YKGYFtZnyn 3.6/6 kV Steel Tape Armored Mining Cable

3.6/6 kV PVC mining power cable with class 2 compacted copper conductors, a common copper tape screen and galvanized steel tape armor. Ten configurations cover 10-185 mm² power conductors; suitable excavation inclination is up to 45°.

Overview

YKGYFtZnyn mining cable is a 3.6/6 kV power cable with PVC insulation, a common copper tape screen and galvanized steel tape armor. It supplies electrical equipment and carries power through mine distribution routes, including excavations inclined up to 45 degrees. The design uses compacted class 2 copper conductors and a red PVC outer sheath with specified flame-propagation performance.

The range covers ten three-power-core configurations from 10 to 185 mm². Each construction has its own diameter, weight and electrical data, so the complete designation matters when matching a new run to existing equipment. The configuration suffix forms part of the order description and should remain on the cable schedule, quotation and termination review.

Select this model around the required voltage, steel tape armor and installation route. The copper tape screen and steel tape armor perform different roles in the construction; both need to be considered when planning cable entries and terminations. The route also needs enough space for the minimum bend radius and appropriate support for the selected cable weight.

Use the technical sections below to compare construction, routing requirements and the complete size tables. For other equipment duties, browse the mining cable range. The YKGYFtZnyn PDF datasheet provides a compact reference for project documentation.

Construction

YKGYFtZnyn combines a common copper tape screen with galvanized steel tape armor around a three-core PVC assembly.

YKGYFtZnyn three-core cross-section schematic with copper tape screen and steel tape armor
YKGYFtZnyn three-power-core construction with a copper tape screen and steel tape armor. The illustration shows black outer-sheath coloring; the 3.6/6 kV ordering specification is red PVC.
YKGYFtZnyn 3.6/6 kV construction
ParameterValue
Power conductorsCompacted stranded copper, class 2, PN-EN 60228
InsulationSpecial PVC
Core identificationNatural-colored cores numbered 1, 2 and 3
Core assemblyPower conductors stranded around a PVC liner
Filler sheathPVC or non-vulcanized rubber
Inner sheathPVC
Common screenCopper tape
Separating sheathMolded PVC or special PVC tape
ArmorGalvanized steel tape
Outer sheathSpecial flame-retardant PVC, red
Oxygen index>29

Specify the screen and armor separately

The copper tape screen is a separate layer inside the steel tape armor. Keep both elements on the termination specification so that the entry, bonding arrangement and accessories match the ordered cable. Steel wire armor is a different construction and should not be substituted merely because the conductor size is the same.

When the filler and inner sheath use the same material, they may form one component. Confirm the final layer arrangement with the selected construction drawing before specifying stripping lengths.

Confirm the sheath color for the order

The product and cross-section illustrations use black outer-sheath coloring. The 3.6/6 kV construction is specified with a red PVC outer sheath. Include the required color and cable marking on the order.

Applications

YKGYFtZnyn is intended for 3.6/6 kV power transmission and the supply of electrical equipment in mines.

Red power cables clamped to wall supports beside closed switchgear in a sloping underground mine service gallery
Supported red power feeders along a sloping mine service gallery. Confirm the route inclination, cable weight and bend space before installation.

Match the route to the 45° installation limit

Use this construction in excavations with inclination up to 45°. A route that becomes steeper needs a separate cable selection review; a larger conductor size does not change the model's inclination limit.

Plan support and bend space together

Allow a minimum bending radius of 10 times the cable outside diameter. Review the route, support arrangement, entry position and handling equipment with the diameter and weight of the selected size. Keep the copper screen and armor termination requirements on the installation drawing.

Match the mine conditions

Before ordering, ask our engineers to confirm the mine-area classification, route inclination, fixing arrangement and required approval documentation for the project. Specify stationary distribution duty and identify any movement or pulling requirements separately.

Specifications

YKGYFtZnyn operating and installation data
ParameterValue
Operating voltage3.6/6 kV
Test voltage11 kV
Operating temperature-30°C to +70°C
Minimum bending radius10 × outside diameter
Maximum excavation inclination45°

Configuration, diameter and weight

Use the complete model and construction code when ordering. Match the entry and bend-space checks to the selected outside diameter; the configuration suffix remains part of the required cable designation.

