resistance: aluminum conducts less than copper, so an aluminum conductor of the same gauge has a higher resistance.

The same holds for every row of the chart, including 1/0 AWG and 2/0 AWG. For the differences between the two metals, see aluminum vs copper conductors.

Before ordering an aluminum conductor in place of copper, ask our engineers to confirm the conductor the circuit needs.

Sources: AWG definition, NBS Handbook 100 (1966), section 2.2; ASTM B258-18(2026).

What does this converter not cover?

It converts conductor geometry only. It does not give current rating, resistance, voltage drop, insulation thickness or the overall dimensions of a finished cable.

Current rating depends on insulation, installation and the applicable code; for DLO cables, see the DLO cable ampacity chart.

The converter also has these limits:

  • Range. It covers 40 AWG to 4/0 AWG, and areas from about 0.005 mm² (40 AWG) to 1,013 mm² (2000 kcmil). Outside that range, it declines and says why.
  • Other gauge systems. SWG, BWG and metric gauge numbers are not converted.
  • Stranded or compacted conductors. The result is the solid-wire area; see stranded and solid conductors.
  • Other units. Values with length or current units, such as “5 ft” or “20 A”, are refused.

Need a cable in this conductor size?

Send the conductor size in mm² or AWG, the number of cores, the length and the standard you need, and our engineers will quote a matching TEBAOFLEX cable. The quote button under a converter result copies the conversion into the inquiry form, or you can write through our contact page.

Our ranges include EV charging cables such as H07BZ5-F EV charging cable, screened control and data cables such as LiYCY, and PVC control and data cables.

We can also make a 120 Ω RS-485 data bus cable on request, with tinned copper conductors, PE insulation and a foil plus braid shield. If a drawing calls for 24 AWG data pairs, the chart gives 0.2047 mm² per conductor; for 22 AWG, it gives 0.3255 mm². Before ordering, ask our engineers to confirm the conductor size and stranding of the pairs.

Our minimum order quantity is 50 m for standard and custom cables alike. Lead time is 7–45 working days, depending on product type, stock and customization, and the written quotation confirms it.

Request a quote

These pages cover the topics next to this converter:

Frequently asked questions

What does AWG stand for?

AWG stands for American Wire Gauge, the North American gauge system for solid round electrical wire. A larger number means a smaller wire, and above 4/0, conductors are named by area in kcmil. The gauge sizes are specified in ASTM B258. See what AWG means.

Is 2.5 mm² wire 14 AWG or 12 AWG?

Neither exactly. 14 AWG is 2.081 mm², about 17 % less copper than 2.5 mm², and 12 AWG is 3.309 mm², about 32 % more. The closest gauge by area is 13 AWG (2.624 mm²). Charts that list 14 AWG pick the nearest even gauge, which is smaller. See the 2.5 mm² row.

What is 1.5 mm² in AWG, and is 4 mm² the same as 12 AWG?

1.5 mm² is closest to 15 AWG (1.650 mm²); 16 AWG is 1.309 mm², about 13 % smaller. 4 mm² is closest to 11 AWG (4.172 mm²). 12 AWG is 3.309 mm², about 17 % smaller than 4 mm², so the two are not the same. See the 1.5 mm² and 4 mm² rows.

How many mm² is 1/0 aluminum wire?

1/0 AWG is 53.48 mm² (105.5 kcmil), whether the wire is aluminum or copper. The metal changes the resistance, not the geometry. The nearest IEC metric size is 50 mm², and the next larger is 70 mm². Before ordering, ask our engineers to confirm the conductor the circuit needs. See copper and aluminum.

Is #2 wire the same as 2 AWG?

Yes. “#2” and “No. 2” are shorthand for 2 AWG. A solid 2 AWG conductor is 6.544 mm across, with an area of 33.63 mm², or 66.37 kcmil. The nearest IEC metric size is 35 mm². See the 2 AWG row of the wire gauge chart.

Which is bigger, 2 AWG or 2/0 AWG?

2/0 AWG is bigger: 67.43 mm² against 33.63 mm². The two are three gauge steps apart (2, 1, 1/0, 2/0), and three steps roughly double the area. Above 1 AWG, the more zeros a size has, the larger it is. See the 2/0 AWG row.

Sources: values calculated from the AWG definition in NBS Handbook 100 (1966), section 2.2; ASTM B258-18(2026).

What should you do next?

Use the converter for exact areas, and read both the “nearest” and the “not smaller” columns before you replace one cable with another. Check the conductor resistance and the other electrical values on the datasheet, not the area alone. On the order, state the size in both mm² and AWG. When you are ready, send the size, number of cores, length and standard to our engineers through the contact page.

Last verified: 2026-10-09, against the AWG definition in NBS Handbook 100.

Change log: 2026-10-09: first version, with the converter for AWG, mm², kcmil and circular mils, the wire gauge chart from 40 AWG to 2000 kcmil, and the mm² to AWG chart from 0.5 to 1000 mm².

Disclaimer: Figures are geometric conversions for solid round conductors and serve as preliminary estimates only. Choose a cable to the applicable installation standard and its datasheet, and have a qualified engineer confirm the choice.