YKGYFtZnyn 3.6/6 kV dimensions and weights
Model and cable construction (mm²)Power section (mm²)Outer diameter (mm)Weight (kg/km)
YKGYFtZnyn 3x10/101038.72298
YKGYFtZnyn 3x16/101641.52711
YKGYFtZnyn 3x25/142544.53377
YKGYFtZnyn 3x35/163547.24241
YKGYFtZnyn 3x50/185051.05022
YKGYFtZnyn 3x70/187055.05989
YKGYFtZnyn 3x95/209560.07240
YKGYFtZnyn 3x120/2212063.88272
YKGYFtZnyn 3x150/2415069.39948
YKGYFtZnyn 3x185/2718572.711978

Electrical reference data

YKGYFtZnyn 3.6/6 kV power-conductor electrical data
Power section (mm²)Resistance (Ω/km)Inductivity (mH/km)Reactance (Ω/km)
101.830.4000.126
161.150.3720.117
250.7270.3490.110
350.5240.3380.106
500.3870.3170.100
700.2680.2990.094
950.1930.2860.090
1200.1530.2780.087
1500.1240.2680.084
1850.09910.2620.082
YKGYFtZnyn 3.6/6 kV earth and current data
Power section (mm²)Earth capacitance (µF/km)Earth SC (A/km)Short circuit (kA)Current (A)
100.110.351.1566
160.110.371.8485
250.120.402.88110
350.130.414.03133
500.130.435.75160
700.140.458.05197
950.150.4710.93240
1200.150.4913.8276
1500.150.5017.25314
1850.160.5121.28360

Earth-data key: Earth capacitance means to-earth capacitance. Earth SC means to-earth short-circuit current, expressed in A/km; it is separate from the short-circuit value in kA. Before ordering, confirm the fault duration, installation arrangement, ambient temperature and load conditions for the protection and conductor-sizing calculations.

Standards

YKGYFtZnyn construction and flame-performance references
ParameterValue
PN-EN 60228Class 2 compacted copper conductor construction
PN-EN 60332-1Single-cable flame-propagation reference
PN-EN 60332-3-24 / IEC 60332-3Bunched-cable flame-propagation references
Oxygen indexOuter sheath >29
Test voltage11 kV

For a project specification, identify the required standard editions, inspection records and acceptance documents with the cable schedule. Keep flame-propagation testing distinct from the electrical test voltage.

Request Quote

Send the YKGYFtZnyn configuration, required voltage, length and quantity, installation duty, equipment connection details and sheath color. Include the protective-core, screen or armor requirements that apply to the selected construction, together with inspection requirements.

    Leave Us a Message

    Whether you need a quotation, have a technical question or want a cable recommendation, our engineers reply within 24 hours.

    You can also use our technical contact form.

    Quality Assurance

    Testing at every stage in our own workshop and laboratory, from incoming copper to the packed drum.

    Bare copper wire bobbins inspected before stranding at the TEBAOFLEX factory

    Raw Material Inspection

    Every batch of copper rod, rubber compound and reinforcing material is checked before it reaches the line.

    • Copper: conductor resistance, elongation and surface condition on incoming rod and drawn wire
    • EPR, CPE, PUR and silicone compounds: hardness, tensile strength, elongation and ageing samples from each mix
    • Suppliers and batch numbers are recorded so every drum can be traced back to its materials
    Operator monitoring an extrusion line control panel in the TEBAOFLEX workshop

    Manufacturing Process Control

    Stranding, insulation extrusion, core assembly and sheathing run under recorded process parameters.

    • Class 5/6 stranding with lay length and tension monitored for trailing and reeling flexibility
    • Continuous-vulcanisation extrusion with wall thickness and spark tests logged on every length
    • Operators sign off each stage before the cable moves to the next machine
    3.5 kV voltage withstand test station in the TEBAOFLEX laboratory

    Electrical Testing

    Finished lengths go through the routine tests required by the referenced VDE, ICEA, IEC or NEK standard.

    • Conductor resistance and insulation resistance on every length
    • Voltage withstand (3.5 kV and higher) and partial-discharge measurement in the shielded HV laboratory
    • Screen and pilot-core continuity checks for mining and reeling constructions
    Tensile testing machine for conductor and sheath samples

    Mechanical and Ageing Tests

    Samples from production are tested for the duty a mining, crane or submersible cable will actually see.

    • Tensile strength and elongation of insulation and sheath before and after ageing
    • Hot-set, ozone, oil-immersion and low-temperature bending tests
    • Constant-temperature water bath for insulation resistance of submersible constructions
    Single-cable vertical flame test chamber

    Flame Test and Final Inspection

    Before packing, the cable is checked against the order and the flame-performance requirement of its standard.

    • Single-cable vertical flame test to IEC 60332-1-2 where specified
    • Metre marking, printing, drum length and appearance inspection
    • Test report and packing list issued with every shipment